Why a Modbus TCP speed reference is not 32-bit resolution
Short answer
A 32-bit Modbus TCP float does not give 32-bit speed resolution. Usable resolution is set by the least-resolving stage: 12-bit or 16-bit analog channels, the register scaling, and a drive control section stepping at 0.01 Hz across its span, which is only about 12.5 bits.

On this page
- Which stage in the chain sets the real speed resolution?
- How many bits do the analog converters really give you?
- What does the drive's own control section allow?
- Does the 32-bit float survive the trip through the register?
- Does update rate decide anything here?
- How do I verify the real resolution on my own drive?
- Which path should you choose for the pump?
- Questions asked
No. A 32-bit floating-point speed reference over Modbus TCP does not give your pump 32 bits of speed resolution, and the 4-20 mA path is not automatically worse or better: the usable resolution is set by the least-resolving stage in the whole chain, and for most drives that stage is the drive's own control section. This article shows what each stage contributes, works the arithmetic, and ends with the decision for both paths.
Which stage in the chain sets the real speed resolution? #
The stage with the fewest usable increments sets it, and on a typical drive that is the internal frequency command, not the transport. An analog current-loop reference passes through a PLC digital-to-analog converter, the current loop, and the drive's analog-to-digital converter before it becomes a number; a Modbus TCP reference skips all three and arrives as a number directly. Either way the drive then turns that number into an internal speed command with its own step size, so the finest speed change you can actually command equals that internal step, whatever you sent.
Compare the two paths stage by stage:
| Stage | 4-20 mA path | Modbus TCP path |
|---|---|---|
| PLC numeric value | shared | shared |
| PLC output conversion | DAC, 12 or 16 bit | none |
| Signal transmission | current loop, noise and drift | Modbus TCP frames |
| Drive input conversion | ADC, 12 or 16 bit | register scaling |
| Drive internal speed command | same steps both paths | same steps both paths |
Digital communication removes the analog output, the loop and the analog input from the reference path, which removes their conversion errors, but it cannot create finer speed increments than the drive accepts and uses.
How many bits do the analog converters really give you? #
A 12-bit converter gives 4,096 codes and a 16-bit converter gives 65,536, and these are the ceilings before anything else is subtracted. Both figures are common for PLC analog output modules and drive analog inputs; drive manuals describe the analog inputs as programmable for duty as a speed or frequency reference, with the resolution stated in the drive's own hardware manual. Worked example for the 4-20 mA path: a 16-bit output spanning 4 to 20 mA has 16 mA of span, so one least-significant code is 16 mA divided by 65,536, about 0.24 microamp. Across the same 16 mA span that represents a 0 to 100 percent command, one code is about 0.0015 percent of span. On a 60 Hz drive that is roughly 0.0009 Hz per code from the converter alone, which looks fine, until the drive's internal command steps say otherwise.
Those code counts also shrink in practice: endpoint conventions, live-zero offsets and over-range excursions, and calibration error all cost usable codes, and each analog stage in the path costs them independently.
What does the drive's own control section allow? #
A sensorless drive stepping its frequency command at 0.01 Hz over a 60 Hz span has only 6,000 usable increments, which is about 12.55 bits. The arithmetic: 60 Hz divided by 0.01 Hz per step is 6,000 steps, and log2 of 6,000 is about 12.55. That is the ceiling for both paths on such a drive. Sending a 32-bit float cannot produce a speed change finer than one internal step, and a 16-bit analog channel with 65,536 codes cannot either, because 65,536 codes across the same span would suggest 0.0009 Hz steps the control section never applies. Check your drive's manual for its frequency reference resolution or minimum frequency step; that number, divided into the span you actually use, is your true end-to-end resolution in bits.
Does the 32-bit float survive the trip through the register? #
Only until the drive scales or rounds it. The float format carries about seven significant decimal digits, so 87.34567 percent arrives intact at the drive. The drive then multiplies by its register scaling, for example a 0.01 factor so 8,734.567 maps to a 16-bit or 32-bit register word, and converts the result to an internal command in 0.01 Hz steps. The value you sent and the value the drive applies can differ by more than the float's own precision. The register data type, scaling factor and accepted range are stated in the drive's communications manual, and the register round-off joins the internal step size as a second ceiling on the digital path.
Does update rate decide anything here? #
It can, and it favors neither path by default. Higher numeric resolution is worthless if command updates arrive slower than the pump loop needs, so compare the two paths' actual update behavior: the analog output updates every PLC scan with essentially no transport delay, while the Modbus TCP write rate depends on your scan time, network load and how the drive applies register writes. A parallel-polling architecture keeps digital reference updates fast under load, as covered in the article on why parallel Modbus TCP clients beat one sequential poller. Measure it rather than assume it, using the method in the article on measuring PLC to SCADA command response time end to end.
How do I verify the real resolution on my own drive? #
Test adjacent commands and watch what the drive actually applies. The procedure:
- Read the drive manual for three numbers: the analog input resolution, the Modbus frequency reference register's data type and scaling, and the internal frequency reference resolution.
- Compute the increments each stage allows over your actual span, and take the smallest as your expected end-to-end resolution.
- On the digital path, write two adjacent float values, for example 50.000 and 50.005 percent, and read back the drive's internal reference or output frequency. If both land on the same internal step, your effective resolution is coarser than the float.
- On the analog path, step the PLC output by one code at mid-span and watch the drive's displayed reference for a distinct change.
- Repeat at the top and bottom of the span, where endpoint and live-zero conventions bite hardest.
The smallest command change that produces a distinct applied setpoint is your measured resolution. If the digital path misbehaves during this test, the failure modes are usually register mapping and command gating rather than resolution, as described in the article on why a VFD ignores Modbus RTU start commands from a PLC.
Which path should you choose for the pump? #
Choose Modbus TCP when its register scaling and update rate meet the pump's control needs, because it removes the DAC, the current loop and the ADC and their offset, drift and noise errors from the reference. Choose the analog current loop when the loop is short, the resolution math above satisfies the process, and you want a reference path that survives network faults; remember that a lost analog reference has its own failure behavior, covered in the article on why a VFD runs at minimum speed when the analog reference is lost.
On a 60 Hz sensorless drive with 0.01 Hz internal steps, both paths deliver the same usable resolution of about 12.5 bits, so decide on error sources, diagnostics and network reliability, not on the bit width of the transport. For a full side-by-side of the interface options, see the article on how a PLC controls a VFD: five interfaces compared.
One safety note: whatever path you pick, the drive's own safe-stop and emergency-stop functions stay hardwired; neither a Modbus TCP command nor a current loop is a safety channel.
Questions asked
How many steps does a 0.01 Hz resolution over the drive's span actually give?
6,000 steps, because 60 Hz divided by 0.01 Hz is 6,000 increments. In bits that is log2 of 6,000, about 12.55, so the drive's control section caps end-to-end resolution near 12.5 bits regardless of how the reference travels.
What limits resolution on the 4-20 mA path besides the DAC?
Three stages each add a limit: the PLC analog output converter, the drive's analog input converter, and the drive's internal speed command steps. A 12-bit channel has 4,096 codes and a 16-bit channel 65,536, but the final command is never finer than the drive's internal resolution, and analog stages also add offset, drift and noise error.
Does a 32-bit float in a Modbus register preserve the value end to end?
No. The float carries roughly seven significant decimal digits in transit, but the drive converts it to a register or internal command with its own scaling and step size, so the delivered speed increment equals the drive's internal resolution, not the float's.