Troubleshooting
Why an S7-300 F-DO10 stays dark on SAFE with SF lit
Short answer
The F-DO10 rejects its F-parameter record because the PROFIsafe F-destination address wired on its rear DIP switches does not match the value the project sends. Set the ten rear switches to the project value, power-cycle the module, and SAFE lights while both SF LEDs clear.
On this page
An S7-300 fail-safe output module holds every output open until it has accepted a complete F-parameter record from the F-CPU, and it refuses that record whenever the PROFIsafe destination address wired on its rear DIP switches differs from the address the project sends. That single mismatch is what an SF LED that stays red on both the module and the CPU, next to a SAFE LED that never lights, describes on an F-DO10. The fix is to read the address from the F Parameters tab in the project, set the ten rear switches to that value, and power-cycle the module; no recompile or download of the safety program is involved.
What the SAFE and SF LEDs mean on an F-DO10 #
SAFE lights only after the module has accepted a valid F-parameter record and is running in safety mode; before that, the outputs stay passivated regardless of the safety program. SF is the group fault indicator: the module reports the fault and the F-CPU mirrors it, so both LEDs glow together. The combination SF red plus SAFE dark therefore means the module never entered safety mode, not that a safety channel tripped while running. If a sibling F-module in the same rack shows SAFE lit, the F-CPU, the compiled safety program and the F configuration pack are all working, and the problem belongs to this module's parameters alone.
Reading the diagnostic buffer #
Bring the station online in STEP 7 and open the module diagnostic buffer for the F-DO10. On a module of order number 6ES7 326-2BF01-0AB0, hardware version 5, firmware V 2.0.9, in rack 0 slot 10, a failed parameter handshake reads:
16#F580:8006Module not assigned parameters - the module started with no valid parameter set16#F580:8007Wrong parameters on module - a record arrived and failed validation16#F580:0101Parameter assignment error (parameter number 16) - the index of the rejected entry inside the record
STEP 7 lists the newest entry first, so the chronological order is 8006, then 8007, then 0101: the module came up unparameterized, received a set, rejected it, and named the offending entry. That sequence rules out wiring and load faults outright - the outputs never closed, so nothing on the 24 V DC field side was ever switched - and it rules out a protection problem, because the F safety password governs edits to the safety program, not a module's parameter assignment.
The F-destination address lives in two places #
The F-destination address is the PROFIsafe address (F_Dest_Add) the F-CPU embeds in every parameter record and safety telegram sent to the module; it must be unique per module on that F-CPU. It exists independently in two spots:
- A 10-pole DIP switch block on the rear of the module, reachable only with the module pulled from the rack.
- The project, under the module properties, tab F Parameters, field DIP switch setting (9...0).
At startup the module compares the destination address in the incoming record with the address on its switches and discards the record on any difference. Older S7 Distributed Safety installations commonly carry the module's old I/O start address on those switches, and that stale value is the mismatch. On this module the project field is read-only, so the hardware must follow the project - never the reverse. The same F-DI in the rack read 40 in the project with its switches set to 40, which is why the E-stop channel at I40.0 worked while the output module, project 10 against switches 80, did not.
Setting the DIP switches for F-destination address 10 #
Worked example: the project shows DIP switch setting (9...0) = 10 for the F-DO10, but the rear switches carry 80, the module's output start address seen in the channel addressing 80.3/81.0.
The rule: the ten switches are labeled 9 down to 0 with binary weights 512, 256, 128, 64, 32, 16, 8, 4, 2, 1, most significant first, and the switch pattern must spell the project value.
The arithmetic for address 10: 10 = 8 + 2, so switches 3 and 1 are on and the rest are off, giving the pattern 0000001010. For comparison, the old value 80 = 64 + 16 sets switches 6 and 4 (0001010000), and the F-DI's address 40 = 32 + 8 sets switches 5 and 3 (0000101000).
The steps:
- Read the target from F Parameters, field DIP switch setting (9...0); here it is 10.
- Convert it to the 10-bit pattern
0000001010. - Switch off the module supply and the load voltage, then pull the module from slot 10.
- Set the ten rear switches to the pattern and confirm no other F-module on the same F-CPU carries that number.
- Reinsert the module, restore both supplies and power-cycle it; the switch position is read only at module startup.
Decision: with the address matched, SAFE lights and both SF LEDs go out. Any F-DO10 that keeps SF red after a matched power-cycle, with no new incoming 16#F580 events, is a hardware fault - replace the module.
Faults that mimic an address mismatch #
Before pulling hardware a second time, eliminate these in order:
- F-monitoring time. Changing it from 250 ms to 2500 ms cannot help here: the monitoring time watches telegram round trip only after the module reaches safety mode, and a module whose SAFE never lights has exchanged no telegrams. Derive it from the loop response-time calculation, not by trial.
- Stale module entry. Inserting the wrong F-module type first and swapping it later can leave the earlier entry in the compiled data on some Distributed Safety versions. Delete the module in HW Config, re-insert the correct order number, recompile and download; if the fault survives, rebuild the station in a fresh project.
- Version alignment. STEP 7, S7 Distributed Safety and the S7 F configuration pack must sit at matching levels; V5.4 across all three is a valid combination, and the service packs for that generation are worth applying before chasing an intermittent parameterization fault.
Cross-check the module's behavior against the Automation System S7-300 Fail-Safe Signal Modules manual for the hardware and firmware version the buffer prints.
Verifying the fix and the output topology you are running #
After the change, download nothing and recompile nothing: the project was already correct. With the CPU in RUN, expect SAFE lit, both SF LEDs dark, and the three 16#F580 entries showing as outgoing events with no new incoming ones. Then test the channel - the coil contactor on Q81.0 driven from the safety program - and watch it follow.
One design note while you are there: the F-DO10 switches twice in the plus, with both switching elements in series in the P line and the load return fixed to M. A cross circuit from that return to a foreign potential is not disconnected by the module, so route the M return protected and never treat it as an M-switching output. The newer F-DO8 switches in plus and minus and removes that exposure, so prefer it for new designs.
Passivation scope is a configuration decision in the project, not a module property: whole-module passivation drops all ten outputs when any channel faults, per-channel passivation drops only the affected channel - choose it from the risk assessment. The related behavior of module-level self-test and group faults is covered in how fail-safe I/O modules detect their own faults, and the front connector side of these modules in the S7-300 front connector coding key on analog I/O modules.
Questions asked
Does the F safety password block the parameter record on an S7-300 F-DO10?
No. The safety password protects edits to the F-program and F-configuration in the engineering software; the module does not use it when it validates the incoming F-parameter record. A wrong or forgotten password produces a download or protection error, never the 16#F580 parameter-assignment sequence in the module diagnostic buffer.
Why did raising the F-monitoring time not clear the SF LED?
The F-monitoring time watches the PROFIsafe telegram round trip only after the module has accepted its parameters and entered safety mode. A module whose SAFE LED never lights has received no valid telegrams at all, so no monitoring-time value, whether 250 ms or 2500 ms, can change the fault. Set the time from the loop's response-time calculation once the address matches.
Can the F-destination address be changed in the software for an F-DO10?
No. On the 6ES7 326-2BF01-0AB0 the DIP switch setting field in the F Parameters tab is read-only: the project always uses the address the module carries on its rear switches, and the hardware must follow the project. Newer fail-safe modules store the address in software, so for those the mismatch can be corrected from the project without touching the module.
Does a rejected F-parameter record mean the module hardware is faulty?
Not by itself. The 16#F580 events state that a record arrived and failed validation, which is exactly what an address mismatch produces. Prove the hardware is sound by confirming a second F-module in the same rack reaches SAFE, by reading a sensible firmware version in the buffer, and by re-reading the buffer after correcting the switches: a matched address with a fresh 16#F580 error then points at a real module fault.