SCADA and data logging Published 6 min read

Short answer

Retrying means the collector cannot hold a DCOM connection to the RSLinx OPC server, and the interface coming up the moment the Windows firewall was disabled proves the block is on the PC, not the SLC 5/05. Restore the firewall with scoped rules and DCOM permissions. The empty tag browser is a separate fault: read F8:0 through topic ARM04 with an independent client and configure the item by hand if the read is good.

On this page
  1. Read the two symptoms separately
  2. Open the DCOM path with the firewall on
  3. Prove F8:0 through ARM04 without the browser
  4. Reading F8:0 through ARM04 after the firewall test
  5. Bring the collector back and verify delivery
  6. Questions asked

Retrying on the IS Statistical tab means one thing: the collector cannot hold its DCOM connection to the RSLinx OPC server. Your own test already settled where the fault lives. The interface came up the moment the Windows firewall was disabled, so the block is on the PC, not on the SLC 5/05, the topic or the Ethernet link. Restore the firewall and open the DCOM path properly instead of leaving it off. The empty online tag list is a second, separate fault: OPC DA address browsing and item reads are different server functions, so an empty browser does not stop you reading F8:0 through topic ARM04. Prove that item with an independent client, then configure it by hand. The steps below take the collector from Retrying to verified delivery.

Read the two symptoms separately #

What you see What it means Next check
The server appears during configuration Discovery works; activation and data exchange are unproven Make one real item read
IS Statistical stays at Retrying The collector is not holding its DCOM connection Firewall filtering, then DCOM launch and access
The interface starts with the firewall disabled Filtering on this PC blocked the DCOM traffic Scoped rules and DCOM permissions
The online tag list stays empty Browsing fails; the data path may still be good Read F8:0 through ARM04 directly
A direct read fails too The fault is deeper than browsing Item error, topic destination, data table, permissions

Do not rebuild the PLC project or change Ethernet addressing. The firewall test already localized the problem to the PC, and controller changes belong nowhere in the first repair attempt.

Open the DCOM path with the firewall on #

OPC DA runs on Windows COM and DCOM, where server discovery, server activation, access to server objects and delivery of subscribed data are separate operations. Allowing discovery alone is not enough: the negotiated RPC endpoint traffic has to pass as well.

  • Record which computer's firewall you disabled, whether the collector and RSLinx are on the same PC or two PCs, and which account the collector runs under. A service account and your logged-in account have different permissions; the same identity trap is described for another SCADA package in why Citect OPC DA fails in Runtime Manager service mode.
  • Read the collector's diagnostic log for the connection error behind Retrying, and turn on firewall logging to catch dropped packets during one controlled connection attempt.
  • Restore the firewall and add rules for the DCOM and RPC traffic between the collector host and the RSLinx host, scoped to those hosts and the active network profile. Windows lets you bound DCOM to a defined port range so the rules cover fewer ports, but that reduction does not remove the rule work.
  • In the DCOM configuration, grant the collector's execution account launch, activation and access permissions on the RSLinx OPC server.
  • Do not apply a DCOM configuration utility built for another vendor's OPC server as a drop-in repair. Its security edits only help when they match this server, this computer arrangement and this account.

Prove F8:0 through ARM04 without the browser #

The topic selects the controller connection; the address selects the data. Creating a topic proves neither that the PLC is reachable nor that the element exists, so check each layer once:

  1. Open the DDE/OPC Topic Configuration dialog from the DDE/OPC menu and confirm ARM04 points at the intended SLC 5/05 on the Ethernet driver, not another device visible on the network.
  2. Confirm RSLinx communicates with that controller through the configured driver.
  3. In the controller data table, confirm floating-point file 8 exists and element 0 is populated. The topic does not create PLC data.
  4. In the same dialog, select ARM04, browse for the address string and use the copy-to-clipboard function to take the exact item string. Never guess separators or copy item syntax from another OPC server; a valid PLC address in the wrong string format comes back as an invalid item.
  5. Connect an independent OPC DA client to the same RSLinx server, add the copied item, and record value, quality and timestamp. The client-side groundwork is the same one described for a C# OPC DA client that needs its own RSLinx Classic server.

Reading F8:0 through ARM04 after the firewall test #

This is your case: the collector starts with the firewall disabled, the browser is empty, and you want the SLC 5/05 element F8:0.

Inputs, and where each comes from:

  • Topic ARM04, created in your RSLinx configuration and pointed at the SLC 5/05 over Ethernet (your setup).
  • Item F8:0: floating-point data file 8, element 0, checked present in the controller data table (your PLC program).
  • The controller value: take whatever the data table shows at the moment of the test; for the arithmetic below, say the table reads 23.5 (an illustrative value, not a reading from your machine).
  • The OPC read returned by the independent client: value, quality and timestamp.

The rule, in words: item access and address browsing are separate server functions, so a Good-quality read of the correct value proves the whole chain (topic, driver, Ethernet link, controller, data file, client) and leaves the browser as the only broken piece.

The arithmetic:

23.5 (controller data table) minus 23.5 (OPC read) = 0.0, which sits well inside the precision of the controller's 32-bit floating-point element (about 7 significant decimal digits), with quality reported Good. The values agree; the data path is proven.

The decision: a Good-quality read with the firewall back on ends the network hunt. Configure the item manually in the collector and drop browsing from the repair. A failed read ends the browser hunt instead: an invalid-item result means the string is wrong, so copy it again; a communications-failure result means the path behind the topic is broken.

Bring the collector back and verify delivery #

  1. Re-enable the firewall with the new rules and repeat the test-client read. If it fails with the firewall on, fix that connection before touching any collector variable.
  2. Reconnect the EPM OPC DA interface and confirm IS Statistical leaves Retrying and stays out of it during normal operation.
  3. If the online list is still empty, create the item manually with the proven string and map the returned floating-point value to a real-type collector variable.
  4. Compare the collected value with the controller data table, and read quality and timestamp alongside the number. A cached value with Bad quality still looks like a number on screen.
  5. Watch one real change arrive. Change F8:0 only if it is a spare, non-control element, and only in an approved window; otherwise wait for the process to move it.
  6. Restart the collector in an approved window and confirm it reconnects under its normal service identity. A desktop pass does not clear a service-account fault.
  7. If the test client works and the collector does not, compare server selection, execution identity and item string between them; the working local-server arrangement is laid out in how a MicroLogix 1500 reaches WinCC through a local RSLinx OPC server.

Acceptance is the full chain under the firewall: the collector out of Retrying, a value that matches the data table with Good quality, and an update that arrives when the process changes. Anything less is still a fault, not a quirk.

Questions asked

The interface runs with the firewall off. Can I leave it off?

No. The disabled firewall is a diagnostic result, not the repair. Restore it, add rules scoped to the DCOM and RPC traffic between the collector host and the RSLinx host, and grant the collector's execution account the DCOM launch, activation and access rights it needs on the server. A Windows firewall left off on a control-network PC exposes the engineering station to every scan on that segment.

Do tags have to be declared in RSLinx before an OPC client can read them?

A read needs only a working topic and a valid controller address, so F8:0 under a topic that reaches the SLC 5/05 is readable even when the browse list is empty. Address enumeration is a separate server function that is not exposed the same way for every driver. Get the exact item string from the copy function in the topic configuration dialog and add the item to the client manually instead of relying on browsing.

What does a Bad quality flag on F8:0 tell me?

The item-level result splits the fault in two. An invalid or unknown-item result means the server rejected the string itself, so the topic name, the separator or the address is wrong and you copy the string again from the topic configuration dialog. A communications-failure result means the item was accepted but the read failed, which points back to the path behind the topic: the driver, the Ethernet route to the controller or the data table itself.

The test client reads fine but the collector still shows Retrying. Why?

They run under different identities. Your desktop client uses the account you logged in with, while the collector usually runs as a service under its own account, and DCOM launch, activation and access permissions are set per identity and per server. Give the collector's service account the same DCOM rights on the RSLinx server that your test account has, then confirm both the client and the collector point at the same server instance and the same topic name.

Keep reading

  • Explainer

    Why a C# OPC DA client needs its own RSLinx Classic server

    The OPC DA endpoint your C# client needs comes from a licensed RSLinx Classic installation with a configured communication driver and a named DDE/OPC topic — the plant's built-in HMI link provides neither. Install Classic on the computer that runs your client, configure the driver and topic, prove the topic with a generic OPC DA test client, then connect. If you only need tag values, libplctag reads EtherNet/IP tags from C# without RSLinx.

    SCADA and data logging

  • Explainer

    How a MicroLogix 1500 reaches WinCC through a local RSLinx OPC server

    The MicroLogix 1500 is never an OPC endpoint. WinCC reads it only through three links: the NET-ENI Ethernet path, a locally installed RSLinx Classic OPC DA server with a configured driver and topic, and the WinCC OPC channel. The deciding check is a good-quality read of one known PLC item with a local OPC test client before any WinCC tag is built.

    SCADA and data logging

  • Troubleshooting

    Why Citect OPC DA fails in Runtime Manager service mode

    Run the Runtime Manager service and the Schneider Electric SCADA OPC DA Server DCOM identity under one specific Windows account. CO_E_SERVER_EXEC_FAILURE for SchneiderElectric.SCADA.OpcDaServer.1 is a COM activation failure caused by the SYSTEM-versus-interactive identity mismatch, not a tag or DCOM-permissions problem, and adding SYSTEM to DCOM security does not fix it.

    SCADA and data logging