IMDHMIControls LibraryShop main store

Troubleshooting

Why the TP700 Comfort watchdog shows no communication loss alarm

PLC programming Published 7 min read By IMDHMI controls team

Short answer

A watchdog time only marks the HMI connection faulty; it puts nothing on screen. The message appears when the panel's system diagnostics are selected under Alarms > Controller alarms in Runtime settings and the alarm display the operator actually has open includes system events and active alarms. Prove both halves with one timed outage longer than a single watchdog interval.

On this page
  1. What the watchdog time does and does not do
  2. Prove detection first with a timed outage
  3. The checks in order
  4. Reading the result
  5. Report the loss somewhere other than the panel
  6. The decision for each case
  7. Questions asked

Your watchdog time is almost certainly working. A watchdog has exactly one job: when the data exchange with the CPU stops for longer than the configured interval, the panel marks that connection faulty. It never puts anything on the screen. The message you want is a system alarm, and the panel only raises and shows one when two further things are configured: "System diagnostics" is selected in the TP700 Comfort's "Runtime settings" under "Alarms > Controller alarms", and the alarm view the operator actually has open includes system events, shows active alarms, and sits on a screen reachable without data from the S7-1200. Configure the detection, then configure the presentation, then prove both with one timed outage. The checks below separate the two halves so you know which one is missing.

What the watchdog time does and does not do #

The watchdog time on the HMI connection is a supervision interval for that connection: when no expected data exchange arrives for the whole interval, the panel sets the connection status to faulty. That status is an internal state. Unless something displays it, an expired watchdog is invisible to the operator, which is exactly the symptom you are looking at.

Keep it separate from the watchdog time that STEP 7 documents for PROFINET IO devices; that one monitors the cyclic data exchange between an IO device and its IO controller. A TP700 Comfort on this link is an HMI, not an IO device. Sharing the PROFINET network does not turn an HMI outage into an IO watchdog event, so nothing in the IO watchdog will make this message appear.

Three layers must all work, and each is configured in a different place:

  • Supervision: the watchdog time on the HMI connection sets the connection status when the interval expires.
  • Alarm generation: the "System diagnostics" option in "Runtime settings" makes the panel raise these status changes as system alarms.
  • Presentation: the alarm view's class and status filters and the screen navigation decide whether anyone ever sees it.

Prove detection first with a timed outage #

Begin with a healthy system: put a counter in the CPU program that visibly increments on a panel screen and confirm the connection status shows no fault. Without that baseline, a silent result proves nothing.

Then, with the machine in a safe state, interrupt the link and time it. Example values: the connection's watchdog time is 5 s and you pull the connector for 15 s. The 15 s outage spans three complete 5 s intervals, so the panel declares the connection faulty 5 s into the outage, leaving 10 s in which the fault indication can appear before the link returns. Two results follow directly. An outage shorter than one interval produces nothing, and that is correct behavior, not a fault. An outage that spans several intervals with no connection-fault indication anywhere means the interval in the project is not the value you believe, or the setting supervises something other than this connection; re-read the setting's help in your TIA Portal version before changing any number.

The checks in order #

Run them in this order; each decision gates the next:

  1. Record the watchdog time configured on the HMI connection and read its help text in your TIA Portal version. Decision: a setting that supervises this connection's data exchange can only ever set the connection status, so keep it and continue; a setting that supervises a process value or anything else is the wrong knob, and no alarm will ever follow from it.
  2. Establish the baseline: the counter value follows on the panel and the connection status shows no fault. Fix any existing connection problem before testing alarm behavior.
  3. In the project tree, open the TP700 Comfort's "Runtime settings" and select "System diagnostics" under "Alarms > Controller alarms". This is what turns connection status changes into system alarms the panel runtime can show. If the controller also sends alarms of its own, activate "Automatic update" for the HMI connection under "Runtime settings > Alarms > Controller alarms". Compile and download.
  4. Repair the presentation path. In the alarm view the operator uses, the class selection must include the system events; a view filtered to your own alarm classes silently drops the connection message. Its status selection must include active alarms, because a history-only view shows the event only after the link is back. The view must sit on screens reached by fixed screen-change buttons; a screen selection that depends on values read over the failing connection locks the operator out of the one screen that matters. The "Alarms" menu of "Runtime settings" also carries the "System events" display settings that decide what the standard alarm display shows during runtime. For the alarm view configuration in detail, showing a PLC connection fault on a Comfort Panel alarm display walks that setup step by step.
  5. Repeat the timed outage and watch the operator's alarm view, not your engineering station. Expected result: the connection-fault message appears while the link is down and remains in the alarm buffer as a past alarm after the link returns.
  6. Stand at the panel the operator uses and navigate the way the operator does. A message visible on the engineering screen but nowhere at the panel is a navigation or view problem at that station, not a detection problem.

Reading the result #

Observation during the timed outage Meaning Action
Connection-fault message in the alarm view Detection and presentation both work Record the test as passed
Connection status faulty, but no message anywhere "System diagnostics" off, or the view's class or status filter hides the event Select "System diagnostics" under "Alarms > Controller alarms"; include system events and active alarms in the view
No fault indication and the screen values are frozen The outage was shorter than one watchdog interval, or the setting supervises another connection Repeat with an outage several intervals long; re-read the setting's help for your version
The message exists but the operator cannot reach it Navigation at that station depends on values read over the failing connection Put the diagnostics view behind fixed screen-change buttons on every relevant screen
Panel dark or rebooting Nothing running on the panel can announce its own failure Report the loss from outside the panel, as in the next section

Frozen numbers or question marks on the screens during the outage are the display layer's reaction to lost updates, not the raised event; article:why-hmi-values-show-question-marks-plc-comms-timeouts covers what the panel shows when those timeouts expire. Neither behavior informs the operator unless the alarm configuration above is in place.

Report the loss somewhere other than the panel #

A panel cannot display its own power loss, and a PLC alarm bit cannot be delivered over the connection that just failed. If someone must know when the panel is gone, the observer has to sit outside the failed path. Two patterns work. The CPU watches a tag the panel toggles and raises the condition on a station it still reaches when the toggling stops; size the window from the tag's production period, so with a tag the panel writes every 1 s, a 3 s window misses three writes before declaring the fault, and the same timed outage then proves both halves. Or raise the condition at the supervisory level, where the link between the SCADA station and its sources is supervised on its own terms; article:how-to-create-a-scada-plc-communication-alarm-for-link-loss builds that alarm on the SCADA side.

Interrupt the link only with the machine in a safe, approved state: while the panel is down the operator loses view and controls even though the CPU keeps running, and a communication alarm is diagnostics, not a safety function.

The decision for each case #

  • Watchdog expires and no message ever appears: apply checks 3 and 4, download, and repeat the timed outage. This is the usual answer: the watchdog was configured and the alarm path was not.
  • The message shows on the engineering screen but not at the operator's station: it is navigation or a different view at that station; rebuild the operator's path with fixed buttons.
  • The outage you tested was shorter than one watchdog interval: expected silence, not a fault; test again with an outage several intervals long.
  • The panel is dark or crashed: no panel-side setting helps; raise the condition in the CPU or at the SCADA station.
  • The link is up but the values stop changing: the watchdog will not catch it; use the toggling tag and the CPU-side observation window.

Questions asked

What watchdog time should I set on the TP700 Comfort connection?

Set it from how fast the operator must learn of the loss. For a worked example: at 5 s, a 15 s outage is declared faulty 5 s in, with 10 s of indication before the link returns, while a 2 s outage with the same setting correctly produces nothing. Choose the value, then prove it with a timed interruption at the panel.

The fault message appeared during the outage but vanished once the link came back. Where did it go?

Nowhere wrong. When the connection recovered, the event moved from active to past. A view whose status selection shows only active alarms drops it as soon as the link is healthy again. Include past alarms in that view's status selection or open the alarm buffer after the event, and the outage stays on record for the shift handover.

Does switching on system diagnostics affect the alarms my PLC program sends to the panel?

No. Alarms triggered from the controller program travel through the configured connection and follow your alarm and view configuration as before. The system diagnostics option governs the events the panel itself raises about the connection and the controller status, which is why it must be on for the connection-loss message even when your own alarm traffic already works.

Screens froze and fields showed question marks during the outage. Is the watchdog failing?

No. Frozen or substituted fields are the display layer's reaction to missing updates, not a raised event. The watchdog has failed only when an outage longer than the interval produces no connection-fault indication anywhere. Keep the three layers apart: connection status says the link is down, the alarm configuration decides who is told, and what the fields do is neither.

Keep reading

  • Troubleshooting

    Why HMI values show question marks: PLC comms timeouts

    Yes — a running PLC program can cause intermittent HMI timeouts by consuming nearly all controller execution time, and clean Ethernet counters do not clear it: utilization measures bytes, not the cost of servicing requests. Work controller load first: Task Monitor above 90% on the dropping units against 7–15% on healthy ones, then message pacing, packet-rebuild address forms, read grouping, and power last.

    PLC programming

  • How-to

    Write an S7-1200 heartbeat in ladder logic in TIA Portal

    Tie the light to a detector, not to the heartbeat level: time the on half with one TON and the off half with a second TON, both at three times the measured state time, and OR the two done bits into one communication-fault coil. With a PC heartbeat that changes once per second, PT is 3 s and the fault trips 3 s after the last change; add TCON and TDIAG supervision when the PLC owns the TCP connection.

    PLC programming

  • Explainer

    PLC tags or a communication DB in TIA Portal for HMI data

    TIA Portal assigns DB offsets itself: clear Optimized block access and the Offset column appears, but no documented control lets you type an offset. So keep I/O and global signals in PLC tags, put the HMI and SCADA exchange in one dedicated non-optimized communication DB, pad alarm bytes with spare Bool members, and snapshot values before every DB change.