Why RSLinx shows a yellow question mark and what the EDS name means

Industrial networks Published 8 min read By IMDHMI controls team

Short answer

The yellow question mark means RSLinx read the device identity but found no registered EDS matching it. The reported EDS file name is device metadata, not proof the file is on your PC. Get the EDS or connection sheet from the vendor, register it, or build a Generic Ethernet Module from the documented assemblies and judge the result in the controller I/O tree.

On this page
  1. Why does RSLinx show a yellow question mark on my EtherNet/IP device?
  2. Is the EDS file already on my PC if the device shows an EDS file name?
  3. Which identity values do I record before asking for the EDS?
  4. Where do I register an EDS file once I have it?
  5. What goes in a Generic Ethernet Module definition when there is no EDS?
  6. How do I confirm the connection is actually working?
  7. Why does fixing the icon not fix the I/O?
  8. What is the decision for each case?
  9. Questions asked

The yellow question mark means RSLinx read your device's CIP Identity but found no registered EDS on that PC whose vendor ID, product type, product code and revision match it. Discovery is working; the description layer is not. The file name the device reports is not on your disk. Get the EDS from the vendor, register it with the EDS tool, or bypass the EDS entirely with a Generic Ethernet Module built from the documented assembly instances and sizes — then judge success in the controller I/O tree, not by the icon. The same layer distinction is argued in why an imported EDS does not prove EtherNet/IP cyclic I/O; here we walk the fix from the browse symptom.

Why does RSLinx show a yellow question mark on my EtherNet/IP device? #

RSLinx found the device, read its identity over the network, and matched that identity against every EDS registered on the PC without a hit. The question mark is a missing-device-description symptom, not a communications fault: if the browse reached far enough to show a question mark, TCP and EtherNet/IP discovery both worked.

Separate the layers before you touch anything:

  • Browse and identity read — working, because the device answered and its properties are visible.
  • EDS registration — broken, because no registered file matches the reported vendor, product type, product code and revision.
  • Cyclic I/O connection — unknown until you check the controller's I/O tree; a clean icon and a working connection are independent.

A registered EDS removes the question mark without producing valid I/O, and a correctly defined Generic Ethernet Module exchanges I/O with no EDS at all. Treat the icon as an identification check only.

Is the EDS file already on my PC if the device shows an EDS file name? #

No. The EDS File Name entry is metadata the device itself reports — it is the file name the vendor intends for that unit, and it proves nothing about what is stored on your machine. If the matching file were registered, RSLinx would already show the vendor's icon instead of the question mark.

The same question applies to the missing upload option: some devices serve their EDS over the network and some do not, and the browse tool only offers upload when the device advertises it. Yours does not, so there is exactly one legitimate source: request the EDS package from the device vendor or its authorized distributor for your machine's fitted communication module, quoting the identity values below. Do not hunt for the file on third-party download sites; a file that carries the right name but was built for a different firmware revision will register cleanly and still describe the wrong assemblies.

Which identity values do I record before asking for the EDS? #

Record exactly what the device reports, punctuation included, and send those strings to the vendor or distributor. The values from the checked machine read:

  • Device Name: Wipotec
  • Vendor: 9999
  • Product Type: 43
  • Product Code: 1.002
  • Serial Number: 0089A76
  • EDS File Name: 270F002B00C801XX.EDS

Keep the Product Code as the device shows it — 1.002 with the dot — rather than reformatting it to 1.2 or 1002 when you write the request, because the vendor's records and the EDS header carry it in their own encoding. The file name itself encodes the identity numbers behind the scenes: vendor ID, product type, product code and major revision packed into the leading hex digits, which is why a mismatch in any one of them produces a different file name. Ask the vendor to confirm the file applies to the embedded EtherNet/IP module fitted to this machine, not to a fieldbus accessory on another variant, because a different module means a different data map.

Where do I register an EDS file once I have it? #

Register the file with the vendor's EDS Hardware Installation Tool, then restart the browse software so it reloads its description cache. The documented procedure in the registration tool is: choose Add, then select whether to register a single EDS file or a directory of EDS files, and point it at the file you received.

After registration and a restart, the question mark should become the vendor's chosen icon. That change confirms one thing only: the identity read now matches a registered description. It says nothing about whether the assemblies in the file match what the machine actually exposes. Cyclic I/O is judged in the controller, in the next step.

What goes in a Generic Ethernet Module definition when there is no EDS? #

A Generic Ethernet Module needs five fields from the vendor's EtherNet/IP connection sheet: the input assembly instance and size, the output assembly instance and size, the configuration assembly instance and size, the communication format, and the permitted requested packet interval range. Get them from the manual or the vendor — never guess, because a reachable device will simply reject every guessed connection.

The worked example below uses illustrative values to show the arithmetic; your vendor sheet decides the real ones.

Worked example (illustrative values):

Field Example value Check
Input assembly instance 0x64 (100) Decimal and hex both accepted in the module definition
Input size 16 bytes Count the full map: 4 bytes weight + 4 bytes tare + 8 bytes status/reserved
Output assembly instance 0x96 (150) From the command map
Output size 4 bytes One 32-bit command word, reserved fields included
Config assembly instance 1, size 0 bytes Only if the sheet prescribes instance 1 with no data for the no-config case
Communication format Format code from the sheet Byte-counted format needs sizes in bytes; a word-counted format needs sizes in 16-bit words
RPI 20 ms Inside the range the sheet declares; do not tune until the connection opens

The arithmetic that bites people is the size check. If the sheet's input map lists weight (4 bytes), tare (4 bytes), gross (4 bytes) and two reserved status bytes, the input size is 4 + 4 + 4 + 2 = 16 bytes — not 12, and not 8 words. If you enter the communication format as word-counted while the sheet's sizes are bytes, the module requests 16 words where the device offers 16 bytes and the connection is refused. Count every reserved field the map lists; the connection needs the whole image even when your logic uses only the weight.

How do I confirm the connection is actually working? #

Judge the connection in the controller's I/O tree, then prove the data, in that order:

  1. Enter the device's IP address in the module definition exactly as RSLinx shows it, download the project, and read the module's connection status in the I/O tree. Resolve any displayed error code before touching application logic.
  2. Keep command outputs inactive during the first test, then monitor the raw input assembly while you place a known weight on the platform. Note which bytes change and compare the pattern with the vendor's data map — weight, status bits, signedness and byte order.
  3. Fire one permitted command output at a time and confirm both the machine's response and the returned status bit.
  4. Cycle power on the controller connection and the machine's communication interface and confirm the I/O connection returns without a project edit.

If you need to pull non-cyclic data such as identity or register values without disturbing the implicit connection, explicit messaging does that job; the method is laid out in read EtherNet/IP module register data with explicit messaging.

Why does fixing the icon not fix the I/O? #

Because EDS registration and cyclic I/O sit on different layers, and each has its own failure mode. When the I/O tree still faults after the icon looks right, the mismatch is almost always one of four things: an assembly instance number entered differently on the two sides (decimal 100 versus hex 0x64 confusion), a size in the wrong unit, a communication format the device does not accept for those assemblies, or the device-side fieldbus settings not set to EtherNet/IP with the data image your project assumes. An I/O connection fault on one device type but not others is the same pattern seen in EtherNet/IP remote I/O fails on one controller, not another.

What is the decision for each case? #

Commit to one path based on what the vendor supplies:

  • Vendor supplies the EDS — record the identity, register it with the EDS Hardware Installation Tool, restart, and confirm the icon. Then build the module from the connection sheet anyway, because the icon never validated the assemblies.
  • Vendor supplies a connection sheet but no EDS — skip the EDS. Build a Generic Ethernet Module with the documented instances, sizes, format and RPI, and treat the yellow question mark as cosmetic. A stable I/O connection with correctly decoded weight outranks any icon.
  • Vendor supplies neither — escalate to the vendor in writing with the six identity values above and a request for the connection sheet or the file matching 270F002B00C801XX.EDS. Do not guess assemblies; a reachable device rejects every guess and the machine stays down.
  • Icon fixed but I/O faulting — work the four mismatches in the previous section, size units first.

One safety note: keep command outputs inactive until you have decoded the input map against the vendor's documentation, because a mapping mistake on the output assembly can issue an unintended machine command on a live checkweigher line.

Questions asked

Does the yellow question mark mean my network or cable is faulty?

No. The icon only means the identity RSLinx read did not match a registered EDS on that PC. To see the device at all, EtherNet/IP discovery over TCP already worked, so cabling, IP addressing and the switch are functioning. Fix the description layer by registering the vendor EDS, not the network layer.

Can I leave the yellow question mark if my Generic Ethernet Module connects?

Yes. The icon is cosmetic on the RSLinx side and does not affect the controller's implicit connection. A Generic Ethernet Module with the correct assembly instances, sizes and format exchanges I/O without any registered EDS. Registering the EDS later improves the display and documentation, nothing more.

What do I do if the vendor cannot supply the EDS at all?

Ask for the EtherNet/IP connection sheet from the communication module manual instead: input, output and configuration assembly instances, their sizes in the declared units, the communication format and the permitted requested packet interval range. A Generic Ethernet Module built from that sheet connects the device without an EDS.

Why does my EDS-backed module still show a connection fault in the I/O tree?

The EDS only supplies the description. A connection fault means the controller's requested assembly instances, sizes, communication format or RPI disagree with what the device accepts, or the device-side fieldbus settings differ. Count the full assembly image including reserved bytes, and match the format before changing the RPI.

Keep reading

  • How-to

    Set up a PSTX softstarter on EtherNet/IP with a ControlLogix

    Set parameter group 12 on the PSTX first: 12.02 FB interface connector to Anybus, 12.03 Fieldbus control to On, and a static address in 12.05, 12.06 and 12.07 with 12.08 DHCP OFF. Then add a Generic Ethernet Module in Studio 5000 with input assembly instance 100 at 12 words and output assembly instance 150 at 5 words; any other size and the starter rejects the connection.

    Industrial networks

  • Troubleshooting

    Why a Keyence scanner result shows only one byte in CODESYS

    One character arrives because the assembly generated from the scanner's EDS file reserves a single result element instead of the fixed 128-byte result block. Delete the Result Data entry and re-add it with Bit length = 8 and Count = 128, then bind a union of STRING(127) and ARRAY[0..127] OF BYTE to the regenerated start address to read the null-terminated result.

    Industrial networks

  • Explainer

    Why an imported EDS does not prove EtherNet/IP cyclic I/O

    Importing an EDS file registers an EtherNet/IP device in the engineering tool; it opens no connection. Cyclic I/O works only when the scanner's Forward Open matches the adapter's documented connection definition: the same assembly instances, the same byte counts in the same directions, and a packet interval the adapter accepts. Verify the entry against the adapter documentation, then prove it with connection status and controlled test values.

    Industrial networks