Fix an AB9006-B gateway showing only ConnectionFault

Industrial networks Published 4 min read By IMDHMI controls team

Short answer

When the AB9006-B EtherNet/IP-to-Modbus TCP gateway shows only the ConnectionFault BOOL in Controller Tags, the module was created from the wrong EDS file, in the reported case EDS_ABX_ETNM_2P-EIP_2P_V_1_3.eds. Delete the module, import the EDS published for the AB9006-B, and recreate it with 16-byte input and output connections; the data tags then generate, readable as 16 SINTs, 8 INTs or 4 DINTs.

On this page
  1. Why only the fault bit appears
  2. Delete and rebuild the module
  3. Map the connection to PLC data types
  4. Prove the fix with live data
  5. What to leave alone
  6. Questions asked

Only one BOOL, ConnectionFault, under the module tag in Controller Tags means the module in your RSLogix 5000 project was built from the wrong EDS file. The gateway itself is configured for 16 bytes of input data and 16 bytes of output data, but the file EDS_ABX_ETNM_2P-EIP_2P_V_1_3.eds does not describe the AB9006-B's cyclic connections, so the controller generates only the fault bit. Delete that module, register the EDS published for the AB9006-B from the gateway's product support page, and add the module again with the same connection sizes; the input and output arrays then appear beside the fault bit. Nothing in the gateway configuration or the PLC logic needs to change.

Why only the fault bit appears #

The EDS registered on your engineering station decides which members the controller auto-generates for a module. When the definition is wrong, the connection is built without assembly data, so the module tag carries the fault status and nothing else. The file EDS_ABX_ETNM_2P-EIP_2P_V_1_3.eds is easy to pick by mistake: it is one of several X-gateway files with near-identical EtherNet/IP-to-Modbus TCP descriptions. Similar text on the download page does not mean the file describes your part number.

The gateway side is not at fault here. Its Modbus TCP client configuration, including the transaction map, stays valid; only the PLC's picture of the adapter is wrong.

Delete and rebuild the module #

Do this with the machine stopped: deleting the module drops the connection and the outputs go to their configured fault action.

  1. Open the I/O configuration tree and note the module's name and IP address, so you can recreate both.
  2. Delete the module definition that was built from the wrong EDS.
  3. Register the EDS written for the AB9006-B, downloaded from the gateway's product support tab, using the EDS registration tool so the module catalog picks it up.
  4. Add the module again from the newly registered definition, with the same name and IP address.
  5. Set the connection to 16 bytes of input data and 16 bytes of output data, matching the gateway's own configuration of two transactions.
  6. Open Controller Tags and confirm the input and output data arrays now exist next to ConnectionFault.

Map the connection to PLC data types #

The payload size is fixed; the element type you read it with is your choice:

Representation Elements Total size
SINT 16 16 bytes
INT 8 16 bytes
DINT 4 16 bytes

The arithmetic: each SINT is 1 byte, so 16 elements fit; each INT is 2 bytes, so 16 divided by 2 gives 8; each DINT is 4 bytes, so 16 divided by 4 gives 4. Modbus holding registers are 16-bit, so INTs line up one-to-one with the registers in your transaction map and are the simplest choice. DINTs pair two registers per value, which only works if you control the word order at both ends. In this project the default 16 SINTs per direction is fine; copy bytes into typed structures in logic if you need 32-bit values.

The Module Definition dialog may show the size in bytes and grey the field out. That is the connection size the EDS fixes, not a fault and not a data-type choice.

Prove the fix with live data #

A cleared ConnectionFault proves the connection is up; it does not prove your register offsets or byte order are right:

  • Change a value in a mapped register at the Modbus TCP slave and confirm the corresponding input element changes in Controller Tags.
  • Write an output element from the PLC and confirm the value arrives in the intended register at the slave.
  • If bytes move but land one or two positions away from where you expect, the transaction map, not the EDS, is the place to correct it.

An imported EDS alone proves nothing about cyclic I/O, as the article on why an imported EDS does not prove EtherNet/IP cyclic I/O explains; the live read and write above is the evidence that counts.

What to leave alone #

  • The two-transaction configuration in the gateway: the missing tags were traced to the EDS selection, not to the transaction count.
  • Your PLC logic: nothing in it caused the symptom, and nothing in it needs to change after the module is rebuilt.
  • The greyed size field in the module definition, as described above.

If you ever replace the gateway hardware itself, the successor needs its own EDS registered the same way; the file you downloaded for the AB9006-B belongs to that adapter only.

Questions asked

Does the EDS written for the AB9006-B also cover its successor gateway?

No. The AB9006-B has been discontinued, and its current successor, the ABC3207-A, is a different EtherNet/IP adapter with its own EDS file. When you replace the hardware, register the successor's EDS and rebuild the module from that definition; do not reuse the AB9006-B file or the old module definition.

Could an older RSLogix 5000 version cause the missing data tags?

No. The module was created without issue on RSLogix 33.12 using the EDS from the gateway's product support page, and the reported case cleared on the corrected file with the software unchanged. If the tags are still missing after the correct EDS is registered, confirm the module was added from the new definition and is not a leftover copy of the deleted one.

Why is the size field in the Module Definition dialog shown in bytes and greyed out?

That field is the connection size the EDS fixes for this adapter, and the AB9006-B definition expresses it in bytes without offering a data-type choice. It is not a fault. Finish creating the module, then read the payload as SINT, INT or DINT elements in Controller Tags, or copy it into typed structures in your logic.

Keep reading

  • Selection guide

    Choosing a ControlLogix path to a Modbus TCP Schneider PLC

    ODVA Volume 7 defines how Modbus devices integrate into CIP; it is not a ControlLogix feature, so no stock 1756 Ethernet module speaks Modbus TCP natively. Choose from four paths: an in-rack or standalone gateway, Modbus TCP written over generic sockets on a 1756-EN2T at firmware 5 with RSLogix 5000 v20 (or a 1756-EWEB), an OPC bridge on a PC, or EtherNet/IP on the Schneider side where the CPU supports it.

    Industrial networks

  • Explainer

    What an S7-300 ControlLogix Ethernet gateway must do

    An S7-300 and a ControlLogix cannot talk by sharing a switch: the Logix ends CIP over EtherNet/IP and the Siemens CPU expects S7 communication over ISO-on-TCP port 102. Use a documented gateway that terminates both stacks, or the Siemens function-block EtherNet/IP driver on an S7-300 CP, then verify with a byte-order test before production.

    Industrial networks

  • Troubleshooting

    Why explicit writes to Omron assemblies fail over EtherNet/IP

    Your Set Attribute message carries service code E, which is Get Attribute Single, so it reads, succeeds and writes nothing — and the two codes are transposed, since Set Attribute Single is 10 hex. Even corrected, CS/CJ-series EtherNet/IP units do not accept explicit writes to assembly instances, because that service is optional in the specification. Carry the 240 bytes on a Generic Ethernet Module connection or use CIP Data Table Read and Write messages.

    Industrial networks

Why RSLinx shows a yellow question mark and what the EDS name means