Troubleshooting
Why a LOGO! 8 AM2 module RUN LED stays off
Short answer
When the RUN/STOP LED on a LOGO! 8 AM2 expansion module stays completely dark, the module has no operating power: it is not an analog scaling or program problem. Measure the supply directly at the AM2 power terminals with the module connected, repair the termination, then re-seat the expansion connector to the device on its left.

On this page
A LOGO! 8 AM2 expansion module with a completely dark RUN/STOP LED is not operating at all, and no program change will make it read inputs. The dark LED separates this fault from a communication fault: orange means the module is initializing, red means it is powered but not talking to the device on its left, and only a total absence of light means the module electronics are dead. In the reported installation, a LOGO! 8 CPU 6ED10521HB000BA8 and an AM2 module 6ED10551MA000BA2 sit on a shared 24 VDC supply, the lugs and plug are engaged, and the inputs never reach the program. Start with a meter at the module's own power terminals, then the expansion connector, and leave scaling alone until the LED is green.
What each RUN/STOP LED state means #
The AM2 indicator distinguishes module operation from communication, and each state sends you to a different place:
| LED state | Meaning | Where to go next |
|---|---|---|
| Off | The expansion module is not operating | Its power terminals and the supply-wire contact |
| Orange | Initialization phase | Watch whether it progresses to green |
| Red | No communication with the left device | The expansion connector and the left-hand device's state |
| Green | Communication with the left device established | Channel assignment and the 4-20 mA loop |
A base module that runs normally proves nothing about the AM2's power. The two devices can share one supply yet lose it through separate conductors, distribution terminals, or individual terminations. The same goes for the expansion interface: an engaged plug shows mechanical position, not electrical continuity.
Measure at the module's own power terminals #
The measurement that decides this fault is the potential difference directly between the AM2's positive and return power terminals, with the module connected and supposed to be running. Measuring at the power supply output only checks the source; it does not cover the wires, the terminals, or the contact under each clamp.
A termination can look connected and still fail. A loose conductor, insulation trapped under a clamp, or a strand sitting outside the clamping area all leave the wire apparently seated. A high-resistance contact is worse than an open one, because it drops voltage only when the module draws current, so an unloaded measurement on a pulled wire reads a healthy nominal value while the powered module sees almost nothing. Check the return conductor with the same care as the positive: a good positive with an open return still leaves the module without a circuit. Verify polarity against the module markings; a healthy 24 VDC source somewhere else in the cabinet is not the test.
The analog signal and module power do different jobs. The 4-20 mA loop carries the measurement; the supply lets the module's electronics process that measurement and put it on the expansion interface. A module with no operating power ignores scaling, channel configuration, and program logic completely.
Repair sequence #
Work through this list in order and record each result:
- Record the starting state. Note the CPU's operating indication, the AM2 LED color or absence of light, and the program's analog value. For this fault the expectation is: LED off, value frozen.
- Measure the source. Confirm the supply output is near nominal with correct polarity. This establishes what the module should be receiving.
- Measure at the AM2. With qualified personnel and controlled live-measurement practice, measure between the module's own power terminals while it is connected. Pass is a reading near nominal; a reading near zero or far below nominal fails and ends the search here.
- Isolate power, then inspect both terminations. Look for loose conductors, damaged strands, misplaced ferrules, and insulation inside the contact area. Re-terminate both the positive and the return.
- Inspect the expansion interface. With power isolated, check alignment, full engagement, and visible connector damage between the AM2 and the device immediately to its left. Refit the connector fully.
- Restore power and watch the LED. Expect orange during initialization, then green. Red sends you back to step 5 and to the left-hand device's own state; still-dark keeps you on power delivery or module hardware.
- Prove the measurement path. Only after green: confirm the program reads the physical channel carrying the signal, drive the loop with a calibrator, and confirm the value tracks the applied current.
The same discipline applies to other platforms: when S7-1200 expansion module I/O does not update, the cause is likewise in the detection and communication path before the program, as covered in why S7-1200 expansion module inputs and outputs do not update.
Worked example: the reading that ends the search #
Take the reported installation. At the supply output you measure 24.2 VDC, correct polarity. With the module connected and its LED dark, you measure across the AM2's own power terminals: 2.1 VDC.
The voltage missing at the module is:
24.2 VDC − 2.1 VDC = 22.1 VDC
The module is receiving 2.1 VDC of the 24.2 VDC supplied, so 22.1 VDC is dropping across something between the source and the module, and the only candidates are the two conductors and their terminations. That is a failed contact, not a scaling problem, and the decision is made without opening the program. Isolate power, pull the return conductor, and in this example you find the insulation seated in the clamp instead of the copper. Re-terminate both ends.
After re-termination, the terminal measurement reads 24.1 VDC, within a tenth of a volt of the source, so the loop resistance of the supply path is now negligible. The LED shows orange for the initialization phase, then green. If the reading had stayed at 24 VDC at the terminals with the LED still dark, the fault would be inside the module and the measurements would go to Siemens support with both order numbers, 6ED10521HB000BA8 and 6ED10551MA000BA2.
An orange RUN/STOP LED on other Siemens controllers means something different again; on an S7-1500, a RUN/STOP LED blinking orange points to the CPU stuck in its connecting phase, not to module initialization. Read the color against the device's own manual, not by analogy.
Green is the start of the analog checks, not the end #
Green proves communication with the left device and nothing more. It does not prove the transmitter is wired to the channel the program monitors, and it does not prove the current loop is complete. Treat operation, communication, and measurement as three separate acceptance checks:
- Channel match. Compare the configured analog input with the physical terminal carrying the signal; read the assignment from the project configuration, not from memory.
- Loop continuity. A current loop is a closed circuit in which the current represents the process variable. Confirm the transmitter's power arrangement against the AM2 wiring diagram, with correct polarity and a return path.
- Known signal. Drive the input with a loop calibrator: the monitored value must track the applied current across the range. For a linear mapping, the bottom of the range maps to the configured lower endpoint and the top to the upper endpoint; the same endpoint arithmetic applies when fixing 4-20 mA scaling on a Quantum AVI030 analog input.
One limit worth knowing before blaming hardware: the LOGO! system manual documents a maximum of 16 expansion modules on one base module, and a 17th module in the chain is simply not detected. If the AM2 was recently added at the far end of a long chain, count the modules before ordering a replacement.
Do not rewrite the program while the LED is dark. That buries a hardware fault under software changes and destroys the baseline. Restore operation first, establish communication second, prove the measurement third. Once the LED is green and the values still wander, the cause moves to the signal lines: use shielded sensor cable and keep it short, as the module's own EMC guidance requires.
Questions asked
Can the CPU read AM2 analog values while the LED is red instead of green?
No. Red means the module is powered but has no communication with the device to its left, so no measured values reach the base module's program. Red points you at the expansion connector and the operating state of the left-hand device, not at the analog wiring. Fix communication first; only a green LED guarantees that channel data is being exchanged.
How many expansion modules can one LOGO! base module detect?
The LOGO! system manual documents a maximum of 16 expansion modules on one base module. A 17th module in the chain is not detected, which shows up as absent I/O with no further fault indication. If your installation has grown past 16 modules, the last ones added will never appear no matter how good their power and connectors are, and the chain must be split or reduced.
The LED is green now but the analog values fluctuate. Is the power still bad?
Not necessarily. Fluctuating readings on a green, communicating AM2 point to the signal lines: use only shielded sensor cable, keep the sensor cable as short as possible, and connect the shield as the module documentation specifies. Power and connector faults stop communication entirely; noise on long unshielded sensor lines corrupts an otherwise working measurement.
Can wrong 4-20 mA transmitter wiring keep the RUN/STOP LED dark?
No. The RUN/STOP LED reports module power and communication only; the analog signal is a separate function. A broken current loop or reversed transmitter produces wrong or frozen values while the LED stays green. Conversely, a perfectly wired 4-20 mA loop cannot light the LED when the module itself has no operating power, so repair power first and test the loop second.