Why two PLC outputs must not share one motor starter coil

PLC programming Published 7 min read By IMDHMI controls team

Short answer

Never land two PLC output wires on one starter coil terminal. Put both processors on one EtherNet/IP subnet, produce the old run command as a tag in the retiring controller, consume it in the new one, and OR it into the rung that drives the single physical output. That keeps every command visible in logic and survives a phased migration.

On this page
  1. Two sources on one coil screw: what actually collides
  2. The shortcuts that get tried, and where each one stops working
  3. Put both processors on one EtherNet/IP subnet and hand the command over as a tag
  4. ORing the migrated starter's two commands in the new controller
  5. Program the connection-loss path before the migration day
  6. Test the handover with the motor locked out
  7. Faults that show up after the handover
  8. Questions asked

Two output wires on one motor starter coil terminal is the one thing not to do. Land only the new controller's output point on the coil screw, put both processors on the same EtherNet/IP subnet, produce the old run command as a tag in the retiring controller, consume it in the new one, and OR it into the rung that drives the single physical output. Two output stages tied to one load back-feed each other, and neither program can tell what the coil actually saw. The produced/consumed tag keeps every command visible in logic, fits a phased migration where logic moves to the new processor over weeks, and leaves exactly one branch to delete when the old processor retires. This article covers why the hardware OR fails, the tag handover with the rung arithmetic worked out, the connection-loss behavior, and the bench test before the motor runs again.

Two sources on one coil screw: what actually collides #

Each discrete output point is built on the assumption that it is the only device driving its line. Land a second output wire on the same coil terminal and that assumption breaks in a specific way: when one point conducts and the other is off, the full control voltage sits across the off point. A transistor or triac output that is off is not an open contact — its leakage path and protection circuitry now carry current that was meant for the coil, and a stage that fails short can hold the starter pulled in with neither program able to drop it.

The damage is not only electrical. Two independent output circuits tied to one load are invisible to each other's diagnostics: a fault, a force, or a program-mode stop in one processor changes what the coil sees, and the other program has no way to know. The decision is simple, and it holds for every shared load in the panel: pick one physical driver before any wire moves.

The shortcuts that get tried, and where each one stops working #

  • Two wires on one coil screw. The back-feed and the shorted-stage risk described above. Never do this on a live starter.
  • Paralleled relay output cards. Relay contacts are isolated from their electronics, so this is the only case with an electrical argument — but it works only when both cards share the same control supply and rating and the commons are deliberately linked. It is a field-wiring trick the next technician who opens the panel will not expect.
  • A diode OR terminal block. It stops back-feed on a DC coil and does nothing for an AC coil. Even where it conducts, it is still a hardware OR of two controllers: an extra part to maintain, and both programs blind to the coil's real state.
  • Forcing the old output off. A force is an edit-room tool, not an interlock. It disappears the day someone clears it, and until then the old processor is a hidden dependency nobody documented.

Put both processors on one EtherNet/IP subnet and hand the command over as a tag #

The handover has one hard documented constraint: for two controllers to share produced or consumed tags, both must be attached to the same subnet — you cannot bridge a produced or consumed connection over two networks. So the migration needs no new network hardware. Put the retiring processor and the new one on the existing subnet and confirm each can reach the other before any logic is written.

Then move the command. In the old processor, hold the run command in a controller-scope tag and configure it as produced. In the new processor, create a consumed tag with the same name and the same data type, addressed to the old controller's path in the I/O tree, and set the produced tag's consumer connection count to the number of consumers. The walkthrough on configuring produce and consume tags on CompactLogix controllers covers those dialogs step by step.

One safety note, and it belongs here: if the starter coil is part of a safety function, keep that function hardwired. Produced and consumed safety tags over concurrent communications are supported only on GuardLogix 5580, ControlLogix 5590 and Logix SIS controllers, so a migration pair without one of those cannot carry a safety command this way.

ORing the migrated starter's two commands in the new controller #

This worked example uses the migration case: one starter coil, an old processor that still runs it, a new processor taking over. Four inputs, with names that are illustrative — the produced and consumed names must match each other, but the words themselves are yours:

  • New_Motor_Run, BOOL, internal to the new controller — the rung its own logic already develops.
  • Old_Motor_Cmd, BOOL, controller scope, produced by the old processor and consumed by the new one.
  • ConnOK, BOOL, the health status of the consumed connection, read in the new controller.
  • Motor_Starter_Out, BOOL, the one output point wired to the coil.

The rule in words: the coil follows the new command, or the old command, but only while the old processor is actually present on the network; every other state drops the starter.

The arithmetic, evaluated each scan:

|--[ New_Motor_Run ]--+--[ (Motor_Starter_Out) ]
|                     |
|--[ Old_Motor_Cmd ]--+--[ ConnOK ]

Motor_Starter_Out := New_Motor_Run OR (Old_Motor_Cmd AND ConnOK)

Three cases settle it:

  • Old command true, connection healthy: 1 OR (1 AND 1) = 1 OR 1 = 1 — the coil energizes through the single wired point.
  • Old command true, network cable pulled from the old processor: 1 OR (1 AND 0) = 1 OR 0 = 0 — the coil drops, because the stop default is built into the AND.
  • New command true, old processor gone: 1 OR (0 AND 0) = 1 — the new logic runs the starter on its own.

The result: one energization source, evaluated in one controller, one wire on the coil screw. The decision it leads to: every command arriving from a second processor enters through a consumed tag and a branch shaped like this one — a second wire is never the answer — and when the old processor finally retires, deleting that branch is the whole cleanup.

Program the connection-loss path before the migration day #

The consumed tag reports whether its connection is up. If the old processor faults, is power-cycled, or loses its cable, the value goes stale and the connection faults. Gate the old branch with that status, as the rung above does, and choose the safe default: for a motor starter, loss of the old command means the starter drops out.

One physical fact to plan around: the command now crosses a network, so it carries the latency of the subnet rather than the microseconds of a wired contact. Keep anything that needs deterministic response time on direct I/O.

Test the handover with the motor locked out #

  1. Lock out and tag the starter. Toggle the old command in the old processor and confirm the consumed tag changes in the new one.
  2. Drive the rung from each branch alone — new logic only, old tag only, both, neither — and confirm the output matches the truth table from the worked example every time.
  3. Pull the network cable from the old processor and confirm the consumed connection faults and the rung drops.
  4. Place the old processor in program mode while only its branch is active and confirm the coil drops out.
  5. Inspect the coil terminal: one wire, from the new controller, with the old output point unwired.

Faults that show up after the handover #

Symptom Likely cause
Consumed tag never updates Produced and consumed names or data types do not match, or the new controller is not configured as a permitted consumer
Motor drops out whenever the old processor is edited Its command went false in program or fault mode — expected behavior; plan the changeover window around it
Starter runs with no command from either program Stale consumed value with no connection-status gate on the old branch
Output stage failed after a paralleled-wiring attempt Back-feed between two output stages; replace the card and move to the single-output design

Questions asked

Can two PLC output cards ever share one starter coil?

Only relay output cards have a chance, because their contacts are isolated from the output electronics. Even then it works only when both cards use the same control supply and voltage rating and the commons are deliberately linked, which is a field trick the next person opening the panel will not expect. Solid-state output points cannot be paralleled: an off point still leaks and back-feeds. Build one physical output per load and pass every other command through logic.

Can two ControlLogix processors share one run command over the network?

Yes. Configure a controller-scope tag in the old processor as produced, create a consumed tag in the new processor with exactly the same name and data type, and set the produced tag's consumer connection count to the number of consuming controllers. Both processors must sit on the same subnet, because a produced or consumed connection cannot be bridged across two networks.

Does a diode OR terminal make paralleled outputs acceptable?

It blocks back-feed only on a DC coil; an AC starter coil gets no protection from a diode at all. Even on DC it remains a hardware OR of two controllers: an extra component to maintain, and neither program can see the true state of the coil. It is a stopgap during a cutover at best, not a design.

Do I need a second physical network for the produced tag?

No. Both processors join the existing EtherNet/IP subnet and the produced and consumed connection runs over it. Adding a second physical network would break the design rather than help it, since that connection type is documented as not bridgeable across two networks.

Keep reading

  • How-to

    PLC motor interlock logic for three one-at-a-time motors

    Put an examine-off contact of each other motor's output bit into every motor rung, so each motor runs only while the other two outputs are off. With the example rung order, a simultaneous pair of start presses resolves to the first rung in the scan; the software interlock prevents commanded overlap and is not a safety function.

    PLC programming

  • How-to

    Scaling a PLC-5 FLEX analog output from PID 0-4095 to 0-30840

    A PLC-5 PID drives its control variable from 0 to 4095, while a FLEX analog output channel configured for the current loop expects output data from 0 to 30840, so a raw CV gives 6.125 mA at 100 percent. Leave the PID limits at 0 and 100 percent, scale the control variable times 30840 divided by 4095 into a separate integer word, and point the BTW at that word. The CV word and the BTW data word must be different addresses.

    PLC programming

  • How-to

    Set up a CLICK PLC 4-20 mA pressure trip with a relay output

    Wire the two-wire loop into channel 1 of a C0-04AD-1, set that channel to 4-20 mA with 4 mA scaled to 0 PSI and 20 mA to 300 PSI in DF1, and drive relay output Y1 from Set and Rst coils that trip above 250 PSI and release below 230 PSI, with a loop-fault test below -10 PSI.

    PLC programming