Why PROFINET RT and IRT need different PC hardware

Industrial networks Published 6 min read

Short answer

HSE, EtherNet/IP and PROFINET NRT run on a stock PC Ethernet NIC because they ride on IP and TCP or UDP. PROFINET RT also runs on stock hardware if the stack sends raw Ethernet frames and the PC stays on one segment. Only IRT needs dedicated time-scheduled hardware, and a PC connects to an IRT cell through ordinary Ethernet ports only.

On this page
  1. Which layers each protocol actually uses
  2. What each channel asks of the PC NIC
  3. What PROFINET RT costs a PC
  4. Why IRT needs dedicated hardware
  5. The decision for each case
  6. Questions asked

A PC with an ordinary Ethernet NIC runs FOUNDATION Fieldbus HSE, EtherNet/IP and PROFINET NRT, because all three carry their data inside IP packets over TCP or UDP. PROFINET RT also runs on stock PC hardware, on one condition: the protocol stack must send and receive raw Ethernet frames, and the PC must sit on the same network segment as the devices. Only PROFINET IRT needs dedicated hardware, because it needs a network interface with a time-scheduled Ethernet MAC. The suspicion that PROFINET is hard on a PC holds for IRT alone.

Which layers each protocol actually uses #

Ethernet (IEEE 802.3) covers layers 1 and 2 only. IP is layer 3 and TCP and UDP are layer 4, and the stacks are independent: TCP/IP also runs over a modem or ADSL link with no Ethernet at all. HSE and EtherNet/IP do not live at the link layer. Both put application data inside IP packets, which is why any NIC with a working IP stack carries them. EtherNet/IP explicit messaging uses TCP port 44818 and implicit I/O uses UDP port 2222.

PROFINET is the one family here that also writes raw Ethernet frames straight onto layer 2, bypassing IP and TCP or UDP exactly the way a classic fieldbus does. It does this on two of its three channels to keep protocol-stack delay off the cyclic path.

What each channel asks of the PC NIC #

Protocol Layers on the wire PC NIC requirement Crosses a router
FF HSE Ethernet + IP + TCP/UDP Any stock NIC Yes
EtherNet/IP Ethernet + IP + TCP/UDP Any stock NIC Explicit yes; implicit I/O needs multicast handling
PROFINET NRT Ethernet + IP + TCP/UDP Any stock NIC Yes
PROFINET RT Raw Ethernet frames, TCP/IP bypassed Stock NIC, stack with raw-frame access No
PROFINET IRT Time-scheduled frames Dedicated time-scheduled hardware No, one network section only

PROFINET also has two application models. CBA is the older component model, built on Windows COM objects and carried on the NRT channel. PROFINET IO addresses data by slots and indexes, the way PROFIBUS and Modbus do, and it is the model new designs use.

What PROFINET RT costs a PC #

An RT frame carries no IP header, so a router has nothing to forward: RT traffic stays inside one broadcast domain, and the PC joins it there. The NIC itself is ordinary. What the stack needs is raw-frame access, meaning the ability to hand layer 2 frames to the driver and receive them directly, rather than going through the IP stack. Without that, a PC cannot speak RT at all; with it, the OS scheduler sets the jitter, and you measure it rather than assume it. Capture the port in Wireshark and read the delta-time column on the cyclic frames to see the jitter your PC actually adds.

Before any of that means anything, the NIC needs an address in the device subnet. A laptop with no address on the coupler's subnet fails before any protocol starts, the way a P1AM-ETH ping fails because the laptop NIC has no subnet IP. The same discipline applies on the controller side, where a mismatched IP change can break the link entirely, as in a CODESYS PROFINET IP-change fault on an S7-1200 link.

RT traffic does share the cable with normal TCP/IP traffic, and the equivalent question on a controller port is whether one PN port can run Modbus TCP and S7 comms together. If the PC must reach the PROFINET devices from another subnet anyway, the path is a gateway, and a PROFINET IO-device gateway terminates the protocol rather than acting as a controller.

Why IRT needs dedicated hardware #

IRT reserves time slots in every cycle and schedules each real-time frame inside its own slot, with all IRT nodes synchronized to one clock. PROFINET development guidance is explicit: IRT requires a dedicated two-port industrial Ethernet MAC. A standard NIC with an OS-driven transmit path cannot guarantee when a frame leaves the wire, so it cannot hold a scheduled slot. That is why IRT endpoints use dedicated silicon such as the ERTEC family of protocol ASICs.

The bandwidth arithmetic shows why the scheduling matters. Take a 1 ms update cycle on a 100 Mbit/s segment:

  • Bits available per cycle: 100 Mbit/s × 0.001 s = 100,000 bits.
  • Reserve half for ordinary TCP/IP traffic, per the PROFINET design figure of about 50% Ethernet bandwidth left over: 100,000 ÷ 2 = 50,000 bits for scheduled frames.
  • Cost per minimum-size frame: 64-byte frame = 512 bits, plus an 8-byte preamble = 64 bits, plus a 96-bit interframe gap, so 512 + 64 + 96 = 672 bits per slot.
  • Slots per cycle: 50,000 ÷ 672 ≈ 74, which is why the guidance lands at around 64 devices with minimum frames per millisecond, with margin.

An OS-driven NIC cannot place a frame inside a 6.72 µs slot on demand; jitter in the millisecond range is routine for a loaded Windows stack. IRT traffic also stays within one network section: every node using IRT must be interconnected on the same segment, so there is no routing a PC into it.

The PC still joins the cell, just not as an IRT node. IRT-capable controllers provide ordinary Ethernet ports alongside the ports forming the IRT line, and the PC connects to an ordinary port for engineering and supervision. A capture there shows your engineering and diagnostic traffic and does not show the scheduled frames. Never add, remove or rewire a node in a running IRT segment; stop the line, make the change, and let the synchronization re-establish before restart.

The decision for each case #

FF HSE on a PC: yes, stock NIC. HSE targets process control, and the usual PC role is an OPC server that exposes HSE data to HMI, historian or engineering software. H1 field devices reach HSE through a linking device, so the PC never touches H1 directly. Put the PC and devices in one IP subnet or route between them deliberately. The cabinet host for that server or for a data logger is an ordinary computer; an industrial mini PC as the OPC server or logger host is the usual fit.

EtherNet/IP on a PC: yes, stock NIC. Open the explicit TCP session first with a port test to the device on 44818, then bring up the implicit UDP 2222 I/O connections. The explicit port fails fast and isolates routing and firewall faults before you chase I/O.

PROFINET NRT on a PC: yes, stock NIC. It is plain TCP/IP, including DCOM for the legacy CBA model. Nothing special is required.

PROFINET RT on a PC: yes, with two conditions. The stack must have raw-frame access, and the PC must stay in the same layer 2 segment as the devices. That is enough for cyclic I/O and PLC-to-PLC exchange where the update interval sits in the low milliseconds and the jitter you measured in the delta-time column fits under it. If the deadline tightens past what your measured jitter holds, move that node to dedicated hardware.

PROFINET IRT on a PC: never. IRT needs a time-scheduled hardware MAC that a PC NIC does not have, and IRT traffic stays inside one network section anyway. The PC attaches to an ordinary port for engineering and supervision and leaves the scheduled path to the hardware.

The one-line rule: any NIC that runs Windows Update can run three of the five rows in the table above; the fourth needs a raw-frame stack and one segment; the fifth needs silicon built for it.

Questions asked

Can PROFINET RT frames cross a router to a PC on another subnet?

No. An RT frame is a raw Ethernet frame with no IP header, so a router has nothing to forward and drops it. Put the PC in the same layer 2 segment as the devices, or install a gateway that terminates PROFINET on the field side and speaks TCP/IP to the PC. An IO-device gateway terminates the protocol rather than acting as a controller, so it does not turn the PC into a PROFINET controller.

Does EtherNet/IP implicit I/O work across subnets?

Explicit messaging over TCP port 44818 routes like any TCP traffic. Implicit I/O connections often use UDP multicast on port 2222, and multicast does not cross a router by default. Check IGMP snooping on the switches and the multicast TTL set in the scanner software before blaming the device. Unicast I/O connections, where the device supports them, remove the multicast limitation entirely.

Can a PC with an HSE OPC server read H1 field devices directly?

No. FOUNDATION Fieldbus H1 segments connect to HSE through a linking device that bridges the two. The PC addresses the linking device over IP and reads the H1 values through it. Point the OPC server at the linking device and confirm one live value with good quality in an OPC client before you wire that value into HMI or historian screens.

Does PROFINET RT traffic share the cable with normal TCP/IP traffic?

Yes. RT frames coexist with IP, TCP and UDP traffic on the same cable and the same switches; RT does not reserve time slots the way IRT does. The limit is bandwidth. In the 1 millisecond cycle worked out in this article, half the cycle stays free for ordinary traffic. IRT reserves slots instead, so non-real-time traffic is scheduled into whatever bandwidth remains.

Keep reading

  • Selection guide

    How to select a CODESYS fieldbus master for industrial Ethernet

    Select the master around the device, not the connector: the 750-340 is a PROFINET IO coupler, and a PROFIBUS station needs a different coupler. Confirm three matches — device protocol, runtime master package, supported network adapter — then size the bus cycle from the process budget; the worked example clears a 10 ms sensor-to-actuator budget at a 2 ms cycle and fails it at 4 ms. Bench-test a laptop NIC only if the runtime documents it.

    Industrial networks

  • How-to

    Run a PROFINET controller beside an EtherCAT master on ctrlX CORE

    Yes. The CODESYS Fieldbus Communication add-on is hardware independent, so the PROFINET controller runs on any standard Ethernet port other than the one bound to the EtherCAT master. Install and license the controller role, import the camera's GSDML, and put controller interface and camera on one subnet; no hardware change is needed.

    Industrial networks

  • Troubleshooting

    Fix ctrlX CORE PROFINET device not found with XF10 connected

    This is not a Siemens fault: DCP discovery runs at the Ethernet layer, so XF10 and XF51 answer in one broadcast domain through the same unmanaged switch whatever their IP subnets. Put the engineering port on its own switch or VLAN and confirm the device name on XF51, and the startup dependency disappears.