Short answer

The warning compares two stored associated file names for the same module at one node and slot: one in the Logix .ACD project, one in the RSNetWorx .XC file. Align them with Set Association on the offlink CNB, or clear them on both sides. The running network is not affected.

On this page
  1. Why does my ControlLogix project warn about conflicting associated file names on save?
  2. How do I read the warning text to find the exact module?
  3. Can both networks run normally and still produce this warning?
  4. Should I align the association or delete the associated file name?
  5. How do I set the association on the offlink CNB in RSNetWorx?
  6. How do I verify the fix from both directions?
  7. Why does the warning come back after files move to another computer?
  8. Questions asked

The warning on save is not a network fault. It says that two engineering files store different associated RSNetWorx file names for the same module at the same node and slot: one association lives in the Logix .ACD project, the other in the RSNetWorx for ControlNet .XC file. Fix the mismatch in software, save both files, and leave the hardware alone.

Why does my ControlLogix project warn about conflicting associated file names on save? #

The warning appears because the .ACD project and the .XC project each store their own associated file name for one module, and the two names differ. When you save the Logix project or launch RSNetWorx from it, the software merges the two records, finds a mismatch at a node and slot, and reports the conflict.

ControlLogix stores the association in two places on purpose:

  • The association inside the .ACD project lets you launch RSNetWorx for ControlNet from the Logix environment.
  • The association inside the .XC file supports Jump to the Associated Network, which navigates from one ControlNet project to another through a bridge module.

The second association is assigned on offlink CNB modules. Offlink means a CNB in a rack other than the bridge connecting that rack to the local ControlNet network. A project with several ControlNet networks holds several offlink bridges and several .XC files, and each bridge must point to the file assigned to the same module in the Logix I/O tree. When two records disagree, RSNetWorx cannot treat the navigation relationship as unambiguous and warns while merging.

If you need a refresher on why the .XC file exists at all in a bridged setup, the article on why a PLC-5C15 FLEX I/O ControlNet setup needs the XC file covers the same file from the other side.

How do I read the warning text to find the exact module? #

Read the warning literally: the node and slot fields identify the module record that was being merged when the mismatch was found. An earlier line that says Merging module names the same location. Use those two numbers to pick the module before you change anything.

The message compares an associated RSNetWorx file name against the ControlNet project record at a matching node and slot, so it points at one location. Do not clear or edit associations across the whole I/O tree. A working 1756-DNB cannot diagnose this warning, and replacing modules or reterminating media cannot fix two disagreeing file names.

Can both networks run normally and still produce this warning? #

Yes. The conflict lives in engineering-file navigation metadata, so both networks can pass traffic normally while the warning appears every save. The warning is not evidence of a failed connection, a bad node, or a hardware fault, and it does not clear just because both networks look healthy.

Check network health separately, through the status and diagnostic views you normally use. Treat any real communication fault, unscheduled connection drop, or module status indication as its own diagnostic path. If the only symptom is this warning on save, the correction is entirely in the project files.

Should I align the association or delete the associated file name? #

Align the association when your maintenance workflow uses the launch and jump navigation between ControlNet projects; delete the associated file names when it does not. Both corrections stop the warning, and the second is the simpler one. Do not mix them: one side populated and the other pointing elsewhere recreates the conflict.

To align, set the RSNetWorx association to the same .XC file selected for that module in the Logix module properties, comparing the full name and location rather than similar-looking base names. To delete, clear the associated file name in the module properties on both the CNB and DNB modules named by the warning, then save the changed project files. Do not delete the .XC project itself to clear an association.

Before clearing links, record which .XC file belongs to each ControlNet network so technicians can still open the correct project manually. The links are a convenience that goes stale when projects move between computers, which is exactly how this warning usually returns.

Set the association through the module Properties and the Device Bridging tab, and apply it to the bridge the warning names, not the one connecting the chassis to the local network. Work through these steps for each reported node and slot:

  1. Open the RSNetWorx for ControlNet .XC file involved.
  2. Select Enable Edits.
  3. Find the chassis from the warning and right-click the offlink 1756-CNB at the reported node and slot.
  4. Open Properties and select the Device Bridging tab.
  5. Select Set Association.
  6. Choose the same .XC file assigned to that module in the Logix module properties.
  7. Apply the change and save the .XC file.
  8. Repeat for every other offlink CNB in a chassis on a separate ControlNet network, then save again.

How do I verify the fix from both directions? #

Verify by reopening the projects and testing the navigation that caused the comparison in the first place. Close the edited ControlNet project first so the check does not rely on unsaved in-memory data, then:

  • Reopen the .ACD project and launch RSNetWorx for ControlNet through the associated module; the warning for that node and slot should be gone.
  • In RSNetWorx, right-click the offlink CNB and test Jump to the Associated Network if you kept navigation.
  • Confirm the jump opens the intended .XC project, not a file with a similar name.
  • Repeat for every ControlNet network represented in the Logix project.

If you removed the associations instead, the verification is simply that repeated saves no longer warn. That proves the engineering references agree; it does not certify the physical network, so run your normal status checks afterward.

Why does the warning come back after files move to another computer? #

The associations are file names and paths, and a move changes how they resolve. When the .ACD and .XC files are copied to a different PC, one stored reference can point at a different file than the other, so the same comparison fails again. Recheck both associations from the new location and save both files there.

Other recurring traps to avoid: editing only the first warning when a multi-network project holds several mismatches; selecting the local bridge instead of the offlink one; saving only the .ACD file when the second association lives in the .XC file; and assuming a healthy 1756-DNB rules out the warning. Work the node and slot the message gives you, every time it appears.

Questions asked

Does the warning mean my ControlNet or DeviceNet network is failing?

No. The warning is a comparison of two stored engineering file references for one module location. Both networks can run normally while it appears. Check network health through its own status and diagnostics, and treat any live communication fault as a separate diagnostic problem.

Why does the warning come back after I copy the project to another computer?

The stored association is a file name and path. When the .ACD and .XC files are moved or copied to a different PC, the two stored references can resolve to different files, so the comparison fails again.

What is an offlink 1756-CNB module?

It is a ControlNet bridge module in a chassis other than the bridge that connects that chassis to the local ControlNet network. A Logix project with several ControlNet networks has several of them, each with its own associated .XC file, which is why the associations can drift apart.

Keep reading

  • Explainer

    Why a PLC-5C15 FLEX I/O ControlNet setup needs the XC file

    A PLC-5C15 drives FLEX I/O over ControlNet through a 1794-ACNR/15 with no extra hardware. RSNetWorx for ControlNet builds the scanlist and the real I/O connections and loads them with Save to Network; RSLogix 5 shows rack descriptions only after you associate its project with the matching .XC file. Discovery succeeding in RSNetWorx while RSLogix 5 shows nothing is a missing file association, not missing hardware.

    Industrial networks

  • How-to

    Configuring the S7-200 EM277 as a PROFIBUS DP slave

    The EM277 takes no PROFIBUS configuration inside the S7-200. You import its GSD file into the DP master's hardware configuration, set the slave address to match the module's rotary switch, choose the input and output byte counts, and set the V-memory offset that selects the memory block the S7-200 program reads and writes. The module is slave-only, so a master such as an S7-300 or a configured PC station must run the exchange.

    Industrial networks

  • How-to

    How to map a 1747-SDN scanner for DeviceNet drive control

    Seeing the drive in an RSNetWorx browse is not an I/O connection. Put the drive in the 1747-SDN scanlist, read the M-file words the scanner mapping assigns, and reference those mapped words in the SLC 5/04 ladder. A node address is not an integer-file offset: the mapping view, not node 10, decides where each command and status word lives.

    Industrial networks