Land the readout's analog negative on the channel's CH- terminal, not on the module's 0 VDC supply terminal: the F2-04AD-1 senses current between CH+ and CH-, so an unwired CH- passes no current and the channel stays dark. Bond the two supply 0 V rails only where the wiring diagrams call for it, then bring the data in with IBox 460 and scale it with IBox 423 for BCD or IBox 403 for binary.
On this page
The readout's analog negative lead goes on the channel's CH- terminal, not on the module's 0 VDC supply terminal. The F2-04AD-1 measures current that enters CH+ and leaves through CH-, so with the return parked on the supply common no current passes the channel and no scale can recover a signal that never arrived. Moving that one lead is the fix. After it: bond the two supply 0 V rails only where the wiring diagrams call for it, prove the loop with a meter in series, and match the scaling instruction to the data format — IBox 460 brings the channel in, IBox 423 scales it when 460 is set to BCD, IBox 403 when it is set to binary. The walk-through below covers a DL205 rack with a 260 CPU and a readout that already has its own supply.
Why the return belongs on CH- #
A current input is a series circuit with two ends: the loop current enters the channel at CH+, passes the module's internal sensing circuit, and exits at CH-. The +24 VDC and 0 VDC terminals are a different circuit — they feed the module itself from a user-supplied 24 VDC supply, which the F2-04AD-1 requires from outside the rack. Landing the readout's analog negative on that supply terminal closes no path through the channel: the current has no way out, nothing flows, and the raw value never responds.
That is the whole explanation for the reported dead channel. Analog positive on CH1+ was right; the return on the supply common left the measurement path open. For what happens inside the module once current does flow — sensing, conversion, raw counts — see how PLC analog input and output modules convert signals.
Move one lead #
Do the repair in this order so each step can be checked:
- Power the loop down under your site's electrical procedure. The module's connector pulls off for bench wiring: squeeze the top and bottom retaining clips and gently pull it free.
- Leave the readout's analog positive on CH1+.
- Take the readout's analog negative off the supply terminal and land it on the CH- terminal of the same channel.
- Leave the module's power as it was wired: 24 V+ on +24 VDC, 24 V− on the supply common. Those terminals only run the module's own circuits.
- Restore power and watch the channel's raw value move as the gate moves, before any scaling is applied.
The readout keeps its own supply. Nothing about the signal pair requires the two supplies to be merged, and after step 3 the loop should already read.
Two supplies, one reference: bond only when the diagrams call for it #
With the return on CH-, the signal pair itself closes the loop, so a bond between the two supply commons is not what makes current flow — it is a reference question, and it has a decision rule:
- Read the readout's output specification. If the current output is not isolated (its negative internally tied to its supply 0 V) and the equipment diagrams show the analog commons referenced to the supply commons, run one wire between the readout supply's 0 V and the module's supply-common terminal.
- If the output is documented as isolated, bond nothing. The signal pair is the only connection between the two supplies, and a bond would defeat the isolation.
- A raw value that is present but offset, or that shifts when other equipment switches, points at this reference problem, not at scaling.
Bonding is the opposite repair from isolation: when both 0 V rails sit at different earth potentials, a wire between them carries current, and the loop needs galvanic separation instead — the output-side version of that fault is fixing a 4-20 mA output ground fault with a signal isolator. The same who-powers-the-loop reasoning appears on a PLC's output side, as when configuring a 1756-OF8 analog output module with an externally powered 4-20 mA loop.
Prove the loop with a meter in series #
A dead channel on the PLC screen cannot tell you whether the readout is silent or the channel is misconfigured, so measure before changing anything else. Put a digital multimeter on its DC milliamp range, open the loop at the CH1+ terminal or at a documented test point, and wire the meter in series so the loop current runs through it. A meter on a current range is a short circuit: it goes in series only, never across the output or the 24 V supply, and it goes back to volts before it goes back in the pouch.
The reading gives you the branch:
- 0 mA: the loop is open or the output is dead upstream — readout configuration, its supply, or the pair itself. The PLC side is not the fault.
- Between 4 and 20 mA: the loop is healthy; the fault is in the PLC-side configuration, format or scaling.
- Steady but outside that band: the readout is out of range or faulted — check its process indication against its output specification.
For a 0–100 span, the expected current is 4 mA + (indication ÷ 100) × 16 mA, so a readout showing 52.5 should be driving 12.4 mA. An open input wire has a second signature on the PLC side: the manual's Diagnostic Inputs section, page 2-12, documents a broken wire as 8000h in that channel's data. 8000h is a flag, not a measurement — never feed it to a scale.
Bring the data in with IBox 460, scale with the matching IBox #
Acquisition and scaling are two instructions with one contract between them. IBox 460 brings the channel's data in and declares its data format, and the scaling instruction must match that declaration:
- IBox 460 set to BCD → scale with IBox 423.
- IBox 460 set to binary → scale with IBox 403.
A healthy loop scaled by the wrong pairing still yields wrong engineering values, so when the raw value tracks the gate but the scaled number is nonsense, this pairing is the first suspect.
The scale itself is linear. For a 0–100 process span:
Engineering value = (raw − raw at the live-zero end) ÷ (raw at full scale − raw at the live-zero end) × 100
Take the two raw endpoints from the module's data table for the format you selected, or from a live loop check at both ends of the span. Worked example, with illustrative endpoints of 0 counts at the live-zero end (4 mA) and 4095 counts at full scale (20 mA; a 12-bit module's full binary span, 2^12 − 1 = 4095):
- The meter reads 12.4 mA. Fraction of span = (12.4 − 4.0) ÷ (20.0 − 4.0) = 8.4 ÷ 16 = 0.525.
- Engineering value = 0.525 × 100 = 52.5.
- Expected raw value = 0.525 × 4095 ≈ 2150. Check: (2150 − 0) ÷ (4095 − 0) × 100 = 52.5.
If your process span is not 0–100, substitute its endpoints in the last multiplication; the arithmetic is identical. If you would rather read the slot's V-memory window directly and scale in ladder, how to assign V-memory values and scale analog in ladder walks that path, and the 12.4 mA above must still land at 52.5.
The decision for each case #
| What you observe | What it means | The action |
|---|---|---|
| No signal; analog negative on the supply terminal | The channel's current path was never closed | Move the return to CH-; CH1+ stays as wired |
| 0 mA in series at the readout output | Dead or open loop upstream of the PLC | Fix the readout, its supply or the pair; the module is innocent |
| Healthy loop current present; raw value frozen | PLC-side configuration: slot, channel or format | Verify the channel setup and IBox 460's settings |
| Raw value moves; scaled value wrong | Scaling IBox does not match 460's format, or wrong endpoints | IBox 423 with BCD, IBox 403 with binary; endpoints from the data table |
| Raw value shows 8000h | The module's broken-wire diagnostic (page 2-12, Diagnostic Inputs) | Repair the loop wiring; no scale instruction fixes it |
Three final calls:
- Keep the two supplies. Bypassing the readout only to avoid a second supply trades a solved problem for an unsolved one, unless the slide gate monitor's own output is verified on its data sheet as a compatible current source.
- Bond the 0 V rails only where the diagrams call for it, and leave an isolated output isolated.
- Wire first, prove the current second, scale third — one change at a time, so a corrected raw reading is never confused with a scaling change.
And if your symptom is a different animal — a DL-06 4-20 mA reading that drops to half rather than to nothing — that fault has its own cause and its own fix.
Questions asked
Can the F2-04AD-1 power a two-wire loop transmitter?
Yes, but the circuit is different from this one. A loop-powered two-wire transmitter needs a DC supply in series with its channel, and the external 24 VDC supply that powers the module can serve that role. The readout in this loop already has its own supply, so its output pair lands on CH+ and CH- directly and no loop power comes from the PLC side.
Why does the scaled value jump to a huge number when the loop opens?
8000h in a channel is the module's broken-wire flag, not a measurement. As a binary number 8000h is 32768, and scaling it against a 4095-count span produces about 800 percent, so the flag travels through the scale instruction like real data. Compare the raw value against 8000h before scaling and drive the engineering value to a fault state instead.
Should I bypass the readout and wire the slide gate monitor straight to the module?
Only after confirming the monitor's own output is a 4-20 mA current source. In the reported loop the readout generates the loop current, and the monitor may feed it something else entirely, such as a voltage or a contact. Bypassing also removes the local indication. Check the sensor's data sheet first; if its output is not a compatible current source, the readout stays in circuit.
Do I need IBox 460, or can I read the slot's V-memory directly?
You can. The module's data appears in the V-memory range assigned to its slot, so plain ladder can read it, but the raw representation then arrives unconverted and you own the BCD or binary handling. IBox 460 exists to select the slot and channel and deliver the value in one declared format, and that declared format is what decides whether IBox 423 or IBox 403 scales it correctly.