PLC programming Published 7 min read

Short answer

The IM 153-2 is the PROFIBUS DP slave head of an ET 200M station, so it cannot sit on an S7-300 central rack backplane, and the CPU 313 has only an MPI port, so no DP master exists to own it — hence SF lit and STOP blinking. Move the head module to its own rack with its own supply, add a CP 342-5 as DP master, and configure the slave in HW Config.

On this page
  1. Why the CPU stops with SF lit and STOP blinking
  2. The IM 153-2 belongs under a DP master, not in the rack
  3. Why the CPU 313 cannot be that master
  4. The hardware that makes the station work
  5. Configure the DP master and the remote slave
  6. Worked example: byte counts and bus addresses
  7. Verify the station
  8. The decision for your case
  9. Questions asked

Move the IM 153-2 out of the central rack: it will never run there. The 6ES7 153-2BA01-0XB0 is the PROFIBUS DP slave head module of an ET 200M distributed I/O station, not a module for the S7-300 backplane, so the CPU 313 rejects it at power-up and holds STOP with SF lit. The second gap is that this CPU, order 6ES7 313-1AD03-0AB0, has an MPI port only, so no DP master exists anywhere in the station to own a slave — which is exactly what STEP 7 tells you with "A DP Slave can only be inserted in a PROFIBUS master system". The fix is physical first, then software: a second rack with its own power supply for the IM 153-2, a DP master such as a CP 342-5 in the main rack, and a PROFIBUS subnet configured in HW Config.

Why the CPU stops with SF lit and STOP blinking #

The LEDs are the power-up check talking, not a fault in your program. At startup the CPU compares the modules it finds on the backplane against the hardware configuration it holds. An IM 153-2 on a central-rack connector is hardware the configuration cannot describe at that position, so the check fails and the CPU announces it:

  • SF, red, on solid — the physical station does not match the configured one.
  • STOP, orange, blinking slowly, roughly a second on and a second off — the CPU refuses to start until the mismatch is gone.
  • Pull the IM 153-2 out and the CPU starts again with the two I/O modules it knows.

For the reason in words, open Module Information for the CPU and read the Diagnostic Buffer: the startup entries name the offending slot. The engineering tool reports the same fact from the other side. A DP slave needs a PROFIBUS master system object to attach to, this project has none, and that is why every insert attempt dies with the message you have been seeing.

The IM 153-2 belongs under a DP master, not in the rack #

The ET 200M is a distributed I/O station: an IM 153-x head module carrying ordinary S7-300 I/O modules on its own rail, linked to the controller over PROFIBUS-DP. The manufacturer's documentation describes the station as S7-300 configuration technology — an IM 153-x plus S7-300 I/O modules — but as a DP slave station, not a central rack extension. Its connector mates with its own rail, it feeds itself locally, and it has no function on the CPU's backplane. That is the whole reason for the LEDs above.

As a slave it behaves like any other device on the bus: it waits under a PROFIBUS master system, takes one slave address, and exchanges its I/O bytes cyclically. That is the same master-plus-slave structure you work through when connecting a Beckhoff BK3150 PROFIBUS-DP slave to an S7-300; the IM 153-2 is just the head for S7-300-style I/O instead of terminal blocks.

Why the CPU 313 cannot be that master #

This CPU is a plain CPU 313. Its only port is MPI, the programming port; there is no integrated PROFIBUS DP interface and no setting that turns it into a DP master. Even a correctly housed IM 153-2 would sit on the bus with nothing to talk to. The MPI port stays yours for the programming device, and the DP master you add lives on its own separate subnet, so the two never interfere.

The missing piece is hardware, not a parameter: put a DP master in the main rack, or move to a CPU that carries DP on board.

The hardware that makes the station work #

Power both racks down before moving modules — central-rack and remote-station modules are not hot-swappable. Then build:

  • Main rack: an S7-300 power supply (for this bench, a 5 A unit is ample), the CPU 313, and a CP 342-5 communications processor as the PROFIBUS-DP master on a free slot — slot 4 in this example. Your existing DI16 and DO16 stay central.
  • Remote rack: its own 24 V supply, the IM 153-2 head, and S7-300 I/O modules on its rail. The head gives eight module positions, slots 4 to 11 in the configuration.
  • Cable: two-core shielded PROFIBUS cable, 150 Ω characteristic impedance, with 9-pin D-sub connectors and terminating resistors. Switch the resistors on at the two physical line ends only, off at every tap between them.
  • The remote rack feeds itself locally and never draws power from the CPU rack's backplane.

Configure the DP master and the remote slave #

  1. Open the project in SIMATIC Manager and start HW Config for the station.
  2. Insert the CP 342-5 on the free slot from the hardware catalog.
  3. In the CP's interface properties, create a new PROFIBUS subnet. Keep the master at address 2, the default for a new subnet, and set the transmission rate to 1.5 Mbit/s — a safe bench rate. The CP can run up to 12 Mbit/s once the cable plant is proven; nothing on this station needs it.
  4. In the catalog under PROFIBUS-DP > ET 200M, drag the IM 153-2 onto the master system line and give it slave address 3. Every device on the subnet holds exactly one unique address, master and slaves alike.
  5. Drag the DI16 and DO16 into the head's module slots if you are distributing the I/O. If your STEP 7 version lacks the exact IM 153-2 variant in the catalog, install its GSD file first, through Options > Install GSD File in HW Config.
  6. Compile and save the station, then download the configuration to the CPU.
  7. Power the remote rack last, after the CP 342-5 is up, so the slave is on the bus when the master runs its parameterization pass.

Worked example: byte counts and bus addresses #

Check the arithmetic against your own modules:

  • DI16: 16 input points ÷ 8 points per byte = 2 input bytes.
  • DO16: 16 output points ÷ 8 points per byte = 2 output bytes.
  • One slave station carrying both modules therefore moves 2 input bytes and 2 output bytes per bus cycle.
  • Bus addresses: master at 2, slave at 3, and no other station on the subnet may use either number.

With a CP 342-5 as master, the program exchanges that data through the CP's function blocks as consistent blocks rather than reading the slave's bytes out of the local process image, so expect the slave's bytes to arrive through the CP's exchange calls, each module's bytes kept together as one unit.

Verify the station #

  • Diagnostic Buffer after the download: clean startup entries, no slot-mismatch line.
  • CP 342-5: RUN steady green, no red SF, BUSF dark. A lit BUSF means baud rate, slave address or termination — check those three in that order.
  • IM 153-2: SF and BF dark on the head once the bus is up.
  • Write a 1 to the first remote output bit from a variable table and watch the DO module's channel LED follow.
  • If the slave joins the bus but its data stays empty, compare each module's byte addresses against the configured transfer area — the same root cause that appears when an S7-300 PROFIBUS gateway is detected but reads no I/O data.

The decision for your case #

  • Learning on the bench with the CPU you own: add the CP 342-5, build the second rack with its own supply, and configure the subnet as above. That answer also runs a real machine later.
  • Lab-only, where a PC can stay wired in: a PC with a PROFIBUS interface card and SIMATIC NET software takes the DP master role. Fine for experiments; not a controller for a machine that must run unattended.
  • Buying parts anyway: a compact CPU with DP on board, the CPU 313C-2 DP, replaces both the CPU 313 and the CP, and the IM 153-2 hangs off the integrated DP port.
  • No configuration puts the IM 153-2 back into the central rack: it has no central-rack function, and the slot check will reject it every time.

One lifecycle point before you order: more than 250 S7-300 and ET 200M assemblies enter the phase-out period from 1 October 2025, so check the manufacturer's discontinuation bulletins for the exact CP and head module you plan to buy.

Questions asked

Can a laptop running STEP 7 take the DP master role instead of a CP?

Yes, for bench work. A PC with a PROFIBUS interface card and SIMATIC NET software can run as DP master with the IM 153-2 as its slave, and an OPC server on that PC can pass the data to other programs. The PC has to stay attached, so it suits experiments and demos, not a machine that has to run unattended.

Which CPU could master the IM 153-2 without a separate CP?

A compact CPU with an integrated DP interface, for example the CPU 313C-2 DP, order number 6ES7 313-6CF03-0AB0. Its DP port runs as DP master, so the IM 153-2 connects straight to it, the CP 342-5 becomes unnecessary, and you keep the same S7-300 rack and programming workflow.

Does adding a DP master cost me the port I program through?

No. The CPU 313's MPI port stays available for the programming device at its default 187.5 kbit/s. The CP 342-5 brings a separate PROFIBUS subnet with its own connector and its own addresses, so programming traffic and DP traffic never share a port.

Can I keep the DI16 and DO16 modules I already have?

Yes. S7-300 signal modules work in both places: they can stay in the central rack with the CPU or move onto the rail next to the IM 153-2, and you choose per module while building the station in HW Config. Their byte counts and catalog entries are the same wherever they sit.

Keep reading

  • How-to

    Read DP slave diagnostic addresses with SFC51 on an S7-300

    SFC51 RDSYSST with SSL ID 0x00B4 selects a DP slave by its configured diagnostic address, and that address never comes from the 0x0092 station list: station numbers and diagnostic addresses live in separate addressing domains with no conversion between them. Read the address from the documented 0x00B status list family or from the hardware configuration, then call 0x00B4 once per address.

    PLC programming

  • Selection guide

    Choosing a CP-341 or gateway for an S7-300 Modbus RTU slave

    For an S7-300 that must answer as a Modbus RTU slave, a PROFIBUS DP-to-Modbus RTU gateway is the lower-effort route: no separately licensed loadable driver and no serial code in the CPU. Choose the CP-341 with its Modbus Slave (RTU) driver only when the link must be independent of the fieldbus or when you need a per-write flag such as CP_NDR. Before ordering, confirm the exact gateway variant runs DP slave and Modbus RTU slave simultaneously.

    Industrial networks

  • How-to

    Connecting an S7-1200 to a PROFIBUS slave through a CM 1243-5

    An S7-1200 cannot speak PROFIBUS from any built-in port: its onboard Ethernet is PROFINET. PROFIBUS DP-V1 master duty needs the CM 1243-5 communications module in the S7-1200 rack. Confirm the remote device is a PROFIBUS slave, import its GSD into TIA Portal, give it a bus address no other station uses, and terminate the segment at both ends.