Change an MR-J4-TM servo amplifier network protocol card

Drives and motion Published 7 min read

Short answer

The MR-J4-TM PROFINET, EtherNet/IP and EtherCAT variants are the same amplifier with different communication cards, so you convert one by exchanging the card and rebuilding the controller-side device configuration. Fit ABCC-M40-PIR for PROFINET, ABCC-M40-EIP for EtherNet/IP or ABCC-M40-ECT for EtherCAT; if handling the connector risks bent pins, send amplifier and card to the manufacturer's service instead.

On this page
  1. Can an MR-J4-TM servo amplifier change from PROFINET to EtherCAT or EtherNet/IP?
  2. Should you swap the card yourself or send the amplifier to service?
  3. How do you identify the fitted card before you order the replacement?
  4. How do you swap the communication card step by step?
  5. What must change on the controller after the card swap?
  6. How do you verify the conversion works?
  7. What do you check when the controller still does not connect?
  8. Questions asked

An MR-J4-TM servo amplifier that speaks the wrong industrial network does not need replacing. The PROFINET, EtherNet/IP and EtherCAT variants are one amplifier behind three different communication interface cards, and the manufacturer documents exchanging the card as a supported conversion: performed correctly, the swap makes the unit work on the new protocol. The job is one card plus a rebuilt controller-side device configuration, and the one real hazard is bent connector pins during handling. Below are the card numbers, the swap sequence and the checks that prove the conversion, plus the service route for shops that would rather not touch the connector.

Can an MR-J4-TM servo amplifier change from PROFINET to EtherCAT or EtherNet/IP? #

Yes. The MR-J4-TM family is one servo amplifier behind three interchangeable communication cards, so converting between PROFINET, EtherNet/IP and EtherCAT is a card exchange plus controller-side reconfiguration, not a replacement. The three variants and their cards, shown for the MR-J4-20TM size:

Amplifier variant Network protocol Communication interface card
MR-J4-20TM-PNT PROFINET ABCC-M40-PIR
MR-J4-20TM-EIP EtherNet/IP ABCC-M40-EIP
MR-J4-20TM-ECT EtherCAT ABCC-M40-ECT

The servo hardware, meaning the power stage, motor control and encoder handling, is identical across the three variants; only the fitted card differs. Across the family the trailing suffix is the part that selects the card. The vendor's position is that anyone holding an MR-J4-TM amplifier and the card for either of the other two protocols can perform the exchange, and that a correctly performed exchange leaves the amplifier working on the new communication method. The conversion runs in any direction, because the target card depends only on the protocol you are moving to.

Should you swap the card yourself or send the amplifier to service? #

Both routes are supported: swap it yourself when you can seat and unseat the connector without bending pins, and send the amplifier and card to Mitsubishi Electric service when you cannot.

  • Local swap when the target card is on hand and positively identified, the person has handled plug-in interfaces on powered-down equipment before, and the machine can be down for the swap plus verification.
  • Service when the exchange looks difficult in-house or pin damage risk is unacceptable. Arrange it through the manufacturer's sales representatives and ship the amplifier and the communication card together, because the exchange needs both.

The bench decision: if you have already done this class of connector work on a production axis, do the swap locally in the next planned window; if this would be your first, book the service. A bent pin turns a card exchange into an amplifier repair.

How do you identify the fitted card before you order the replacement? #

Read the full type designation on the amplifier's rating plate first: the suffix PNT means PROFINET, EIP means EtherNet/IP and ECT means EtherCAT, and each suffix maps to exactly one card.

Then confirm the marking on the card itself before anything is ordered, because the rating plate keeps the suffix the amplifier shipped with. On a unit converted earlier, badge and fitted card disagree. Worked example: the machine records say axis 3 must move to EtherCAT and a spare ABCC-M40-ECT is already on your shelf. The amplifier's plate reads MR-J4-20TM-PNT, so the fitted card is ABCC-M40-PIR. The target protocol EtherCAT maps to ABCC-M40-ECT. Parts to order: 1 required minus 1 on the shelf equals 0. The job is the exchange plus the EtherCAT master's device configuration for the axis. Had the plate read MR-J4-20TM-EIP, the same shelf spare would still be the right part.

How do you swap the communication card step by step? #

Plan seven steps, record and back up, isolate, remove, install, label, reconfigure, verify, and treat the card's connector as the only fragile part; the amplifier's instruction manual gives the removal and installation method, and no generic torque or pin arrangement substitutes for it.

  1. Record and back up. With the machine still on its old network, write down the amplifier's full type designation and the fitted card's marking, and save a parameter backup from the amplifier's setup software.
  2. Isolate. Put the machine in its safe state and remove all power, control power included. A servo amplifier holds a hazardous charge on its DC bus after power-off, so wait the discharge time the instruction manual states before you open anything.
  3. Remove the fitted card by the instruction manual's method, keeping the pull straight and free of side load. Stop the moment alignment feels uncertain; forcing is how pins bend.
  4. Install the target card after checking its marking against the intended protocol. Seat it fully, again by the manual's method, and give the connector a visual check that every pin sits straight.
  5. Label the new state: enter the fitted card's designation in the maintenance record and update the cabinet label and network drawing.
  6. Reconfigure the controller before power-up: replace the old protocol's device in the engineering project with the target network's device for this amplifier, then download the project.
  7. Power up and run the three checks in the verification section below.

What must change on the controller after the card swap? #

Everything at the project level: the engineering project still holds the old protocol's device for that axis, so replace it with the target network's device for the amplifier before you expect a connection.

The physical swap changes nothing in the project, so rebuild it for the target:

  • EtherNet/IP: import the drive's EDS file into the engineering tool, add the amplifier as an EtherNet/IP node and set its IP address; the vendor's commissioning material for the EIP variant covers exactly this EDS-and-address sequence.
  • PROFINET: add the amplifier's PROFINET device and configure the cyclic telegram data the controller exchanges with the servo, which Control a PROFINET servo drive with cyclic telegram data walks through.
  • EtherCAT: scan the drive into the EtherCAT master, import its device description and map the process data before the axis will exchange I/O.

The name or address the amplifier carried on the old network does not transfer. Set the addressing the target network uses as part of the new device configuration, and download the finished project before power-up so the first scan already speaks the right protocol.

How do you verify the conversion works? #

Power up and pass three checks in order: the amplifier's status indicators show a ready state, the controller's network diagnostics list the amplifier, and a low-speed test move commanded from the controller produces the expected feedback.

  1. Ready state: at power-up the amplifier's indicators match the ready pattern in the manual's indicator list, with no fault shown.
  2. Connection: the controller's network diagnostic shows the amplifier present and in data exchange, not merely linked at the port.
  3. Motion: with the axis enabled in the machine's commissioning state, command a small move at reduced speed and confirm the feedback tracks the command.

Pass all three and the conversion is done. Fail any one of them and work through the order in the next section before touching the hardware again.

What do you check when the controller still does not connect? #

Work from the card outward, marking, seating, cable and switch port, then the controller project, because after a conversion the usual causes are a wrong card or an unreplaced project device, not the amplifier.

Condition Check first Reason
The controller's network scan never sees the amplifier The fitted card's marking against the target protocol Each card speaks one protocol; an ABCC-M40-PIR never answers an EtherCAT master
The amplifier appears but the connection drops or errors Card seating and connector pins A pin bent during handling makes intermittent contact
The amplifier connects but the axis will not run The controller project's device and its configuration The old device was replaced but its settings or the axis data were not rebuilt
A fault shows at power-up The amplifier's diagnostics against the manual's fault table An incompletely seated interface reports as a communication fault

On an S7-1200 whose PROFINET axis still faults after the connect, the diagnostic sequence in Troubleshooting S7-1200 PROFINET servo motion control issues applies.

The decision for every case: with the target card confirmed and the connector work inside your team's hands, swap locally, rebuild the project and pass the three checks; otherwise the amplifier and card go to the service together, and the project rebuild and verification stay on your side either way.

Questions asked

Does the card exchange erase the amplifier's parameters or require re-tuning?

No. The parameter memory, motor matching and gain set live in the amplifier, which stays in the cabinet; the card is only the network interface. The vendor's stated outcome of a correct exchange is an amplifier that works on the new protocol, not a re-commissioned drive. The parameter backup in step 1 is cheap insurance for the service route, where the amplifier leaves your cabinet.

Can the removed card be kept as a spare for the old protocol?

Yes, and label it before it goes on the shelf. The documented exchange assumes exactly this: an MR-J4-TM amplifier plus a card for one of the other two protocols. Inspect the connector pins under strong light, note the card designation on the bag, and store it with the machine's records; a card with a bent pin is a repair, not a spare.

Can the same amplifier be converted again later to the third protocol?

Yes. The hardware never changes, so a later move to the third protocol is the same exchange with that protocol's card, followed by the same controller-side rebuild. Each exchange is a fresh pin-risk event, so let the same trained hands do every swap and keep the unused cards labeled as spares; two careful exchanges cost far less than one rushed one.

What should the conversion record contain?

Five entries: the amplifier's full type designation, the removed card's designation, the fitted card's designation, the date, and the controller project revision downloaded after the swap. Add where the removed card is stored. With that on paper, a network fault years later is diagnosed from the record before anyone opens the cabinet.

Keep reading

  • How-to

    Bridging a PLC-5/15 DH+ network to a Kinetix 300 servo drive

    Yes, a DH+-to-EtherNet/IP gateway exchanges command and feedback words between a PLC-5/15 and a Kinetix 300, but it only moves data: the drive must execute the motion profile locally. Replace the stepper controller, pulse expander, and encoder-counter functions with an eight-word map that carries a 32-bit position as two 16-bit words behind a data-valid handshake. If the machine needs trajectory points streamed per scan, migrate the controller instead of bridging it.

    Drives and motion

  • Explainer

    Why ctrlX MOTION needs EtherCAT for third-party axes

    ctrlX MOTION addresses axes only as EtherCAT slaves through CoE (CiA 402) or SoE, so a PROFINET/PROFIBUS servo module like the Siemens F-TM cannot be declared as a native axis. Command it instead with CODESYS Fieldbus Communication plus CODESYS SoftMotion, which excludes the ctrlX MOTION feature set.

    Drives and motion

  • Troubleshooting

    Troubleshooting S7-1200 PROFINET servo motion control issues

    Fix an S7-1200 PROFINET servo project in order: compile the motion calls in FB1 first, set drive and TIA Portal to the same telegram — Telegram 3 on this pairing — then prove one axis holds enable and velocity through repeated scans. A first-generation CPU 1214C executes independent single-axis motion only; the flying shear's deterministic master-slave cut belongs in the drives or in a motion-class controller, and no telegram adds it.

    Drives and motion