Connecting an S7-300 to SINAMICS S120 CU310-2 DP with terminal safety
Short answer
Run the cyclic commands over PROFIBUS DP with Siemens telegram 111 and the FB283 example blocks, and keep every Safety Integrated demand on the CU310-2 DP terminals, because this route needs no PROFIsafe and no fail-safe CPU. Confirm the nameplate reads 6SL3040-1LA00-0AA0 before reusing anything from the old CU310 DP project: the two control units differ in interface, terminals and safety configuration.

On this page
- Which control unit is on the drive, CU310 DP or CU310-2 DP?
- How do I wire PROFIBUS DP and set the station address?
- How does the S7-300 exchange cyclic data with the CU310-2 DP?
- Which terminals carry the Safety Integrated demands?
- How do I commission and accept the safety functions?
- What do I check first when the link faults?
- Questions asked
Keep the two command paths apart from the first wiring drawing: PROFIBUS DP between the CPU 315-2 DP and the CU310-2 DP carries the cyclic telegrams, and every Safety Integrated demand arrives on hard-wired terminals of the control unit — no PROFIsafe, no fail-safe CPU. Siemens telegram 111 with the FB283 example blocks handles the cyclic data, and application example 67261457 documents exactly this combination with Safety Integrated via terminal. Before you adapt the old CU310 DP project, confirm the nameplate: 6SL3040-1LA00-0AA0 is the CU310-2 DP, and its interfaces and terminal assignments differ from the one in your old project.
Which control unit is on the drive, CU310 DP or CU310-2 DP? #
Read the order number on the control unit before you open the old project: 6SL3040-1LA00-0AA0 identifies the CU310-2 DP, and the CU310 DP you commissioned years ago differs in communication interface, terminal assignment and supported safety configuration, so its drawings are not a template. The control unit decides the communication interface, the terminal assignments and which safety configuration is supported, so identity comes before any parameter work. Work through the nameplates in this order:
- Power unit: the drive here is a SINAMICS S120 with order number 6SL3210-1SE14-1UA0; match it to the power-unit documentation that belongs to it.
- Control unit: 6SL3040-1LA00-0AA0 is the CU310-2 DP. A nameplate that reads CU310-2 PN ends the PROFIBUS plan, because that variant speaks PROFINET; a CU310 DP nameplate ends it too, because you would be wiring a different unit.
- Firmware: read the firmware identification online in the commissioning tool and confirm that the manuals and the engineering-tool compatibility cover that version.
- Documents: obtain the CU310-2 DP operating instructions and the Safety Integrated documentation from Siemens or an authorized distributor, and keep the old CU310 DP project as a record of machine behavior, never as a wiring authority.
How do I wire PROFIBUS DP and set the station address? #
Wire the CPU 315-2 DP master to the CU310-2 DP with PROFIBUS cable and terminated connectors, then give the drive a unique address — set by parameter or by the rotary coding switches, factory position 0 — matching the slave address in the STEP 7 hardware configuration. The bus tolerates no duplicate address and no missing end termination, so proceed in this order:
- With power isolated as the equipment instructions require, connect the CPU's DP port to the drive's PROFIBUS socket; check the data-line pinout against the manual and land the shield at the connector.
- Enable the termination resistors only at the two physical ends of the segment: an enabled termination at an intermediate station loads the bus, and a missing end termination gives intermittent communication that may still let commissioning succeed sometimes.
- Set the station address once and record it. Worked example: for station 15, put the tens coding switch on 1 and the units switch on 5, because 1 × 10 + 5 = 15, and enter the same 15 as the PROFIBUS address of the slave object in STEP 7. With both switches left at their factory position of 0, the address comes from the drive's address parameter instead. The CPU keeps its own master address, for example 2, and no other station may share either number.
- In STEP 7 V5, import the drive's GSD file if the hardware catalog does not contain the CU310-2 DP, insert the slave at the chosen address and download; the slave must enter cyclic data exchange with no bus fault. The master-side sequence for this CPU is the one in connect an S7-300 to a DCM drive over PROFIBUS or PROFINET.
How does the S7-300 exchange cyclic data with the CU310-2 DP? #
Configure one telegram identically on both sides, and make it Siemens telegram 111: application example 67261457 — positioning an S120 with S7-300/S7-400 under STEP 7 V5 with Safety Integrated via terminal — transfers setpoints and actual values with telegram 111 and supplies FB283 blocks for your own program. The telegram fixes the layout of the cyclic process data, the PZD: control words, setpoints, status words and actual values in a defined order. A healthy bus proves that words move, not that they mean what your program assumes.
- Select the telegram in the drive and in the STEP 7 slave object so the lengths and the word order match; a one-word offset writes your enable into the setpoint.
- Write down the input and output addresses the hardware configuration assigns to the slave, and use only those in the program.
- Map every control and status bit from the telegram documentation until each PLC command has a defined drive meaning and each returned bit a defined interpretation. Do not plan on reading drive digital-input states this way: telegram 111 does not carry them, as shown for the S210 in why telegram 111 does not carry SINAMICS S210 digital input status.
- Scale setpoints and actual values against the drive's reference quantities until the PLC engineering units agree with the drive display; the word-level mapping is covered in configuring SINAMICS actual values in PZD telegrams.
- Copy FB283 from example 67261457 into your application instead of hand-typing the sequence, because the blocks are meant for direct reuse. If position values are later needed over PZD on a newer CPU, the method is in reading SINAMICS S120 position to an S7-1500 via PZD telegrams.
- With motion prevented by the approved commissioning arrangement, step the commands and confirm the drive reports the documented states as they change.
Which terminals carry the Safety Integrated demands? #
The safety demands arrive on the documented safety input terminals of the CU310-2 DP, wired from the machine's safety device: with terminal control, Safety Integrated acts on those electrical states, PROFIsafe stays unused, and no standard CPU output is the sole origin of a safety demand. Safety Integrated functions perform defined safety-related actions; select them from the machine risk assessment, and give each one a defined demand path and a defined safe response.
- Take the terminal numbers and the channel requirements only from the CU310-2 DP documentation for the installed firmware.
- Where the selected arrangement requires two channels, keep the prescribed channel separation and diagnostic behavior, because jumpering the two channels removes the cross-check the function is validated on.
- Siemens documents the Safety Integrated extended functions via the onboard terminals of the CU310-2 PN; the function logic and the acceptance procedure carry over to your architecture, but the terminal numbers do not.
One point the risk assessment must own: Safe Torque Off, where selected, prevents torque generation and nothing else — it gives no controlled deceleration and does not hold a suspended load, so coast-out, gravity and braking need their own measures. Run, stop and fault acknowledge over PROFIBUS remain operational commands and never substitute for the safety demand.
How do I commission and accept the safety functions? #
Commission in the documented order — wire, configure, then accept — and release motion only when the drive reports the intended safety configuration with no unresolved safety diagnostics. Each step has a pass condition you can read, so record it:
- List each required safety function with its documented terminal path and the safe machine response it must produce.
- Connect the safety device and any required safety logic per the applicable wiring diagram, then verify the terminal states against the documented normal condition and the documented demanded condition.
- Configure and activate the functions with the control unit's documented authorization and activation procedure; expected result: the drive accepts the intended safety configuration without unresolved safety diagnostics.
- Test each function with motion prevented by the approved commissioning arrangement; expected result: the drive reports the documented states as each demand changes, and torque returns only after the demand clears.
What do I check first when the link faults? #
Read parameters r2075 and r2076 first: the CU310-2 DP exposes the received and the sent PROFIBUS diagnostics telegram there, and the content points to an address, configuration or line problem before you change any wiring. Then work the condition table instead of acknowledging faults repeatedly:
| Condition | Check | Expected reading after the fix |
|---|---|---|
| No cyclic data | Switch and parameter address, slave object, cable, termination | Slave in cyclic data exchange, no bus fault |
| Data exchanges, drive stays disabled | Telegram length and word order, control-word sequence, safety state | Each command answered in the status word |
| Intermittent dropouts | Termination at both segment ends only, shield landed | Stable exchange, quiet diagnostics |
Keep the three fault families apart — communication, command sequence, safety — and fix them in that order, because repeated fault acknowledgment clears the message while the inhibit stays. If the setpoint and the control word look written in the PLC and nothing moves, the mapping is the suspect, which is the failure walked through in fix missing setpoint and control word writes to a PROFIBUS drive.
Questions asked
Do I need a fail-safe CPU for terminal-based Safety Integrated?
No. The terminal route places each safety demand on hard-wired inputs of the CU310-2 DP, so the CPU 315-2 DP stays a standard CPU with standard I/O. PROFIsafe is the other Siemens example: it needs a fail-safe CPU, fail-safe modules and F-programming, which is precisely the hardware this panel does not have. Your program may monitor the safety state and react to it, but it must never be the sole source of the demand.
Can I download my old CU310 DP project into the new control unit?
Not as a working configuration. Use it as a behavioral reference: copy the validated control-word sequence and the machine logic, but take terminal assignments, telegram settings and the safety configuration from the CU310-2 DP documentation for the installed firmware. A shared product family does not make the two control units interchangeable, and a downloaded mismatch can map commands to meanings you never tested.
Which Siemens documents show the terminal-based safety wiring?
Application example 67261457 covers positioning an S120 with S7-300/S7-400 via PROFIBUS or PROFINET with Safety Integrated via terminal, and it includes the telegram 111 blocks such as FB283. The training document 79722926 shows the wiring of a CU310-2 PN, so use it for the safety architecture only. For the CU310-2 DP, the terminal numbers come from its own operating instructions.
Why does the drive refuse the enable although communication is healthy?
Because torque is inhibited by something the control word cannot override: an active or not-accepted safety function. Check the safety input states and the acceptance result first, then the telegram mapping, then the control-word sequence, in that order. Repeated fault acknowledgment clears the message but not the inhibit, so the drive stays silent and the real cause stays hidden.