Troubleshooting
Why a VTScada Rockwell Driver tag stays nonzero on a MicroLogix 1400
Short answer
Read the port tag and the driver tag as two layers: a port value of 0 means the TCP transport to 44818 is established, while a nonzero Rockwell Driver value means the PCCC over CIP (Data File Addressing) transaction failed. In the reported case the SCADA host firewall had no rule for the PLC's address; allow that traffic, keep the driver on its port tag, and use an empty Port Segment Path for a direct connection.

On this page
A VTScada Rockwell Driver tag that will not settle at 0 is reporting a failed protocol transaction, not a bad cable. Read the two communication tags as separate layers: the TCP/IP Port tag reports the transport to the controller, and the Rockwell Driver tag reports the PCCC over CIP (Data File Addressing) transaction itself. In the installation behind this question the port tag read 0 while the driver stayed nonzero, and the root cause was the SCADA host firewall, which had no rule for the MicroLogix 1400's address. The repair, in order: a scoped firewall rule for the EtherNet/IP port, a driver correctly associated with its port tag, and an empty Port Segment Path for a direct connection — all before the PLC program is touched.
Two tags, two layers #
- The TCP/IP Port tag is the transport layer. Its TCP/IP Name/Address field carries the controller's address and its TCP/IP Port Number carries 44818, the IANA-registered EtherNet/IP port.
- The Rockwell Driver tag is the protocol layer. Its PCCC over CIP (Data File Addressing) option matches the data-table model of this controller family — the same data-file route covered in how a SCADA client reads a small PLC over EtherNet/IP.
- Zero is the healthy indication on both tags. A nonzero driver value is an error code; look up the code actually displayed, never a number remembered from last week.
- The reported readings — 0 on the port, possibly -10230 on the driver — were recalled from memory, so record what the tag browser shows now before you change anything.
What the combination tells you:
- Both tags nonzero: the transport itself is failing. Check the controller address, the selected interface, the host route, then the firewall.
- Port at 0, driver nonzero: the session exists but the transaction does not complete. The suspects are the protocol selection, the driver-to-port association, the Port Segment Path, or a firewall that passes one layer and filters the application's traffic. A brand-new server fails exactly this way, which is why a MicroLogix 1400 connection fails from a new SCADA server until its policy and route match the working host's.
- Older tags communicate, new driver tags fail: compare the configurations field by field — endpoint, protocol, parent port, path — instead of replacing hardware.
- Driver at 0 with one bad data tag: that is addressing, not communications, because a PCCC N-file address is not a CIP class instance path; check the tag against a location the PLC program actually uses.
The firewall was the blocker #
A direct cable removes switches and routers from the path; it does not remove host policy. The rules on the server's interface still apply to the SCADA application, byte for byte.
The report's own evidence settles the diagnosis: a VTScadaLight development installation reached the same controller over EtherNet/IP while the office desktop could not. Same controller, same defaults, different host — so the fault lives in the failing host's configuration, and changing driver options on both machines to chase it is wasted work.
- Have the host's administrator add one rule permitting the SCADA application's traffic to the controller's address on TCP 44818, scoped to that application, that remote address, and the profile active on that interface.
- Keep the firewall enabled. Turning it off hides the policy gap and drops the boundary the server needs in production.
- A successful ping proves only that ICMP gets through; it does not show the application can open its session or finish a read, so never accept it as the test.
- The same signature — a reachable device and one application that cannot finish its transaction — appears when a host firewall blocks a SCADA application's HTTP connection, and the cure is identical: a scoped rule, then a log entry or a good read to prove it.
Set the driver for a direct connection #
Once policy allows the session, configure in this order and change one field at a time:
- Confirm the Rockwell Driver tag references the TCP/IP Port tag you built. A driver with no parent port, or the wrong one, errors while the port tag sits at 0 in the tag browser.
- Keep PCCC over CIP (Data File Addressing); it is the option that matches this controller's data tables.
- Set the Port Segment Path to []. The default [1,0] is a CIP route: out port 1, a chassis backplane, to node 0 — a path for a rack-based controller reached through its communications module. A MicroLogix 1400 terminates the session on its own Ethernet port, so the request should carry no route at all; left at [1,0], the controller receives a path it cannot follow, and the transaction fails with the port tag still reading 0.
- Record the driver value after every single change and restore anything that does not improve it.
Worked example: prove where the block is #
Take these example inputs: controller address 192.168.1.50 with subnet mask 255.255.255.0, and the server's direct NIC at 192.168.1.100 with the same mask.
- 192.168.1.50 AND 255.255.255.0 = 192.168.1.0
- 192.168.1.100 AND 255.255.255.0 = 192.168.1.0
- Same network, so the server sends frames straight out that NIC: no gateway and no router sit between the application and the controller.
The decision from those numbers: the only policy in the path is the server's own firewall on that interface's profile, so one scoped rule there is sufficient and nothing downstream needs opening. Test it from the server: ping 192.168.1.50, and if that answers, open a TCP session to 192.168.1.50 on port 44818. A ping that answers while that session stalls is exactly the reported failure — ICMP passes, the application's traffic is filtered. Read the firewall's blocked-traffic log for the SCADA application, add the rule, retry, and the driver value should fall to 0. If the ping fails too, stop: that is addressing or interface configuration, not this fault, and a firewall rule will not fix it.
Prove it with data, not a zero #
- Create one read-only tag at a location the PLC program actually uses — for example N7:0, if integer data file 7 exists in your program — using the data-file addressing syntax the Rockwell Driver Help page specifies.
- Compare that tag with the same data-table location in the PLC programming software, then watch a value that changes during normal approved operation and confirm the SCADA tag follows it with valid quality.
- Restart the communication session in an approved test window and confirm it recovers with the firewall still enabled; a session that works only with the firewall relaxed is not repaired.
- Save the working port tag, driver tag and firewall rule as the baseline before you touch anything else.
The decision for each case #
- Port at 0, driver nonzero, and a second host connects fine: the failing host's firewall. Add the scoped rule for the application to the controller on the EtherNet/IP port and retest.
- Both tags nonzero: transport first. Verify the controller address, the selected NIC and the route; the firewall rule comes after those are proven.
- Port at 0, driver nonzero with the policy proven open: set the Port Segment Path to [] for the direct connection and confirm the driver's parent port tag.
- Port at 0, driver at 0, one data tag bad: fix that tag's data-file address; the communications work is already done.
- Never on this fault: change the PLC program, cycle through protocol options, or disable the firewall to see what happens.
Questions asked
What does a Port Segment Path of [1,0] actually address?
It is a CIP route: leave through port 1, the backplane of a chassis, and stop at node 0. That route belongs to rack-based Logix systems, where the driver reaches a communications module and then a controller in a slot, for example [1,3] for a CPU in slot 3. A MicroLogix 1400 ends the session on its own Ethernet port, so the request should carry no route: enter [] there.
Is TCP 44818 the only port the firewall rule needs?
For this driver, yes. The PCCC over CIP data-file session runs over the registered EtherNet/IP TCP port, so the rule can be scoped to that single destination port. EtherNet/IP implicit I/O connections use UDP 2222, but a tag-reading driver session never opens them, so you do not need to allow UDP for this repair.
Why does a VTScadaLight development PC connect while the SCADA server does not?
Because the two hosts apply different policy. The development PC sits on a different interface, usually with a different firewall profile, and its rules already allowed the traffic. Same controller, same cable and same driver defaults on both machines means the difference is in the failing host's configuration, so repair its firewall rule or route instead of changing the driver on either machine.
Where do I look up the Rockwell Driver error code?
Both pages sit in the installed VTScada help under Tag Reference, in the Communication Driver Tags section: the Rockwell Driver Error Codes page lists each nonzero value, and the Rockwell Driver Help page explains each field. Record the value the tag browser shows now before changing anything, because the earlier -10230 was only recalled from memory. Change one setting, then re-read both tags.