Why a two-wire 4-20 mA transmitter reads zero on the PLC
Short answer
A two-wire 4-20 mA transmitter reads zero because the loop was never completed: one transmitter return terminal must land on the channel input and the return must pass through the input's internal 250 ohm sense resistor back to supply 0 V. No extra resistor is needed; a healthy loop gives 1 V at 4 mA and 5 V at 20 mA.

On this page
- First checks before touching anything
- Why the 500 ohm resistor idea is wrong
- Wire the two-wire transmitter correctly
- Measure loop current and split the fault
- Worked example: load budget at 24 VDC
- Verify the input voltage with the loop connected
- Check channel selection and the raw input value
- The decision for each zero reading
- Questions asked
A two-wire, loop-powered 4-20 mA transmitter reads zero on the PLC for one wiring reason far more often than any other: the loop current never returns through the analog input's internal sense resistor. You do not need a 500 ohm external resistor. The input module already carries a 250 ohm sense resistance, and a correctly completed loop produces about 1 V at 4 mA and 5 V at full scale across the channel terminal and module 0 V. This article walks the zero-reading fault from the field wiring to the PLC mapping, with the checks and numbers that separate a broken loop from a broken program.
First checks before touching anything #
Work down this list in order; each step either finds the fault or eliminates a branch.
- Confirm the transmitter type. A two-wire, loop-powered device uses the same two conductors for power and signal; a four-wire device has separate supply and signal terminals and needs a different return path.
- Stop before adding any resistor. On an input with internal sense resistors, the conversion is already done on board.
- Measure loop current in series. Below 4 mA or zero means the field loop is open or the transmitter is unpowered; a value that tracks pressure means the field side is healthy.
- Verify the return lands on the channel input, not on the supply common. The current must pass through the input's sense resistance; tying the return to the common rail bypasses it and the channel reads zero.
- On transmitters with two equivalent return terminals, use exactly one. Connecting both does not create a redundant loop; one of them can shunt the path you intended.
- Measure DC volts from the channel terminal to the module common: about 1 V at 4 mA, 5 V at full scale confirms current is crossing the sense resistor.
- Confirm the analog module's power and common terminals are actually wired to the power supply. The measured loop voltage is referenced to that common.
- Only then look at the PLC: channel selection, I/O mapping, and scaling. Scaling cannot recover a raw input that is genuinely at zero.
Why the 500 ohm resistor idea is wrong #
An engineer who has only used voltage-output transducers sees a current input, sees 24 V at both ends, and concludes the card needs a load resistor to convert current to voltage. On this class of current input that load already exists: the manual for the F2-08AD-1 documents on-board sense resistors on the channels, with the inputs optically isolated from the PLC logic. Ohm's law across that resistance gives the full working signal:
- 4 mA through the internal resistance: 0.004 A x 250 ohm = 1 V
- Full-scale current through the internal resistance: 0.020 A x 250 ohm = 5 V
An external 500 ohm resistor in series would raise the loop burden by 10 V at full current, eat the transmitter's supply headroom, and still leave the actual fault — an open or bypassed return path — untouched. A 500 ohm shunt belongs on a true voltage input being adapted for current, a different case covered in the article on a 500 ohm shunt giving 2-10 V on a voltage analog input.
Wire the two-wire transmitter correctly #
A loop-powered device powers itself from the same current it measures, so the wiring is one series circuit:
- Power supply +24 VDC to the transmitter's positive terminal (V+).
- One transmitter return terminal (V-) to the channel input terminal (CH+) of the analog module. If the transmitter data sheet marks two equivalent V- terminations, either one works — but only one.
- The analog module's 24 V and 0 V terminals to the same power supply, so the sense resistor's voltage is referenced to a real common.
The error that produces a permanent zero: landing both V- terminals, one on CH+ and one on the supply common. The second terminal completes the loop around the input, no current crosses the sense resistor, and the channel sees nothing. Remove the second connection.
If the device is genuinely four-wire — separate supply terminals and two signal terminals — follow its own connection diagram instead, and identify signal polarity with a meter rather than assuming the two-wire pattern.
Measure loop current and split the fault #
Open the loop at a terminal block and insert a DC milliamp meter in series. Never connect a current-configured meter directly across the supply; that is a short circuit.
- Current is zero or below 4 mA: the fault is in the field circuit — supply polarity, transmitter termination, conductor continuity, or the return through the input module.
- Current sits at a fixed value regardless of pressure: check that pressure actually reaches the port and that the transmitter's configured range matches the test. The PLC cannot fix a stuck field device.
- Current exceeds the 20 mA ceiling: take the channel out of service and inspect wiring and supply before reconnecting; a half-watt sense resistor has limits.
- Current tracks pressure across the signal span: the transmitter and process are fine. Reconnect and move to the voltage check.
The series current reading is the single most useful split in this fault: it separates a field-loop failure from an input-module or program failure. A background on why these transmitters are built this way is in the guide on designing a two-wire loop-powered 4-20 mA current transmitter.
Worked example: load budget at 24 VDC #
Inputs:
- Loop supply: 24 VDC at the transmitter terminals, measured under load (from the reported installation: short runs, little voltage drop).
- Input burden: 250 ohm internal sense resistance (documented in the input module manual).
- Transmitter minimum supply at full current: 14.5 VDC, read from the manufacturer's loop-current-versus-supply chart.
Rule in words: at full-scale current the input resistance drops V = I x R; whatever remains of the supply must still exceed the transmitter's minimum operating voltage.
Arithmetic:
- Input drop at 20 mA: 0.020 A x 250 ohm = 5.0 V
- Voltage left for the transmitter at that current: 24.0 V - 5.0 V = 19.0 V
- Margin above the transmitter minimum: 19.0 V - 14.5 V = 4.5 VDC
Result: the transmitter has 19.0 VDC available at full current against a 14.5 VDC minimum, a 4.5 VDC margin.
Decision: with a 24 VDC supply, this input and this transmitter, the loop is within budget and no resistor of any kind is needed — the original 500 ohm suggestion would have consumed 10.0 V more at full current, dropping the transmitter to 9.0 VDC, below its 14.5 VDC minimum, and stalled the loop at less than full scale. Treat a loaded supply reading of roughly 22 VDC as the point where long cable runs and extra loop devices need checking against the same chart, as shown in a comparable wiring walkthrough for two-wire loop-powered 4-20 mA inputs.
Verify the input voltage with the loop connected #
Reconnect the loop and measure DC volts from CH+ to the module common, positive lead on CH+.
- Negative voltage: channel polarity is reversed; swap the signal conductors.
- Near zero with valid series current: current is bypassing the input. Recheck which return terminal is on CH+ and whether the other V- is tied to the supply common.
- About 1-5 V following pressure: the electrical signal has arrived. Move to the PLC side.
- Fixed voltage with changing current: the meter is across the wrong points, or the common reference is missing.
Check channel selection and the raw input value #
Current-type input modules on modular PLCs often select active channels or ranges with jumpers. A correctly powered loop on an unselected channel will never appear where the program looks. Power the system down with the panel's approved procedure, record the jumper positions, match them to the channel arrangement in the module manual, restore power, and repeat the CH+ to common measurement.
Then monitor the raw input directly in the programming software, not just the scaled engineering value. Many controllers map the first analog input card at consecutive input words — for example WX0 and WX1 on a card in the first slot — but the mapping utility in the programming package shows the exact address assigned. If the raw value moves with pressure and the display still reads zero, the fault is the scaling or the tag mapping, not the loop. Wiring the analog commons correctly matters here too; see the article on wiring 0-10 V outputs to one analog common.
Safety note: open and close the loop only with the panel powered down and lockout applied; a series meter jack briefly interrupts a live measurement circuit, and a meter set to volts across a supply is a dead short.
The decision for each zero reading #
- Raw input zero, series current zero or under 4 mA: field loop fault. Fix supply polarity, termination or continuity; retest.
- Raw input zero, series current valid: the return bypasses the input. Land one V- on CH+, remove any second return to the supply common, confirm module power and common terminals are wired.
- Voltage about 1-5 V across the channel, raw count still zero: channel selection or mapping. Match the jumpers, then fix the raw address and scaling.
- Voltage valid, raw valid, display zero: scaling or program reference. Correct the engineering-unit conversion.
- Never: add an external resistor to a current input that already carries its own sense resistance.
Questions asked
Do I need an external resistor for a 4-20 mA input with an internal sense resistor?
No. The module's internal 250 ohm, half-watt precision resistor already converts 4-20 mA into 1-5 V across the channel terminal and module 0 V. Adding an external resistor raises the loop burden, eats transmitter headroom, and does nothing to fix the open return path that causes a zero reading. Only add a resistor when the input is a true voltage input with no internal sense resistance.
Why does 24 VDC at both devices still read zero?
Voltage present on an open circuit proves nothing about current. A two-wire transmitter needs a complete series loop: supply positive to the transmitter, the transmitter return to the channel input, and the current through the input's sense resistor back to supply 0 V. If the return is wired to the common rail instead of the channel input, or both return terminals are used, no current crosses the resistor and the raw count stays at zero.
What is the loop power budget for a two-wire transmitter on a 24 VDC supply?
At 20 mA, the 250 ohm input drops 5 V, leaving 19 V of the 24 VDC supply for the transmitter and cable. If the transmitter's data sheet lists a 14.5 VDC minimum supply at full current, the margin is 19 minus 14.5, or 4.5 VDC at the transmitter, which is adequate for short cable runs. Longer runs add conductor resistance and reduce that margin.
How do I measure the loop to confirm the fix?
Break the loop at any convenient point and put a DC milliamp meter in series: expect 4 mA with no pressure and a rising value with pressure. Then measure DC volts from the channel input terminal to the module common: expect about 1 V at 4 mA and 5 V at full current. If current is valid but voltage is not, current is bypassing the sense resistor, which points back to the return wiring.