Why an M221 simulation fails with TCP error 10013 on port 51234

PLC programming Published 6 min read

Short answer

Error 10013 is Winsock WSAEACCES: Windows refused the simulation runtime's bind to TCP port 51234 before any Modbus traffic ran. Find a listener with netstat -ano; if none exists, test the port against the Windows excluded-port ranges with netsh. Fix the ownership or exclusion on the Windows side, not in the PLC project.

On this page
  1. What error 10013 means at bind time
  2. Find the process that owns port 51234
  3. Check the Windows excluded-port ranges
  4. Rule out a security-policy denial
  5. Match the fix to the finding
  6. Confirm the channel and test the Modbus link
  7. Questions asked

Windows socket error 10013 is a permission denial, not a Modbus or program fault: when an M221 simulation in EcoStruxure Machine Expert launches, Windows refuses to let the runtime bind TCP port 51234, and the channel fails before any communication begins. The message reads TCPServer: Unable to create a channel (Port: 51234) – Error: 10013. Check if this port is already used by another server. Two causes cover nearly every case: a process already owns the port, or the port sits inside a Windows excluded range that ordinary processes may not bind. Work them in that order — netstat first, exclusions second — and leave the PLC project and the Modbus mapping alone; nothing in them produced this error.

What error 10013 means at bind time #

Error 10013 is the Winsock code WSAEACCES: "An attempt was made to access a socket in a way forbidden by its access permissions." The runtime hits it while creating its listening socket, before the first Modbus request is ever formed. Microsoft documents that a bind attempt on a port inside a Windows excluded range returns exactly this code, which is why the software's own hint — check whether the port is used by another server — is the right first move but an incomplete diagnosis: a port can be forbidden with no listener on it at all.

The causes that can produce WSAEACCES here:

  • Another process holds the port with exclusive ownership.
  • The port lies inside a Windows excluded-port range reserved for components such as Hyper-V and virtual networking.
  • An endpoint-security policy denies the executable the right to open listening sockets.

One classic cause cannot apply: the privilege rule that reserves ports below 1024 for elevated processes, well under 51234.

One boundary matters before you change anything: this channel is not the Modbus service. The Machine Expert Basic simulator's Modbus server is documented at TCP port 502, the port registered for Modbus TCP, so the 51234 channel belongs to the simulation runtime itself. Re-pointing your Modbus client at another port cannot fix a bind failure on a socket the client never touches. The same split between ownership and permission appears wherever a runtime cannot bind — Unix socket bind denials on a Linux-based controller are diagnosed with the same two questions: who owns the socket, and what policy governs it.

Find the process that owns port 51234 #

Ownership is directly observable, so start there:

  1. Open a command prompt and run netstat -ano | findstr 51234.
  2. Read the local-address column. A line carrying LISTENING with a local address such as 0.0.0.0:51234 or 192.168.1.10:51234 is your owner; note the process identifier in the last column.
  3. Match that PID to an executable in Task Manager's Details tab.
  4. If it is a second copy of the same engineering software — a simulation left over from a session that never closed cleanly — close it through its own interface, re-run the command, and confirm the listener is gone.
  5. If it is a different application with a legitimate need for 51234, the conflict is named, and that application's documented port setting is the one to change.

A listener bound to 0.0.0.0 owns the port on every interface, so it collides with a later bind to any single local address as well. Do not end an unfamiliar process just to free the port: a Windows service doing real work can hold it, so identify it first and coordinate with whoever depends on it.

If no line shows LISTENING on 51234, stop hunting for an owner. The cause is an operating-system restriction.

Check the Windows excluded-port ranges #

Windows reserves blocks of the TCP dynamic range for operating-system components and denies them to applications, and those reservations never appear as listeners in netstat. Display them with:

netsh int ipv4 show excludedportrange protocol=tcp

Each row of the output is a start port and an end port. Testing your port against one row takes two subtractions, and both results must be non-negative for the port to fall inside.

Worked example: is 51234 inside the block #

Illustrative output, the shape you see on a machine where three blocks are reserved:

Start Port    End Port
----------    --------
      49671      49770
      51154      51253
      58234      58333

Row one: 49770 − 51234 = −1464, negative, so 51234 is above that block's end — outside. Row three: 58234 − 51234 = 7000, so 51234 is below that block's start — outside. Row two: 51234 − 51154 = 80 and 51253 − 51234 = 19; both non-negative, so 51234 sits inside the block, 19 ports short of its top edge. Windows returns WSAEACCES for any ordinary bind inside that row, which is the error on screen, with no listener anywhere.

The decision follows: an administrator either removes the component holding the reservation (Hyper-V or virtual networking the machine does not need) or restarts Windows, which re-runs the reservation logic and typically moves the blocks. Then verify before restarting the simulation — re-run the netsh command and confirm 51234 falls outside every row. Deleting exclusion rows by hand is not a fix; the components that created them re-create them, and some belong to services you want alive.

Rule out a security-policy denial #

When netstat shows no owner and no exclusion row covers the port, the remaining documented cause is policy:

  • Endpoint-security software with application control can deny an executable the right to open listening sockets. Its own event log, read at the timestamp of the failed launch, names the runtime's executable if it made the denial. The fix is a policy exception from the security product's owner, never disabling the product.
  • One elevated launch is a fair one-minute test: if the bind succeeds elevated and fails normally, a permission rule is following that executable, and the correction belongs in the rule.
  • A firewall rule is not in play — it admits or blocks traffic reaching an existing socket and does not stop the socket from being created.

Match the fix to the finding #

What you observed Cause The fix
LISTENING on 51234; the PID is the same engineering software Duplicate simulation instance Close it, confirm the listener disappears, restart once
LISTENING on 51234; the PID is another application Port conflict between applications Change that application's documented port setting; the simulator's channel has no project setting
No listener; an exclusion row covers 51234 Windows reserved the port Remove the reserving component or restart Windows, verify the ranges, restart the simulation
No listener, no exclusion; the security log names the executable Application-control policy Security owner grants the exception
Binds when elevated, fails when normal Permission rule on the executable Correct the rule; do not run elevated permanently

Restart the simulation once, after the single correction you chose, and check two things: the 10013 message does not reappear, and netstat -ano now shows the runtime listening on 51234. In every branch the decision has the same shape — free the port or clear the policy on the Windows side, change nothing in the project, and prove the fix by seeing the listener appear.

With the channel alive, the communication stack below it becomes testable for the first time. A good next step is to simulate a Modbus TCP SCADA link on one PC and prove the whole path before hardware enters the picture. When the supervisory side joins later, its reads carry failure modes of their own; Machine SCADA Expert Modbus TCP reads to a TM221 covers the addressing traps on this controller family.

Questions asked

Is TCP error 10013 a fault in my Modbus configuration?

No. The failure happens while the simulator is creating its listening socket, before the first Modbus request is ever formed. Winsock error 10013 means Windows denied the bind on port 51234 for a permission reason: an owned port, an excluded range, or a security policy. Your register mapping, slave ID and Modbus client settings are untouched by this error, and changing them will not clear it.

Why can port 51234 be blocked when netstat shows nothing listening on it?

Hyper-V and the Windows components behind virtual networking reserve blocks of the dynamic port range at boot, and those excluded ranges never appear as listening sockets. A port that worked yesterday can fail after a reboot moved the reservation, because the blocks are recomputed when Windows starts. That is why netstat stays empty while the bind still fails.

Will running the software as administrator clear error 10013?

Only ports below 1024 require an elevated process, and 51234 sits far above that line, so an elevated start is not the fix. It is still a useful one-minute test: if the bind succeeds elevated and fails normally, a security or permission rule is following that specific executable, and the answer is a policy correction, not a permanent habit of running the engineering tool as administrator.

Can I point the simulator at a different port instead?

Changing the Modbus client's port addresses the wrong socket. The simulator's Modbus service is documented at TCP port 502, while the failing channel on 51234 belongs to the simulation runtime itself, and no project setting for that channel is documented. The supported fix is to free 51234 on the Windows side, by closing its owner or clearing the exclusion that covers it.

Keep reading

  • Troubleshooting

    Why Modbus cannot transfer a PLC ladder program over TCP

    No Modbus address reaches ladder memory: the application protocol defines four data tables — coils, discrete inputs, input registers, holding registers — and program storage is not in any of them. Swapping RTU for TCP changes transport, not protocol. On DirectLogic PLCs the program moves only over K-Sequence or DirectNET through the vendor's programming tools; Modbus stays for mapped user data.

    PLC programming

  • How-to

    How to run two TwinCAT PLC programs on one laptop

    Merge both PLC projects into one TwinCAT XAE system configuration and activate it once. The XAE assigns each PLC project its own ADS port (851 to the first, 852 to the next by default numbering), and both programs reach RUN on the local runtime. Changing the port in one of two separate XAE projects does not work, because one activation replaces the other.

    PLC programming

  • Troubleshooting

    Reading Modbus TCP from a ControlLogix PLC without a gateway

    Yes — ControlLogix reads Modbus TCP without a gateway card through Rockwell's sample Modbus TCP driver, but only on controller firmware version 20 or later with socket-capable Ethernet hardware such as a 1756-EN2xx module at firmware 5.007 or later. If either side misses the gate, use a standalone EtherNet/IP to Modbus TCP converter. When the driver runs, prove one request against a known-good PC client and match unit ID, start address and count field by field.

    Industrial networks