Why an iQ-R built-in Ethernet port is not an EtherNet/IP scanner

Industrial networks Published 8 min read By IMDHMI controls team

Short answer

No: the R04CPU's built-in Ethernet port runs MELSEC communication and general TCP/UDP traffic such as Modbus TCP, and EtherNet/IP is not among the networks the CPU documents. Devices that need CIP implicit I/O or explicit messaging — Keyence vision, an Omron safety PLC, many robots — stay silent until you fit the RJ71EIP91 EtherNet/IP module, match assembly instances and sizes from each EDS file, and keep every safety function on hardwired safety I/O.

On this page
  1. Does the iQ-R built-in Ethernet port support EtherNet/IP?
  2. How do you tell whether a device needs EtherNet/IP or plain Ethernet?
  3. Can the Keyence vision and Omron safety PLC connect through the CPU port?
  4. Which module adds EtherNet/IP to an iQ-R rack?
  5. How do you budget connections and RPI before ordering the module?
  6. How do you bring up the RJ71EIP91 connection to an EtherNet/IP adapter?
  7. Why does a device ping but exchange no EtherNet/IP data?
  8. Can safety data cross the link between the R04CPU and the Omron safety PLC?
  9. Questions asked

Fit the RJ71EIP91 EtherNet/IP module: the R04CPU's built-in Ethernet port cannot scan EtherNet/IP devices. The port serves MELSEC communication, engineering-tool traffic and general TCP/UDP protocols such as Modbus TCP, but it does not run CIP — the protocol behind EtherNet/IP's implicit I/O on UDP 2222 and explicit messaging on TCP 44818. Keyence vision units, an Omron safety PLC and many robot controllers present themselves as EtherNet/IP adapters, so they stay silent regardless of IP settings until a scanner exists. Work the checks below in order; the first usually ends the diagnosis.

Does the iQ-R built-in Ethernet port support EtherNet/IP? #

No: Mitsubishi documents Ethernet, CC-Link IE Control and CC-Link IE Field as the networks an iQ-R CPU supports, so the CPU itself brings no EtherNet/IP scanner; the CIP services behind EtherNet/IP arrive only with the RJ71EIP91 network interface module.

EtherNet/IP is CIP stacked on Ethernet, not a property of the connector: explicit messages use TCP 44818 and implicit cyclic I/O uses UDP 2222, and neither service exists on the CPU port. What the port does instead is the engineering-software link for programming and monitoring, HMI and SCADA reads over MELSEC communication, and ordinary TCP/UDP work such as a Modbus TCP server. The RJ45 jack proves the transport; it never proves CIP. That gap is the entire fault — a device waiting for implicit packets on UDP 2222 is waiting on a port that will never send them.

How do you tell whether a device needs EtherNet/IP or plain Ethernet? #

Read the PLC-communication section of each device's manual and look for the protocol name: EtherNet/IP, adapter mode, assemblies or an EDS file mean the RJ71EIP91, while MC protocol, SLMP, Modbus TCP or raw sockets belong on the built-in port.

Ethernet names the transport — the frames on the cable — while EtherNet/IP is CIP carried over it in two halves that do not stand in for each other, which is why why explicit and implicit EtherNet/IP messaging do not interwork even on the same switch. The name in the device's manual decides the branch:

  • The manual names EtherNet/IP, adapter mode, assemblies or ships an EDS file: the device wants a scanner, and only the RJ71EIP91 provides one on this rack.
  • The manual names MC protocol, SLMP or MELSEC Ethernet: MELSEC communication on the built-in port, no extra module.
  • The manual names Modbus TCP: served by the CPU on the built-in port — the R04CPU Modbus TCP/IP server configuration guide walks through that setup.
  • The manual names a vendor socket protocol: commit a device to the built-in port only where the CPU's Ethernet specification lists socket communication, and count the traffic it adds.

A green ping never enters this decision: ping answers at the IP layer and is fully compatible with a dead protocol match.

Can the Keyence vision and Omron safety PLC connect through the CPU port? #

Not through the CPU port: Keyence documents EtherNet/IP adapter settings and an EDS import for its vision link, and the Omron safety PLC exposes its non-safety data as CIP assemblies — both expect an EtherNet/IP scanner, which the R04CPU port does not contain.

Decide device by device, from each manual rather than from the connector:

  • Keyence vision: configure the unit as an EtherNet/IP adapter against the RJ71EIP91, with the EDS file and the assembly instances and sizes its connection guide lists.
  • Omron safety PLC: the standard, non-safety data presents as adapter assemblies and connects the same way; writes into those assemblies fail when the instance or size disagrees — the mechanism behind why explicit writes to Omron assemblies fail over EtherNet/IP.
  • Robot controllers: no guessing. If its PLC-facing interface lists EtherNet/IP, it joins the RJ71EIP91; if it lists MELSEC Ethernet or a socket interface, it takes the built-in-port branch; another fieldbus means that network's own module.

Which module adds EtherNet/IP to an iQ-R rack? #

The RJ71EIP91 EtherNet/IP network interface module is the part: it mounts in the iQ-R base unit and runs the scanner side of both CIP traffic types, Class 1 implicit connections and Class 3 explicit messages, with the connection count published in its startup manual.

Class 1 is the cyclic exchange: the module and the adapter push fixed input and output blocks at the RPI set per connection. Class 3 is the on-demand path your program uses for reads and writes when it needs them. The startup manual publishes one connection total covering Class 1 and Class 3 together — budget every device against it, because a camera, a safety PLC and a robot rarely stop at one connection each. The module carries its own IPv4 address alongside the CPU's, and what the connections deliver is mapped into the CPU as ordinary device data your program reads and writes — the same assembly mechanism by which an EtherNet/IP IO-Link master exposes its port data to your PLC.

How do you budget connections and RPI before ordering the module? #

Count each device's connections against the module's documented Class 1 plus Class 3 total, then size the cyclic load from the RPI: at a 20 ms RPI one connection exchanges 50 packets per second, so three Class 1 connections together exchange 150 packets per second.

Worked example, with illustrative device data sizes — not documented or measured values: the camera offers one Class 1 connection of 32 bytes of result data in and 4 bytes of trigger data out; the safety PLC offers one Class 1 connection of 20 bytes each way; the robot offers one Class 1 connection of 48 bytes each way plus one Class 3 connection for parameter reads. Connections: 1 + 1 + 2 = 4, so three Class 1 and one Class 3. Packet rate at a 20 ms RPI: 1 / 0.020 s = 50 packets per second per connection. Cyclic input payload: 32 + 20 + 48 = 100 bytes per cycle across the three cyclic connections, so 100 bytes × 50 packets/s = 5000 bytes/s, about 5 kB/s; output runs 4 + 20 + 48 = 72 bytes × 50 packets/s = 3600 bytes/s. Both figures are trivial for a switched Ethernet link. The binding constraint is the four-connection total against the manual's combined limit, not bandwidth — and every RPI you halve doubles that connection's packet rate, so tighten only where a device proves it must.

How do you bring up the RJ71EIP91 connection to an EtherNet/IP adapter? #

Give the module its own fixed IPv4 address in the same subnet as the adapters, import each device's EDS file, and create its connection with the assembly instances and data sizes copied from the device manual — a size or instance mismatch is the usual cause of a refused connection.

Bring one device up at a time:

  1. Fit the module in the base unit with power off, power up, and confirm its status LEDs match the normal state in the startup manual.
  2. Assign the module a fixed address, for example 192.168.1.50, in the same subnet as the devices; log every address so none collides.
  3. Download each device's EDS file from its manufacturer and import it into the engineering software's EtherNet/IP configuration.
  4. Add one connection per device; copy the assembly instance numbers and input/output sizes from that device's own manual, not from another project.
  5. Set the RPI per connection; begin at 50 ms and tighten to what the process needs once the link is proven.
  6. Map each connection's input and output data to labels in the CPU program, download, and set the CPU to RUN.
  7. Prove it before trusting it: write a known value from the program and read it in the device's own diagnostics, reverse the direction with a value the device generates, then pull the cable and confirm the connection-fault indication appears and your program reacts with a defined state.

Why does a device ping but exchange no EtherNet/IP data? #

A ping reply proves only that IP and cabling work: a refused CIP connection — an assembly instance the adapter does not offer, a size that disagrees with the EDS, an RPI the adapter rejects — leaves ping green and data dead.

Sort the symptom before touching parameters:

  • Ping fails: the fault is the address, subnet mask, cabling or switch. No protocol setting repairs a broken ping.
  • Ping passes, connection never reaches established: the EDS was never imported, or your instances and sizes disagree with what the adapter offers.
  • Connection establishes but data freezes: check the RPI the adapter actually accepted and whether the adapter reports cycling; a paused adapter holds its last data.
  • Explicit reads succeed while implicit data stays stale: the two paths are independent, so a working explicit read proves reachability, not a healthy Class 1 connection.

Read the error detail in the module's connection status before editing anything — it names the parameter that disagreed — then re-download the connection and watch it reach established.

No: nothing that performs a safety function — an E-stop state, a guard-door signal, a safe-stop request — may ride this Ethernet link; hardwire every safety function between the two controllers through safety-rated I/O, and carry only status, diagnostics and mode data over EtherNet/IP.

A standard Class 1 connection carries plain process data: no safety framing and no cross-checking a risk assessment can credit. Safety profiles exist on EtherNet/IP networks, but they bind two endpoints that both document the profile over that exact link, so between these two controllers the working architecture is hardwired safety-rated I/O, with the Ethernet link reporting what happened — safety PLC healthy, zone muted, fault codes for the log. If two CPUs exist only to separate standard and safety programs, the split still holds: map status data across the link and keep every safety function on its own wired channel.

Questions asked

Does the EDS file configure the device itself?

No. An EDS file only describes the device to the scanner's configuration tool: which assembly instances it offers and how large the input and output blocks are. The device's own IP address and operating mode are set on the device itself or in its vendor tool, and the connection is configured in the PLC engineering software from that description.

Do the built-in port and the RJ71EIP91 need separate IP addresses?

Yes. The module is its own node on the network with its own IPv4 settings, and the CPU's built-in port keeps its own address. Put both in the same subnet as the Keyence, Omron and robot devices, reserve the addresses in your IP plan, and confirm no duplicate before powering up.

Can SCADA keep using the built-in port after the module is added?

Yes. SCADA reads the CPU over MELSEC Ethernet on the built-in port, and that traffic is untouched by the RJ71EIP91's CIP connections. Keep the two roles on their two addresses. If you want cyclic EtherNet/IP values in SCADA, map them to CPU labels in the program first and let SCADA read the labels.

Where do I get the EDS file for a Keyence or Omron device?

From the device manufacturer's own download site, matched to the exact model and revision: Keyence publishes EDS files with its connection guides and Omron publishes them per product. Never reuse a file or assembly numbers from a different model, because the instances and sizes belong to that one device.

Do the Keyence camera and the Omron safety PLC talk to each other directly?

No. Both devices are adapters on this link, and each holds its own connection to the RJ71EIP91 scanner. Data the camera produces and the safety PLC needs passes through the CPU program: you map the camera's input data to labels, and the program writes it into the connection to the other device.

Keep reading

  • Troubleshooting

    Why a drive answers ping but the PLC cannot connect

    A drive that answers ping is telling you the IP path works, not that the protocol session does. ICMP echo and the PLC's EtherNet/IP or Modbus TCP connection are separate services with separate settings. Check the responder's identity and subnet, the imported device entry, protocol enable and ports, then cyclic data lengths, and fix the first one that fails.

    Industrial networks

  • Troubleshooting

    Why a Schneider M251 does not appear in RSLinx

    RSLinx and FactoryTalk Linx browse one transaction: the EtherNet/IP List Identity request, and a device appears only when the port you are cabled to answers it. Ping and Schneider software prove IP reachability, nothing more. Enable the M251's EtherNet/IP service on the connected port, browse through the right PC adapter, and register the M251 EDS when the entry shows a red X with a yellow question mark.

    Industrial networks

  • Troubleshooting

    Why explicit and implicit EtherNet/IP messaging do not interwork

    Explicit messaging is request/response CIP over TCP between a client and a server; implicit messaging is a scheduled I/O connection between a scanner and an adapter. The four roles are implemented and configured independently, so one endpoint can lack exactly the mode the other needs, and a reachable IP address proves nothing. Match each endpoint's documented roles, assemblies and byte lengths before you blame the network.

    Industrial networks