Troubleshooting
Fix EtherNet/IP HMI access to an older SLC 5/05
Short answer
The RSLinx Ethernet driver reaches the controller because early SLC 5/05 firmware speaks CSP, the AB Ethernet protocol that predates EtherNet/IP; an EtherNet/IP HMI driver cannot open a session with it. Update the processor: a 1747-L552 Series A at OS500 Series A FRN 1 accepted a ControlFLASH update to FRN 11 and then communicated with an EtherNet/IP HMI. Updated or not, a 5/05 never accepts EtherNet/IP I/O connections.
On this page
- Why does the SLC 5/05 show in the RSLinx Ethernet driver but not in the EtherNet/IP driver?
- Which quick fixes should you rule out before touching firmware?
- What processor identity do you record before choosing an update?
- What firmware revision does the SLC 5/05 need for an EtherNet/IP HMI?
- How do you run the ControlFLASH update on the 5/05?
- What can you do when the firmware cannot be updated?
- When is replacing the processor the right call?
- Questions asked
An early SLC 5/05 speaks CSP — the AB Ethernet protocol that predates EtherNet/IP — so it browses under the RSLinx Ethernet driver and refuses every EtherNet/IP-based HMI driver at any address. The fix is firmware, not networking: a 1747-L552 Series A, Processor Revision 1, OS500 Series A, FRN 1 processor accepted a ControlFLASH update to FRN 11 on the same hardware and then communicated with an EtherNet/IP HMI. Read the full processor identity first, because the hardware series caps the revision the processor accepts. Even updated, a 5/05 carries messaging only — it never accepts EtherNet/IP I/O connections.
Why does the SLC 5/05 show in the RSLinx Ethernet driver but not in the EtherNet/IP driver? #
Early SLC 5/05 firmware speaks CSP, the AB Ethernet protocol that came before EtherNet/IP, so the RSLinx Ethernet driver reaches the processor while any EtherNet/IP-based driver cannot establish a session.
The legacy RSLinx Ethernet driver talks CSP/PCCC. The EtherNet/IP driver and HMI drivers of the same family open CIP sessions over TCP, and CSP/PCCC is not compatible with EIP/PCCC or EIP/CIP: the session establishment and the encapsulation differ on both sides. Both drivers run over the same cable and the same IP address, which is why the network looks healthy while the HMI stays dead.
A device that answers one driver and refuses another is a protocol question before it is an address question — the same class of mismatch behind DF1 reads that work on an SLC 500 but not a PLC-5. Treat the browse-list difference as the diagnosis itself, not as one more fault to chase.
Which quick fixes should you rule out before touching firmware? #
Stop changing IP addresses, HMI tag addresses, and Ethernet hardware: none of them adds a protocol the controller does not speak, and the working RSLinx path already proves the network is not the fault.
- Changing the controller's IP address. The working RSLinx browse proves the address is reachable; no address makes a CSP-only endpoint answer CIP.
- Reinstalling the HMI driver. A reinstall does not teach the component CSP, so it fails identically on a clean install.
- Editing data-file addresses in the HMI project. A bad address fails a read after a session opens; it does not stop the session from opening, which is the symptom you actually have.
- Replacing the cable, the switch, or the port. Link-level hardware is proven by the legacy session that runs over it.
- Installing a standalone CSP utility on the HMI PC. A separate executable is not an HMI communication component; wiring its code into the HMI is a software project, not an installation.
Keep the RSLinx connection alive through the diagnosis: it is your path for reading the processor identity and saving the program before any update.
What processor identity do you record before choosing an update? #
Record five identity fields before you order any update kit: catalog number, processor series, processor revision, operating-system series, and firmware revision, because the catalog number alone does not decide which firmware the hardware accepts.
- Catalog number: 1747-L552 in this class of unit.
- Processor series: Series A.
- Processor revision: 1.
- Operating-system series: OS500, Series A.
- Firmware revision: FRN 1.
Read the first two from the nameplate and controller properties; read the last three over the working RSLinx connection. Two hardware facts hang off the series field: only Series C processors support 100 Mbps Ethernet and the increased connection count, and no flash turns a Series A port into a Series C port. Record installed memory as well, because the compatibility listing ties the maximum accepted revision to the hardware, not to the kit's label.
With 1747-L552, Series A, Processor Revision 1, OS500 Series A, FRN 1 on the unit, you are holding CSP-only firmware on 10 Mbps hardware.
What firmware revision does the SLC 5/05 need for an EtherNet/IP HMI? #
OS500 Series A FRN 1 is CSP-only, and a 1747-L552 Series A, Processor Revision 1 updated to FRN 11 then communicated with an EtherNet/IP HMI driver, so FRN 11 is the demonstrated working revision for that hardware.
The SLC 5/05 supports flash-based firmware, updated through ControlFLASH. The worked numbers from one reported upgrade:
| Reading | Value | Result |
|---|---|---|
| Firmware kit label | version 13 | — |
| Revision offered for Series A hardware | FRN 11 | 13 − 11 = 2 revisions the hardware would not take |
| Processor before update | OS500 Series A, FRN 1 | EtherNet/IP HMI driver: no session |
| Processor after update | FRN 11 | EtherNet/IP HMI driver: connected and reading |
The utility read the processor identity and offered FRN 11, not the label revision, because the Series A compatibility listing capped it there. One installation reported this outcome on exactly that identity, so treat FRN 11 as a demonstrated working revision, not as a vendor-tested minimum for every 5/05 shipped. The decision for any unit sitting at FRN 1 on this hardware: flash to FRN 11, the revision the utility offered and the one proven on this identity.
What the update adds is PCCC messaging carried over the EtherNet/IP transport, which is exactly what an HMI driver needs.
How do you run the ControlFLASH update on the 5/05? #
Flash the processor over a fixed-IP or BOOTP-assigned connection — the kit's release note rules out DHCP — after you save the program and clear the Protect jumper, because ControlFLASH reports the PLC "not ready" while update protection is still set.
- Save the application and the identity readings over the working RSLinx path. If Ethernet drops along the way, DF1 on the serial channel is the fallback, with the same setup used for connecting a laptop to an SLC 500 serial port.
- Give the processor a fixed IP or a BOOTP-assigned address and write the address down; the OS501 kit's release note rules out DHCP for the update.
- Obtain the SLC 5/05 firmware kit from the manufacturer or its distributor. The kit contains the ControlFLASH program itself with several revisions, so the ControlLogix-labeled package is not what you need.
- Move the Protect jumper as the processor's update instructions direct; the utility reports the PLC "not ready" until this is cleared.
- Run the update against the recorded address, confirm the revision it offers — FRN 11 on the Series A hardware above — and do not interrupt power while it writes.
- Restore the jumper, reload the saved program, confirm the address, and point the HMI driver at it.
Plan the flash as machine downtime, not a live tweak: the controller stops for the duration, and an interrupted update can leave the processor needing recovery support. With two identical processors on the line, flash one, prove the HMI session on it, then flash the second — that keeps a verified control running while the variable changes.
What can you do when the firmware cannot be updated? #
Two real paths exist when the update is not available: run the HMI on a CSP-capable communication component, or put a protocol-converting computer between the HMI and the legacy controller.
- CSP-capable HMI component. Keep FRN 1 and use an HMI whose communication component speaks CSP natively and binds to its own controls. A standalone CSP utility does not qualify — it runs alone and does not attach to HMI objects, so using it means writing integration code.
- Conversion host. A computer beside the controller talks CSP to the 5/05 and re-serves the data on a modern protocol such as OPC UA or Modbus TCP. That host is typically an industrial mini PC mounted in the cabinet next to the controller.
If the controller must stay at FRN 1, the conversion host is the path that leaves the HMI fully modern; the CSP component only pays off if your HMI already supports it.
When is replacing the processor the right call? #
Replace the processor when the installed hardware cannot accept an EtherNet/IP-capable revision, when official recovery support for a failed flash is not available, or when the machine's maintenance plan no longer tolerates a CSP-only controller.
Treat it as an engineering change, not a communications adjustment: processor and module changes, program conversion, and readdressing. Two conditions tip the balance in practice. Hardware ceiling: if the installed series cannot accept a capable revision, no flash fixes it. Line direction: when you are already adding a second panel, standardizing both panels on one EtherNet/IP-capable controller removes two protocol worlds from future maintenance. Either way, a Series A port runs at 10 Mbps only, so the switch port in front of it must still negotiate that rate.
With a demonstrated FRN 11 path on this identity, update first; replace when the hardware refuses the revision or the line is consolidating controllers anyway.
Questions asked
Will the firmware update let the SLC 5/05 accept EtherNet/IP I/O connections from a scanner?
No. The update adds EtherNet/IP as a messaging transport for PCCC reads and writes, which is what an HMI driver needs. The 5/05 never acts as an EtherNet/IP I/O adapter, so a scanner cannot open a rack-style I/O connection to it regardless of firmware. Move that data with MSG instructions or a conversion device instead.
Why did ControlFLASH offer FRN 11 when the kit was labeled version 13?
The label names the package, not the revision your processor will accept. ControlFLASH reads the catalog number, series, and revision, then offers the highest compatible firmware from its listing. In the reported case, Series A hardware capped at FRN 11, two revisions below the kit's label, and FRN 11 is what worked.
Does the update make a Series A Ethernet port run at 100 Mbps?
No. Ethernet speed is fixed by hardware series: only SLC 5/05 Series C processors support 100 Mbps and the increased connection count. Series A and B ports stay at 10 Mbps after any flash, so confirm the switch port serving them still negotiates that rate.
Can the controller keep a DHCP address during the flash?
No. The release note for the SLC 5/05 OS501 firmware kit tells you to assign the address with BOOTP or as a fixed IP, not DHCP. Record the address before you start, because the processor must be reachable at a known address when ControlFLASH begins.