FR-E700 Modbus RTU parameters and register addressing

Drives and motion Published 5 min read

Short answer

Configure the FR-E700 for Modbus RTU by setting Pr117=1, Pr118=3 for 9600 baud, Pr119=0, Pr120=2 for even parity, Pr340=1 and Pr79=2, then wire the RS-485 A/B pair. Every register the master uses is the documented 4xxxx reference minus 40001: setting frequency 40014 becomes address 13, motor control 40009 becomes 8, output frequency 40201 becomes 200.

On this page
  1. Parameters to set on the drive
  2. Commission the link step by step
  3. The register address calculation
  4. Verify each layer before moving on
  5. Questions asked

To put a Mitsubishi FR-E700 on Modbus RTU you set the serial parameters in Pr117 through Pr124, put the drive under network control with Pr340 = 1 and Pr79 = 2, wire the master's RS-485 pair to the inverter terminals, and calculate every register address as the documented 4xxxx reference minus 40001. Setting frequency, documented as 40014, is protocol address 13 decimal (0x000D); motor control, documented as 40009, is address 8 decimal; output frequency feedback, documented as 40201, is address 200 decimal (0x00C8). Get those two halves right in that order and the link comes up on the first poll instead of after an afternoon of guessing.

The serial and mode settings below come from the FR-E700 instruction manuals: the basic manual covers protocol selection, and the applied manual covers the MODBUS RTU communication specifications for Pr117 and the parameters around it. Match the master to them exactly.

Parameters to set on the drive #

Parameter Value What it does
Pr117 1 Slave address 1
Pr118 3 9600 baud
Pr119 0 8 data bits, 1 stop bit
Pr120 2 Even parity
Pr121 9999 Communication check/retry function inactive
Pr122 9999 Communication error function inactive
Pr123 9999 Response wait/retry setting inactive
Pr124 1 CR/LF termination selection
Pr340 1 Network operation mode enabled
Pr79 2 External operation mode, the final setting

The master must be configured for the same 9600 baud, 8 data bits, even parity and 1 stop bit. A parity mismatch on an FR-E700 shows up as a completely silent link, so check the parity first when nothing answers.

  1. Set the parameters in the table above on the drive, entering Pr79 = 2 last so the drive finishes in external mode with network operation enabled by Pr340 = 1.
  2. Power the drive down and back up so the new communication parameters take effect.
  3. Wire the master's RS-485 terminals to the inverter's RS-485 terminals, A to A and B to B, using the polarity designation printed at each device's terminals rather than assuming every vendor labels the pair the same way. Daisy-chain additional drives, terminate both ends of the segment, and give each drive a unique Pr117 value.
  4. Configure the Modbus master for 9600 baud, 8 data bits, even parity, 1 stop bit, and slave address 1. Modbus RTU allows one active master per segment, so disconnect or silence any other master before testing. If you are scheduling requests to several drives on the segment, the approach in the article on a Modbus RTU master polling scheduler applies here unchanged.
  5. Calculate the addresses for the registers you will use, using the rule in the next section.
  6. Build a single read of output frequency first: documented reference 40201, protocol address 200 decimal (0x00C8). If the master's configuration screen asks for the human-readable 4xxxx reference, enter 40201; if it asks for the zero-based protocol address, enter 200. Read your master's addressing convention before typing either.
  7. Once the read is stable, add the write to setting frequency, documented reference 40014, protocol address 13 decimal. Use the scaling stated in the FR-E700 register table for that register.
  8. Add the motor control word at documented reference 40009, protocol address 8 decimal. The command values from the register table are 2 for forward run, 4 for reverse run and 0 for stop.
  9. Test motor commands only when it is safe for the motor to turn. A successful write response proves the protocol layer accepted the transaction; confirm the drive state and the motor's response separately. If reads work but the drive will not start, the cause is usually the operating mode or the command word, which the article on a VFD ignoring Modbus RTU start commands from a PLC walks through.

The register address calculation #

The FR-E700 register table lists holding registers in 4xxxx notation, but the address field of a Modbus request carries a zero-based offset. The conversion is one subtraction:

protocol address = documented reference - 40001

Worked example, all three registers from this article plus the parameter-clear register from the manual:

  • Setting frequency: 40014 - 40001 = 13 decimal = 0x000D hex.
  • Motor control: 40009 - 40001 = 8 decimal = 0x0008 hex.
  • Output frequency feedback: 40201 - 40001 = 200 decimal = 0x00C8 hex.
  • Parameter clear: 40003 - 40001 = 2 decimal.

The failure mode is mixing conventions: entering 40014 where the driver expects 13, or 13 where it expects 40014, addresses the wrong location while the serial link itself is perfectly healthy. Keep both numbers in your PLC or HMI documentation, labeled.

The output-current and output-voltage feedback registers are in the same monitoring block as the output frequency register, but their references are not stated here; read them from the register table and apply the same subtraction rather than assuming they follow 40201 consecutively.

Verify each layer before moving on #

Verify reads first. Poll the output frequency register and confirm the returned value tracks the drive's actual output. If the link is stable but the value is implausible, suspect register selection, word order or scaling, not the cable.

Then verify the frequency write by reading back or watching the drive's display, and only then the control word: command forward with 2, stop with 0, and test reverse with 4 only when reverse rotation is safe. Record the slave address, function code, starting address, transmitted value, response and observed drive state for each transaction; those six fields separate a communication success from an application failure, and they are what the article on read-and-write traffic dropping VFD control on one port helps you diagnose when combined traffic starts to interfere.

One safety note: writes to the motor control register move the motor. Commission the control-word steps with the motor disconnected or the machine in a safe state, and enable motion only when the conditions around the machine permit it.

Questions asked

What do Pr121, Pr122 and Pr123 set to 9999 disable?

In this commissioning baseline all three stay at 9999, which is the value that leaves the related communication check and retry functions at their inactive factory setting rather than acting as an active timeout. Leave them at 9999 until reads and writes work, then consult the FR-E700 instruction manual (applied) chapter covering Pr117 to Pr124 before assigning any active value, because each one changes how the drive reacts to a silent or partial exchange.

Where are the output current and output voltage registers?

They sit in the same monitoring block as the output frequency register used in this article, but their exact 4xxxx references are not given here. Read them from the FR-E700 Modbus register table in the instruction manual, then apply the same rule shown for the output frequency register: subtract 40001 from the documented reference to get the protocol address the master sends.

Can several FR-E700 drives share one RS-485 segment?

Yes. Give each drive a different Pr117 slave address, wire the segment as a daisy chain with the A and B pairs in parallel, and terminate both physical ends of the segment. A Modbus RTU segment allows one active master, so poll all drives from a single master and stagger the requests; assigning duplicate addresses makes every drive on the segment answer at once and corrupts the response.

Does a successful write response prove the motor will run?

No. A normal Modbus response only proves the transaction was framed and accepted at the protocol layer. Whether the drive actually starts still depends on Pr340 and Pr79 giving the network command priority, on the commanded frequency being above the drive's minimum, and on the drive not being tripped. Confirm the drive's own indication and the motor response independently of the communication success.

Keep reading

  • Comparison

    How a PLC controls a VFD: five interfaces compared

    A PLC controls a VFD through one of five interfaces: discrete I/O, an analog speed reference such as 0-10 V or 4-20 mA, Modbus RTU or TCP, EtherNet/IP or BACnet/IP, or PROFIBUS or DeviceNet. Discrete and analog wiring carry commands only; the network interfaces also return status and fault data. Pick by how much the PLC must know about the drive, not by brand.

    Drives and motion

  • How-to

    How to commission five VFD drives on one Modbus gateway

    Prove the link in three passes: open the Modbus TCP connection to the gateway, verify one read from one drive against its own display, then run one serial transaction at a time across all five. A TCP-to-RTU gateway must serialize every RS-485 request, so schedule run commands ahead of power reads instead of polling all five at once.

    Drives and motion

  • Troubleshooting

    Fix a PowerFlex 70 start inhibit that mimics a comm fault

    A PowerFlex 70 that answers RSLinx property requests but ignores PLC commands is start-inhibited, not offline: the recorded fix was bit 5 of parameter 277 [Start Mask], cleared from 1 to 0. Read parameter 214 [Start Inhibits] and compare parameter 277 between the running and inhibited axes — a difference of exactly 16 — before replacing the 20-COMM-E or touching DataLinks.