Troubleshooting
Why a Wonderware DASServer connection cannot read LOGO 8 outputs
Short answer
Test the read path in order: Ethernet reachability from the DASServer host, then protocol compatibility between the Siemens DASServer configuration and the LOGO 8 server connection, then item addressing. A LOGO 8 output is read through its variable-memory address, not the Q1 terminal label, and neither Q1 nor Q0.0 fixes a failed connection.
On this page
- Does the Ethernet path reach the LOGO 8 from the DASServer host?
- Does the Siemens DASServer actually speak a protocol the LOGO 8 accepts?
- Where does the read request stop in the live connection?
- Which memory address represents the LOGO 8 output you want?
- Does the item work in DASServer before the SCADA application reads it?
- What is the fix, case by case?
- Questions asked
A LOGO 8 output will not read through a Siemens DASServer connection as Q1 or Q0.0, and no item syntax repairs a broken link or an unsupported protocol. Test the path in order — Ethernet reachability from the DASServer host, protocol compatibility with the LOGO 8 server connection, then the variable-memory address written in the driver's own syntax. The two S7-200 connections that already work validate only themselves, not the LOGO.
Does the Ethernet path reach the LOGO 8 from the DASServer host? #
Check link lights and network settings first, because a dead link makes every driver change pointless. Inspect the link indication on the LOGO Ethernet interface and on the switch port it feeds, confirm both the LOGO and the computer actually running DASServer sit on the same subnet or have a working route between them, and use a CAT 5 or better cable for the initial connection.
The machine that matters is the DASServer host, which is not always the computer showing the SCADA application. If the LOGO address responds from your desk but the reads still fail, the fault may be a router or firewall between that host and the controller. A reply also proves reachability only — it is a network check, not a successful industrial-protocol session.
- Link present at both ends: move on to the network configuration of the DASServer host.
- Link absent: fix the cable, interface or switch port before touching driver settings.
- Reply present but reads fail: inspect the protocol stage, not the wiring.
Does the Siemens DASServer actually speak a protocol the LOGO 8 accepts? #
"DASServer for Siemens" names a driver category, not a guarantee that every Siemens controller accepts the same connection. A LOGO! 8 (OBA8) exposes Ethernet communication through the S7 protocol, and it also supports Modbus TCP/IP as an additional protocol, acting as client or server in it. Read the driver's device list and the LOGO's Ethernet connection side by side before you test a single item.
A server connection in LOGO!Soft Comfort set to accept all connections makes the LOGO available to external clients — it does not translate an incompatible request or create an item mapping for a driver that expects a different controller type. If the installed driver does not document compatibility with the LOGO connection in use, select a driver or interface that does, such as a Modbus TCP path, before changing anything else. The same principle applies across brands: a DF1 driver cannot reach an SLC 5/04 through a DH+ gateway no matter how the items are written, and the fix is a supported communication path, not new addressing.
Where does the read request stop in the live connection? #
Watch the DASServer diagnostics while you issue one read against the LOGO, because the failing stage names the failing layer. A device that never connects points upstream to the destination address, protocol selection, connection definition or filtering; a connected device that rejects one item points to memory addressing, item syntax or data type.
If the diagnostics are inconclusive, capture traffic on the DASServer host during a controlled read. Compare where the request goes and which service port the driver uses with what the LOGO server connection expects; take the port from the selected driver's documentation rather than copying a value from another installation. Increasing a timeout never repairs a rejected handshake or an invalid address — record the diagnostic text and the stage where it appears so the next test targets the same failure.
Which memory address represents the LOGO 8 output you want? #
Open the variable-memory overview in LOGO!Soft Comfort and find the output there, because the terminal label and the externally readable address are separate naming systems. LOGO!Soft Comfort links the block parameters you specify in the Variable Memory Configuration dialog into variable memory, so an output must be mapped there before any driver can see it — the overview shows the addresses of inputs and outputs once mapped.
Then translate that address into the driver's documented item syntax: memory area, offset and bit, in the form the Siemens DASServer expects for that memory location, with a data type compatible with the exposed signal. Q1 names a physical terminal and Q0.0 borrows S7-200 bit notation; neither is a LOGO VM address, and deriving a LOGO mapping from the S7-200 configuration is the mistake that produced both attempts. If the signal is not exposed through the selected interface at all, map it in the LOGO program first or read a documented value instead.
For example: you map the output that drives Q1 to VM address V0.0 in the Variable Memory Configuration dialog. The overview shows it at offset 0, bit 0. In the driver you create an item for that memory location in the Siemens DASServer's own address format for a bit at that offset, set the data type to Boolean, and read it. The item now returns the live state of Q1; Q1 as the item name returns nothing, because the driver has no mapping for a terminal label.
Does the item work in DASServer before the SCADA application reads it? #
Test the mapped item through the server's own diagnostic or client-testing interface first, and read value, quality and update information together. A displayed value without valid quality can be a retained value rather than a current PLC reading, and a quality flag that never goes good means the connection stage still fails below the item.
When the direct read succeeds with good quality, reconnect the attribute in the SCADA application and confirm the application displays the same value while you force the LOGO output from its program. If the direct read fails, work back through the stages above; do not relaunch the application and expect a different result, because the failure lives between the server and the controller, not between the application and the server.
What is the fix, case by case? #
Commit to the stage the diagnostics name, in this order:
- No Ethernet link or no route from the DASServer host: repair the physical or routed path first, then retest. Do not edit items.
- Link good, device never connects: the driver or connection definition is incompatible with the LOGO 8 server connection. Select a documented path — the S7 protocol the OBA8 exposes, or configure the LOGO as a Modbus TCP server if the driver speaks that.
- Device connects, item rejected: map the output in the LOGO program's Variable Memory Configuration, read its address from the variable-memory overview, and write the item in the driver's syntax for that memory location, not as
Q1orQ0.0. - Item reads with good quality in the server test: the connection is done; reconnect the SCADA attribute and leave the configuration alone.
One safety note: a SCADA read path is monitoring only. Anything that later writes to the LOGO must be checked against the machine's safety requirements, and hardwired stops stay outside any network path you touch here.
If the same installation later grows an engineering or logging station that stays at the machine, that computer runs beside the controller as an industrial mini PC in the cabinet, and the connection stages above apply to it unchanged.
Questions asked
Can a LOGO 8 expose outputs over Modbus TCP instead of the S7 protocol?
Yes. LOGO! 8 supports Modbus TCP/IP as an additional protocol and can act as either client or server in it. If the SCADA driver speaks Modbus TCP but has no documented path to the LOGO S7 server connection, configure the LOGO as a Modbus TCP server and address the mapped memory registers in the driver's Modbus syntax instead.
How many values can be exposed through LOGO VM mapping?
LOGO!Soft Comfort lets you map up to 64 parameters into variable memory per LOGO!, configured offline in the Variable Memory Configuration dialog. For a panel that reads a handful of outputs and statuses, 64 mapped values is normally enough; anything beyond that belongs in a larger controller.
Why do the two S7-200 connections work while the LOGO 8 fails on the same driver?
Each working connection validates only its own controller type, addressing and network path. An S7-200 connection proves the driver is installed and licensed, not that it accepts the LOGO 8 server connection or its variable-memory layout. The LOGO needs its own documented compatible configuration and its own item addresses.
Does an echo reply to the LOGO prove the read should work?
No. An echo reply proves basic IP reachability only. A missing reply can equally come from filtering. Confirm the actual protocol exchange in the driver diagnostics or a traffic capture on the DASServer host before concluding the network is clean.