Selection guide
Connecting PROFIBUS devices to an S7-1500 without onboard PROFIBUS
Short answer
A CPU 1511-1 PN has no PROFIBUS interface, so PROFIBUS devices do not connect directly. Add the CM 1542-5 communications module to the S7-1500 station, or use a PROFINET-to-PROFIBUS gateway that presents the PROFIBUS slaves as proxies; only the PN/DP CPUs (1516-3, 1517-3, 1518-4) carry PROFIBUS onboard on X3. For a project already engineered on PROFINET, the right move is to change nothing and wait for the missing connection block.
On this page
A PROFIBUS device does not connect directly to a CPU 1511-1 PN. That CPU, order number 6ES7511-1AK02-0AB0, has one interface and it is PROFINET on an RJ45 port: there is no PROFIBUS socket on the housing and no firmware that creates one. To connect a PROFIBUS device to this S7-1500 you choose between two additions: the CM 1542-5 communications module, which attaches the station to a PROFIBUS network, or a PROFINET-to-PROFIBUS gateway on the PN interface. Only the PN/DP CPUs, 1516-3, 1517-3 and 1518-4, carry PROFIBUS onboard. And when the project is already engineered on PROFINET, as it is with the RF180C and RF340R readers, the third route is to change nothing and wait for the missing 6GT2002-0JD00 connection block.
Selection at a glance #
The route depends on the CPU you already have and on whether PROFIBUS is permanent or a schedule workaround.
| Route | Hardware | PROFIBUS role | Choose it when |
|---|---|---|---|
| Onboard DP interface | None: CPU 1516-3 PN/DP (6ES7516-3AN01-0AB0), or a 1517-3 or 1518-4 | The CPU is DP master on interface X3 | The CPU order can still change |
| Rack module | CM 1542-5 communications module | The module is the station's PROFIBUS interface | PROFIBUS devices stay on the machine for good |
| Gateway | PROFINET-to-PROFIBUS gateway on the PN interface | Gateway is DP master; each slave appears as a PROFINET proxy | The date is fixed and gateway and devices are on hand |
| No PROFIBUS | None: keep the RF180C and RF340R, install the 6GT2002-0JD00 | None | The design is finished on PROFINET |
Adding the CM 1542-5 module #
The CM 1542-5 is the module Siemens documents for exactly this job: a communications module intended for operation in an S7-1500 automation system that connects the station to a PROFIBUS network. It mounts in the rack beside the CPU and becomes the station's PROFIBUS interface, configured as DP master for your slaves. It can also take a DP slave role, a configuration worked through in configuring the DP slave roles of a CPU 1516-3 PN/DP and CM 1542-5.
Engineering happens in the same project as the CPU: add the module, set the bus parameters, import each slave's GSD file, assign PROFIBUS addresses, and terminate the bus at both physical ends. The cyclic DP traffic runs on the module, so the PROFINET interface keeps its update budget for its own IO devices.
Bring the new interface up with the machine in a safe state, because adding a master renumbers the IO layout the running program was written against.
Choose this route when the PROFIBUS devices are permanent, a spare-part strategy or peripherals a sister machine already runs, and you have normal engineering time for the project.
Using a PROFINET-to-PROFIBUS gateway #
A PROFINET-to-PROFIBUS gateway hangs on the CPU's PN interface as an IO device; the CPU remains the IO controller, because a PROFINET IO-device gateway cannot be a controller. On the PROFIBUS side the gateway is the DP master, and each PROFIBUS slave is represented to PROFINET as a proxy: the proxy lets that slave exchange data not just with its master but with every device on the PROFINET side.
In the CPU project you configure the proxy from the slave's GSD file, and the IO or tag data then moves as cyclic PROFINET IO data between gateway and CPU. The PROFIBUS segment keeps its own timing behind the gateway; the CPU never waits on the bus itself.
Choose the gateway when the completion date is fixed, PROFIBUS is a small side bus, and gateway plus PROFIBUS devices are physically at hand: it needs no rack module, and apart from one new IO device the station configuration stays as engineered.
When the CPU already has PROFIBUS #
The PN/DP CPUs change the answer completely. On the CPU 1516-3 PN/DP, order number 6ES7516-3AN01-0AB0, the third interface X3 is the one that connects to a PROFIBUS network, and when it runs as a PROFIBUS DP interface the CPU itself is the DP master, with no module and no gateway. The 1517-3 and 1518-4 give the same direct connection. These are the larger CPUs, the 1516-3 carrying 1 MB work memory for the program and 5 MB for data, so fitting one to gain PROFIBUS means re-engineering the whole station; treat onboard DP as a new-design choice, not a retrofit.
If that PROFIBUS link also has to carry PUT/GET traffic to an older S7-400, the stalling you will meet is explained in why S7-400 to S7-1500 PUT/GET over PROFIBUS stalls.
The RFID decision: stay on PROFINET #
The RF180C is a PROFINET IO communication module, so with the RF340R readers the design is already PROFINET and the only missing piece is the 6GT2002-0JD00 RJ45 connection block. Spares from the customer's PROFIBUS machines do not drop in: a PROFIBUS reader needs a DP master, either the module or a gateway, its GSD file, a bus address, and the PLC's read and write commands remapped to the PROFIBUS telegram. That is fresh engineering against a design that is already finished, for hardware nobody has seen.
So keep the PROFINET design and get the connection block: the RF180C and RF340R configuration on the S7-1500 is worked through in configuring an RF180C with RF340R readers for S7-1500 RFID. If a tag read misbehaves at commissioning, troubleshooting RF340R tag detection on an RF180C covers the sequence. Convert to PROFIBUS only when the block's lead time provably breaks the date and the exact PROFIBUS reader plus a gateway are physically at hand today.
Worked schedule example #
Put numbers on the two routes, as an example. Suppose the connection block is ordered on the 1st of the month and its lead time is 4 weeks: 1st + 28 days = the 29th, against a completion date of the 25th, so the block route lands 29 − 25 = 4 days late. The gateway route, with reader and gateway already at hand, costs engineering time only: proxy configuration and GSD import 1 day, remapping the read and write commands 2 days, tag-read testing 1 day, so 4 days of work finishing on the 5th, which is 25 − 5 = 20 days inside the date. That margin is the whole argument for the gateway route, and every day of it assumes the parts are already in the building; the moment anything has to be ordered, no PROFIBUS route beats waiting and the date moves instead.
Decision by case #
- CPU 1516-3, 1517-3 or 1518-4 fitted or still orderable: PROFIBUS goes on X3 with the CPU as DP master, no module and no gateway.
- CPU 1511-1 PN with permanent PROFIBUS devices: fit the CM 1542-5 and engineer the slaves in the CPU project.
- CPU 1511-1 PN with a fixed date and PROFIBUS as a small side bus: a PROFINET-to-PROFIBUS gateway with proxy, provided the hardware is at hand today.
- Project already engineered on PROFINET, as with the RF180C and RF340R: no PROFIBUS at all; install the connection block when it arrives and prove the link with a tag-read test.
Questions asked
Does a firmware update add PROFIBUS to the CPU 1511-1 PN?
No. The PN in the order number means the only interface is PROFINET on an RJ45 port. PROFIBUS needs its own RS-485 line driver and a 9-pin D-sub connector, so no firmware can create hardware that is not there. The only working additions are the CM 1542-5 module in the rack or a gateway on the PROFINET side.
Is the module called CM 1542-5 or CP 1542-5?
The S7-1500 documentation names it the CM 1542-5 communications module, but tutorials and project notes often write CP1542-5, and both spellings point at the same PROFIBUS module for this CPU family. Order and configure against the CM designation; the CP spelling mainly causes confusion with the CP Profibus modules used on S7-300 and S7-400 stations.
What should the customer's spare PROFIBUS readers come with?
Ask for the exact order numbers, the GSD device-description file, the PROFIBUS address and baud the units ran at, and the telegram layout of their tag data. Without the GSD file you cannot build the slave for the CM 1542-5 or the proxy for a gateway route, and without the telegram layout the PLC's read and write commands cannot be remapped.
Does a gateway load the CPU's PROFINET interface?
Yes. The slaves' data crosses to the CPU as cyclic PROFINET IO telegrams, so the PROFIBUS bytes consume part of the PN interface's update budget and of the IO controller's cycle. Keep the segment small, one reader and a few IO slaves, and let the fast devices keep the shortest update times.