Explainer
Can an S7-1500 control drives on a CC-Link IE Field network
Short answer
Yes, but only through a gateway that can itself hold the CC-Link IE Field control-station role for the fourteen intelligent device stations. A coupler proven only for data exchange between a Mitsubishi PLC and a Siemens PLC keeps the Mitsubishi master on the network, so it extends the architecture instead of replacing the controller.
On this page
- Can an S7-1500 talk to CC-Link IE Field without extra hardware?
- Which station role must the gateway hold on the drive network?
- Does a PROFINET-to-CC-Link coupler replace the Mitsubishi PLC?
- Is CC-Link IE Field Basic the same network as CC-Link IE Field?
- How much cyclic data crosses the gateway for every drive?
- Do drive parameter reads and writes survive the gateway?
- What is the decision for each replacement case?
- Questions asked
Yes, an S7-1500 can take over the fourteen Mitsubishi frequency converters on CC-Link IE Field, but only through a gateway that can itself hold the network's control-station role; the PLC alone cannot. A coupler proven for data exchange between a Mitsubishi PLC and a Siemens PLC keeps the Mitsubishi master on the drive network, so it extends the architecture instead of replacing the controller. Below is the role the gateway must hold, how much cyclic data crosses it, which parameter services survive, and the decision for each case: replace the PLC, keep it, or change the drive network.
Can an S7-1500 talk to CC-Link IE Field without extra hardware? #
No: the S7-1500 speaks PROFINET from its own interfaces and carries no CC-Link IE protocol stack, so the drives stay reachable only through a gateway that translates between the two networks, and which gateway you pick decides the whole project. CC-Link IE Field is specified by the CC-Link Partner Association and runs on gigabit Ethernet, the same cabling and connector family as PROFINET, but the two protocols are not interchangeable.
Its cyclic transmission works so that every station passes its data to all other stations in turn, under the coordination of the network's controlling station. A standard Ethernet switch forwards frames; it does not translate between protocol stacks or run a station role. The translation device must therefore have one port on each network and a documented role on each side.
Which station role must the gateway hold on the drive network? #
It must hold the role the old PLC holds today: the control station that owns the network, because the frequency converters are configured as intelligent device stations, and an intelligent device station exchanges its cyclic data only with a controlling master. An intelligent device station is a station category within CC-Link IE Field; the drives occupy that category, so something on the network must occupy the controlling one.
This is the point that decides the project. A gateway documented only as an intelligent device station cannot own the drive network; it would need a master somewhere else, and that master is the PLC you were asked to remove. A device that maps words between two networks does not become a network controller by translating data, as covered in the explanation of why a PROFINET IO-device gateway cannot be a controller (article:why-a-profinet-io-device-gateway-cannot-be-a-controller). Require, in the manufacturer's documentation, the words control station or controller for the CC-Link IE Field side, with a supported station count that covers every configured drive.
Does a PROFINET-to-CC-Link coupler replace the Mitsubishi PLC? #
Not by itself: a coupler such as the Hilscher NT 151-CCIE-RE that exchanges data between a Mitsubishi PLC and a Siemens PLC leaves a Mitsubishi controller on the CC-Link side, so that architecture puts the S7-1500 next to the old master instead of in its place. That is a legitimate architecture, but it is an extension, not a replacement.
Separate the two goals before selecting anything. If the Mitsubishi PLC may stay as the drive-network master, a coupler of that kind moves selected cyclic and message data to the S7-1500 over PROFINET, and the Siemens CPU supervises the drives as a data partner. If the PLC must physically go, the coupler architecture as demonstrated does not satisfy the request, and you accept only an interface whose data sheet names the CC-Link IE Field control-station role. Where no candidate documents that role, do not promise the replacement; fall back to keeping a Mitsubishi controller as master or to changing the drive network.
Is CC-Link IE Field Basic the same network as CC-Link IE Field? #
No: CC-Link IE Field Basic is a separate, lighter variant built to bring ordinary Ethernet devices into a Mitsubishi controller, and a gateway listed as a Field Basic slave, such as the NT 151-CCIES-RE/PNS, does not join a full CC-Link IE Field network. The variant matters when comparing products, because the same netTAP 151 family serves both: the NT 151-CCIES-RE/PNS is documented as a CC-Link IE Field Basic slave on one side and PROFINET IO on the other, at 24 V DC supply, while the full-field coupler is a different order code.
Read the exact variant out of the running configuration and the drive communication option documentation before comparing gateways. An installation whose drives occupy intelligent device stations on full CC-Link IE Field needs a full-field interface; a Field Basic slave, however well it talks PROFINET, is the wrong product for it.
How much cyclic data crosses the gateway for every drive? #
As a worked example, if each intelligent device station exchanges 32 words in each direction, all fourteen drives produce 896 words, that is 1792 bytes, of cyclic process data that the gateway must carry and re-publish in its PROFINET process image every cycle. The 32-word figure is an example input; the real counts come from the station configuration in the existing project.
The arithmetic for the example:
- Cyclic data to the S7-1500 (inputs): 14 drives × 32 words = 448 words
- Cyclic data from the S7-1500 (outputs): 14 drives × 32 words = 448 words
- Total per cycle: 448 words + 448 words = 896 words = 896 × 2 bytes = 1792 bytes
The gateway's documented process-image size on the PROFINET side and its documented cyclic capacity on the CC-Link side must each cover that total plus whatever diagnostic words you map. The update time through two protocol stages is longer than the old single-network exchange, so measure it on a loaded configuration and compare it with the response the machine's control loop needs.
Do drive parameter reads and writes survive the gateway? #
Only when the gateway documents transient, or noncyclic, transmission as a separate service, because passing the cyclic process image covers commands, speed references and status words but does not reproduce the parameter reads and writes the old program performed. CC-Link IE networks distinguish cyclic transmission, the turn-by-turn shared data, from transient transmission, the message-based transactions addressed to individual stations.
Make a list of every noncyclic transaction in the Mitsubishi program: parameter reads, parameter writes, alarm or fault-history access, and any reset that runs as a message rather than a status bit. Each item needs a documented equivalent on the proposed interface, or an agreed alternative path such as a drive engineering connection. A gateway that maps cyclic words cleanly and documents no transient service fails the project the first time an operator tries to change a drive parameter from the HMI.
What is the decision for each replacement case? #
Commit per case: replace the Mitsubishi PLC only with an interface whose documentation names the full CC-Link IE Field control-station role for at least fourteen intelligent device stations; otherwise keep a Mitsubishi controller as drive-network master and attach the S7-1500 through a coupler.
| Case | Decision |
|---|---|
| The PLC must be removed, the drives stay on CC-Link IE Field | Use an interface documented as a full-field control station with station capacity for every configured drive and transient services if the program needs them. If none is documented, retain a Mitsubishi controller as master or migrate the drive network. |
| The PLC may stay | A coupler of the NT 151-CCIE-RE kind is adequate; the S7-1500 becomes an additional PROFINET data partner, and you document the mapped words. |
| The drive network may change | Fit PROFINET drive interfaces, or replace the network with hardwired I/O as described for whether a PLC gateway can replace a networked VFD with hardwired I/O (article:can-a-plc-gateway-replace-a-networked-vfd-with-hardwired-i-o). |
For whichever case you build, back up the Mitsubishi project, network configuration and drive parameters with authorized tools first, then commission one drive: command, reference, feedback, fault and recovery, verified against the drive's own monitor, before replicating the mapping. Do the first enable with the machine in a safe state, because a drive that follows a newly mapped command source can move without warning during the first test.
Questions asked
Could the S7-1500 join CC-Link IE Field as an intelligent device station instead of the control station?
Not directly. Its Ethernet interfaces run PROFINET and no other fieldbus stack, so it cannot occupy any CC-Link IE Field station role by itself. The station role question applies to the gateway you place in front of it, and a gateway able only to act as an intelligent device station still needs some other control station on the drive network.
Can one Ethernet switch carry both networks since both use gigabit cabling?
No. A switch forwards frames but does not translate between protocol stacks, and both CC-Link IE Field and PROFINET run cyclic real-time traffic that expects its own timing domain. The gateway stands between two separate physical networks with one port on each side, and mixing both protocols on one switch would disturb both.
What should be recorded from the running installation before any gateway is ordered?
Read the exact network variant, every station's cyclic word count and station number, the parameter transactions in the PLC program, the fault-reset sequence, and the update time the machine actually needs. That record is the specification the gateway documentation must be checked against, and it doubles as the acceptance baseline for commissioning the new architecture.
How is the update time through the gateway verified?
Toggle a command bit in the S7-1500 and time its arrival in the drive status word using the gateway diagnostics and the drive monitor, then compare that round trip with the value the machine tolerates. Do this on one drive before replicating the mapping, and repeat it with every configured station online, because fully loaded cyclic traffic changes the result.