Why STARTER routing to G120 PROFIBUS drives stays local
Short answer
STARTER reverts Via Router to Set for Local when the access point is Device instead of S7ONLINE, and routed Ethernet-to-PROFIBUS access to a G120 needs Control Unit firmware V4.7 or later. This 26-drive fleet runs V3.x and V4.6, so connect the PG to the DP segment directly with the cable specified for 12 Mbit/s PG use, 6ES7901-4BD00-0XA0, or update the firmware first.
On this page
The Via Router setting in STARTER keeps falling back to Set for Local because the access point is Device. With that access point the tool treats your PC as a station on the PROFIBUS subnet itself, cannot fill the routing fields, and discards the setting when the dialog closes. Routed access from Ethernet through the CPU also needs a G120 Control Unit at firmware V4.7 or later, and this fleet runs V3.x and V4.6. The connection that works today goes to PROFIBUS directly, at 12 Mbit/s, with the PG cable specified for that rate: order number 6ES7901-4BD00-0XA0. This article explains why the setting reverts, counts the fleet's firmware against the routing threshold, and gives the connection steps.
Why the Via Router setting reverts to Local #
Two access points behave differently, and only one of them can route:
- Device: STARTER treats the PC as a stand-alone station on the DP subnet. Your PC hangs off the panel's Ethernet switch, so the tool finds no DP nodes at all, and when you reopen the communication interface dialog the field has fallen back to Set for Local. Typing an IP address there does not fix this, because manual entry through this access point requires three values you supply yourself: the IP of the PLC, the S7 subnet ID the drives sit on, and the target DP address of the drive.
- S7ONLINE: with the matching project loaded, STARTER fills the routing addresses from the hardware configuration on its own, and the Via Router selection persists because the route now resolves end to end.
Both paths still need the drive to answer routed S7 frames, and that is what the firmware decides.
The firmware rule for routed access #
The vendor's FAQ on routed online access states that the G120 answers S7 routing again as of Control Unit firmware V4.7, even when the online connection arrives through the CPU's routing. Below that version the drive does not respond to routed frames, so a search from the Ethernet side lists only TCP/IP stations — the CPU and the HMIs — and never the DP addresses. That is exactly what a PG set to TCP/IP shows on this machine, while a plain PC on a PROFIBUS adapter sees every node. The broader checks for this symptom are set out in Why STARTER cannot go online to a G120 over PROFIBUS routing.
Counting firmware versions on the 26-drive G120 fleet #
Inputs. 25 drives report firmware V3.x and one reports V4.6, the versions shown on this machine; the routing threshold is Control Unit firmware V4.7, from the vendor's routed-online-access FAQ.
Rule. A drive answers routed S7 online access only at firmware V4.7 or later.
Arithmetic. 25 + 1 = 26 drives in the fleet. V4.6 sits below V4.7, and every V3.x release is below it as well, so 0 of the 26 drives meet the threshold.
Result. No drive in this fleet can be reached by routed Ethernet-to-PROFIBUS access, whatever the access point is set to.
Decision. Stop reworking the Via Router dialog against this firmware. Either schedule a Control Unit firmware update to the routing-capable release, or take the direct PROFIBUS connection in the next section. A Control Unit firmware update restarts the drive, so run it with the machine stopped and nobody in the hazard zone.
Connecting on PROFIBUS at 12 Mbit/s #
The resolution on this machine changed the router from Ethernet to PROFIBUS. A standard PG-to-DP cable does not hold a connection at this bus rate; the cable specified for PG use here is 6ES7901-4BD00-0XA0. The routing device was added as a new PROFIBUS station in the hardware configuration and downloaded, giving the DP segment its own entry point.
- In the interface settings on the PG, select the PROFIBUS interface of the adapter instead of TCP/IP.
- Connect the cable from the PG to a spare PROFIBUS plug on the segment, and switch the terminating resistor in if you use the plug at the end of the line.
- Run the accessible-nodes search. The G120 nodes now appear with their DP addresses instead of only Ethernet stations.
- Right-click the drive object and go online through the Target Device menu, with access set local on PROFIBUS rather than Via Router.
If you would rather work from the Ethernet side once firmware allows it, Connecting STARTER to a PROFIBUS drive through an S7-300 covers the wired access path through the CPU, including the cable and termination practice.
When the fault is something else #
An A08526 alarm is not this problem. It reports that a drive which was already exchanging cyclic telegrams has lost them, which points at the network or telegram configuration during operation rather than at commissioning access; Why a PROFINET drive reports A08526 no cyclic connection works that symptom separately.
Questions asked
How can I check which routing addresses STARTER has filled in?
Right-click the drive object, open the Target Device menu and choose the online access entry, then look at the module addresses it lists. Those fields show the route the tool resolved for that drive. When the fields stay empty while you are routed, the drive is not answering, which is the expected behavior on firmware older than the routing-capable release.
Where is the Control Unit firmware version shown?
Locally, the version sits in the device information screens of the Control Unit's own display. On a direct PROFIBUS connection, the accessible-nodes list in STARTER shows each node, and the drive object properties show the firmware. Record every drive before planning the update so the count reflects the fleet, not one label.
Does the special cable matter at lower bus rates?
The order number 6ES7901-4BD00-0XA0 is specified for PG connection at 12 Mbit/s. At slower PROFIBUS rates a standard PROFIBUS PG cable carries the signalling, but if the segment runs at the full rate, use the specified cable rather than testing whether a generic one holds.
Do the HMIs need the Via Router setting too?
No. The access point and Via Router fields are settings of the commissioning tool on your PG, not of the operator panels. The HMIs read the drives through the PLC's process data and their own driver connection to the CPU, so their communication keeps working exactly as before while you sort out routed access.