Explainer
Why an S7-1500 analog module lacks the KTY83 110 curve
Short answer
The module 6ES7531-7KF00-0AB0 (AI 8xU/I/RTD/TC ST) linearizes only standardized RTD characteristics, and KTY83/110 is not one of them. Configure the channel as 2-wire resistance in ohms and convert with the sensor data sheet's table plus linear interpolation in the PLC; with 10 K table spacing the interpolation error stays below 0.05 K.
On this page
- Why the sensor list has no KTY83/110 curve
- Configure the channel as a two-wire resistance input
- The sensor's characteristic and its table
- Converting ohms to degrees with interpolation
- Worked example at a cooling temperature
- What two-wire wiring costs in accuracy
- Replacing the thermostat without losing its functions
- Questions asked
Your module measures the sensor perfectly well; it only refuses the last step. The AI 8xU/I/RTD/TC ST (6ES7531-7KF00-0AB0) connects resistance-based sensors in 2-, 3- and 4-wire arrangements, but its temperature modes linearize standardized RTD and thermocouple characteristics only, and KTY83/110 is not on that list. The fix: configure the channel as a two-wire resistance measurement in ohms and convert ohms to degrees in your 1511-1 PN with the sensor data sheet's resistance-temperature table and linear interpolation. Follow the arithmetic below and the conversion error stays negligible against the sensor's own tolerance.
Why the sensor list has no KTY83/110 curve #
A temperature mode on an RTD module is curve matching, not physics. The module measures resistance, then maps it through the stored characteristic of whichever standardized sensor you selected. The KTY83/110 is a silicon PTC with its own law — steeper than any platinum RTD and bending by a different amount — and this module ships no stored curve for it, so no selection in the list produces correct degrees. The mismatch is the same class as wiring a Pt100 straight into a current input, which is why a Pt100 cannot connect to a 4-20 mA analog input module: the input has to know the sensor's law before it can output temperature.
The resistance path is curve-agnostic. It reports ohms whatever the sensor. That is the door you use: let the module do what it is built for, and hand the curve to the PLC.
Configure the channel as a two-wire resistance input #
In the hardware configuration of your project, set the channel to resistance measurement with a two-wire connection — the KTY83/110 is a two-terminal device — and set the channel's unit to ohms, so the module delivers engineering values and your program never touches raw counts. Pick the smallest documented measuring range whose upper limit clears the sensor's resistance at your highest process temperature; for the sensor's full span that is about 2.25 kΩ at 150 °C, so read the range list in the module manual and choose accordingly. Enable the channel diagnostics so an open circuit raises a fault instead of a quiet extreme value.
The module then handles excitation, digitizing and the counts-to-ohms step (the stages are described in how PLC analog input and output modules convert signals). Prove the ohms path before any curve work: with the sensor disconnected, wire a 1 % 990 Ω resistor across the input and confirm the channel reports it within the module's specified accuracy plus your lead resistance.
The sensor's characteristic and its table #
The KTY83/110 is nominal 990 Ω at 25 °C with a temperature coefficient near +0.79 %/K there, about 7.8 Ω/K, rising to roughly 10.2 Ω/K by 90 °C. The sensitivity grows with temperature, which is exactly why one straight-line scaling cannot convert it. The data sheet states the nominal characteristic as a parabola in the difference from 25 °C: R = R25 × (1 + α × ΔT + β × ΔT²), with α = 0.007874 /K and β = 1.874 × 10⁻⁵ /K². The same document tabulates, for the KTY83/110, each ambient temperature with its corresponding resistance, temperature coefficient and maximum expected temperature error — Table 7 of the KTY83 series data sheet. Those tabulated points are what you type into the program; the parabola appears below only to show the arithmetic. The bottom of the nominal span is about 562 Ω at -40 °C.
Converting ohms to degrees with interpolation #
With the unit set to ohms exactly one conversion remains: invert the characteristic. Store the data sheet points as temperature-resistance pairs sorted by resistance, find the pair that brackets each measured value, and interpolate:
T = T1 + (R - R1) × (T2 - T1) / (R2 - R1)
with R the measured resistance and the subscripted values the neighboring table points, in consistent ohms and one temperature scale. Reject anything outside the table rather than extrapolating. Ten-kelvin spacing is enough: the nominal curve's second derivative is roughly 0.037 Ω/K², so midway between points 10 K apart the straight chord departs from the curve by 0.037 × 10² / 8 ≈ 0.46 Ω — about half an ohm, which at the local slope stays under 0.05 K, far beneath the sensor's own tolerance column.
In structured text the conversion is a short bracket search; the names below are this article's own example names, in ohms and degrees Celsius:
VAR_TEMP
rOhm : Array[1..3] of Real; // table: resistance, ascending with temperature
rDeg : Array[1..3] of Real; // table: matching temperature
rMeas : Real; // resistance reported by the channel
rTemp : Real; // interpolated temperature
i : Int; // bracketing index
bValid : Bool; // true while rMeas lies inside the table
END_VAR
rOhm[1] := 1474.9; rOhm[2] := 1575.1; rOhm[3] := 1679.0; // extend with the data sheet points over your span
rDeg[1] := 80.0; rDeg[2] := 90.0; rDeg[3] := 100.0;
rMeas := 1525.0; // example channel value
bValid := (rMeas >= rOhm[1]) AND (rMeas <= rOhm[3]);
IF bValid THEN
i := 1;
WHILE rMeas > rOhm[i + 1] DO
i := i + 1;
END_WHILE;
rTemp := rDeg[i] + (rMeas - rOhm[i]) * (rDeg[i + 1] - rDeg[i]) / (rOhm[i + 1] - rOhm[i]);
END_IF;
// Test: with the values above rTemp equals 85.0; a value equal to a table point returns that point exactly
Out-of-table values leave the valid flag false, and the fault logic in the last section uses that flag.
Worked example at a cooling temperature #
Take table points from the nominal characteristic. At 80 °C the difference from 25 °C is 55 K, so R = 990 Ω × (1 + 0.007874 × 55 + 1.874 × 10⁻⁵ × 55²) = 990 Ω × 1.4898 = 1474.9 Ω. The same arithmetic gives 1575.1 Ω at 90 °C and 1679.0 Ω at 100 °C. Suppose the channel reports 1525.0 Ω: the value lies between the first two points, so T = 80 °C + (1525.0 - 1474.9) × (90 - 80) / (1575.1 - 1474.9) = 80 °C + 50.1 × 10 / 100.2 = 85.0 °C.
Check it against the curve: the nominal characteristic gives 1524.5 Ω at 85 °C, so the chord sits about 0.5 Ω above the curve at the midpoint and the interpolation reads roughly 0.05 K low there — the worst case for this spacing.
What two-wire wiring costs in accuracy #
A two-wire measurement adds the loop's lead resistance to the sensor's own, and because the sensor is a PTC the extra ohms read as extra temperature: near 10.2 Ω/K, each ohm of unwanted loop resistance costs about 0.1 K. Ten meters of 0.5 mm² copper is 20 m of conductor at roughly 0.035 Ω/m — about 0.7 Ω — so the reading runs about 0.07 K high. That is negligible, which makes the direct two-wire connection the right choice for a sensor near the cabinet. A 100 m run adds about 7 Ω, nearly 0.7 K, plus noise exposure: beyond roughly 50 m of cable, or wherever the sensor cable shares a tray with drive wiring, mount a transmitter with a KTY input at the sensor, send 4-20 mA back, and configure the channel for current instead.
Two rules keep the reading honest. Do not leave the old thermostat wired across the same sensor — two excitation circuits load the sensor and corrupt both measurements. And keep the measuring current within the conditions the sensor data sheet permits, so self-heating stays inside the sensor's quoted error.
Replacing the thermostat without losing its functions #
Before decommissioning the old thermostat, record what it actually did: control setpoint, switching differential, output action, and its response to an open sensor. The PLC replacement needs that differential as an explicit hysteresis band — for example, stop cooling 2 K below the temperature that starts it — or measurement noise chatters the cooling output around a single threshold.
Wire break deserves a decided answer, because an open sensor circuit drives the channel to overrange, a naive program reads that as extreme heat, and the cooling runs flat out. For most cooling loops that fail direction is acceptable: alarm plus cooling energized. Where overcooling damages the process, choose alarm plus output off instead. Never let the loop hold its last value silently — map the channel's diagnostic to the response you chose.
One boundary stands regardless: if that thermostat also served as an independent high-limit or protective trip, this channel does not replace it, because a standard analog input is not a safety function. Keep a certified limiter on its own sensor, or implement a separately assessed protective function.
Questions asked
Can I select a different sensor type in the module and correct the reading afterwards?
No. Every entry in the list applies one fixed standardized curve. A Pt1000 reads 1000 Ω at 25 °C, close to the KTY83/110, but at 100 °C a Pt1000 is about 1385 Ω where the KTY83/110 is near 1679 Ω, so the module would report roughly 175 °C for a true 100 °C. No single offset or factor repairs that, because the two curves bend differently. Only the sensor's own table converts it correctly.
Do I scale the channel value from 0 to 27648 like on older analog modules?
Not for this channel. With the unit set to ohms, the module delivers resistance directly, so the program receives ohms instead of raw counts. The 0 to 27648 convention is the raw-count representation a program scales itself, typically for voltage and current channels. Prove the ohms path during commissioning: a known resistor wired across the input should appear on the channel as its rated value within the module's specified accuracy.
Can a single linear scaling block replace the table?
No. One straight line cannot follow the KTY83/110 curve. A line fitted through its 25 °C and 100 °C points turns a true 60 °C, about 1286 Ω, into roughly 57 °C, nearly 3 K low, because the sensor's sensitivity keeps growing with temperature. Linear scaling instructions suit straight quantities such as voltage into percent; this conversion needs the table with interpolation.