Troubleshooting
Why 1769 modules show a red X in RSLinx
Short answer
The red X is a stale browse marker, not a module fault: with no application firmware or project loaded, the 1768-L45 cannot forward CIP traffic from the 1768-ENBT across the backplane to the 1769 bank, so every module behind it browses stale. Load matching firmware and a project with the correct I/O tree first, then bring up DeviceNet power, baud rate and node addresses through the scanner's own port.
On this page
A red X on the 1769-SDN and on every 1769 I/O module behind a 1768 CompactLogix, with a clean 1768-ENBT above them, is one fault, not four. The X is a stale browse marker: RSLinx drew those icons from the last enumeration that succeeded, and a controller with no application firmware or project loaded cannot forward CIP traffic from the ENBT across the backplane onto the 1769 bus, so every object behind it times out and is repainted stale. Fix it in that order: firmware and a project with the correct I/O tree into the 1768-L45 first, then DeviceNet trunk power, baud rate and node addresses, then the RSNetWorx browse path. Pulling the scanner off the bank gives the proof: the three discrete modules keep their X without it, because they never answered a browse themselves.
What the red X actually tells you #
RSWho draws its tree from the last enumeration that succeeded and repaints an icon with a red X when the next browse cycle times out for that object. Rockwell's RSLinx troubleshooting note defines the X as a device that is not currently responding to RSLinx Classic, not as failed hardware. Because the icon is a cache entry, clear it before you diagnose: delete the devices from the RSWho tree, stop and restart the RSLinx driver, and browse again. A device that comes back clean had a stale entry; a device that stays X is genuinely not answering.
Then follow the route the browse takes. From the laptop it is four hops: the EtherNet/IP driver, the 1768-ENBT, the 1768 backplane to the controller, then out along the 1769 bus to each module. The ENBT answers the first hop by itself, which is why it stays clean while everything behind the controller goes stale. A discrete 1769 module carries no network processor of its own; the way discrete PLC I/O modules isolate and switch field signals leaves the talking to the controller, which inventories the bank and answers browse requests on each module's behalf. The 1769-SDN is the exception behind the controller: it has its own processor and identity and must answer for itself.
That asymmetry is the whole diagnosis. A clean ENBT with an X on the scanner and all three discrete modules means the controller is not bridging CIP traffic onto the 1769 bus, and no amount of I/O swapping changes that. The same hop-by-hop logic governs any bridged route; reaching a CompactLogix through a ControlNet bridge in RSLinx is worked out the same way, one hop at a time.
Read the panel before you trust the screen #
RSWho reports what RSLinx last heard; the LEDs report what the hardware is doing now. Check them in this order:
- 1768-L45 OK LED solid or flashing red — no application firmware, a major fault, or an I/O fault. Nothing behind the controller browses until this is green.
- 1769-SDN module status LED off — no 1769 bus power reaching the module. Reseat bus levers and check bank power before blaming the scanner.
- 1769-SDN module status LED green, network status LED off — the DeviceNet trunk has no network power. Measure at the scanner's drop before configuring anything.
- Network status LED red with a code on the scanner's two-digit display — a duplicate node address, a bus-off condition, or slaves that are not answering. Read the code against the error table in the scanner's manual.
- RSNetWorx browse completes with an empty network and no error — the driver path is aimed at the 1769 backplane instead of the DeviceNet port under the scanner.
Bring the controller up first #
One safety note before the steps: flash and download only with the machine stopped and locked out, because a controller mid-flash or reset to no firmware can drop every output on the 1769 bank at once.
- Check bank power and seating. The 1768 power supply powers the controller's local bank, the 1769 modules attached to its right included; a 1769 power supply must never be placed in that bank, because the 1768 controller user manual documents a major fault for exactly that. Power down, push every 1769 bus lever fully home left to right, and confirm the 1769-ECR end cap sits on the last module.
- Flash the controller if it has none. Browse the 1768 bank: a controller that appears as an unrecognized device, or with its OK LED solid red, has no application firmware. Flash it with ControlFlash to the revision that matches your RSLogix 5000 major revision; the 1768-L4x family ends at major revision 20, so a newer kit will not load.
- Create the project offline with the controller type set to 1768-L45 and the revision set to the firmware you just flashed.
- Build the I/O tree: the 1768-ENBT in its physical slot on the 1768 bus, then every 1769 module in physical order left to right starting at slot 1, with the 1769-SDN's input and output word sizes set to match the module.
- Download and put the controller in Run or Remote Run. The CIP route does not depend on your ladder logic, but it depends entirely on a running controller that owns its I/O tree.
- Browse again. The controller should answer clean, the scanner should return its identity with its firmware revision, and the discrete modules should clear with it. Then prove the bus with a live point: toggle a field input and watch its tag — for example
Local:1:I.Data.0on slot 1 — change in the program.
Before any module is condemned, run two document checks. The scanner's release note 1769-RN007 states that its firmware enhancements are supported only with 1769-L3x or 1768-L4x controllers, and the pairing matrix in Rockwell Knowledgebase article 462381 settles which scanner firmware revision goes with which controller revision — a brand-new scanner carrying the wrong revision shows the same X as a dead one. If the scanner needs its own firmware update, do it through its DeviceNet port with a USB-to-DeviceNet interface, never across the 1769 bus. And expect nothing from a swap: replacing the scanner cannot fix a routing fault, so a replacement shows the same X until the controller bridges.
Bring DeviceNet up on its own terms #
With the controller bridging, the scanner browses clean and the network behind it becomes an ordinary wiring and configuration job. The 1769-SDN neither powers the trunk nor runs its DeviceNet transceiver from the 1769 bank, so the network has its own supply: measure V+ to V- at the scanner's drop and expect 24 VDC nominal, with anything between 11 and 25 VDC workable at the farthest node. No network power means no port and no browse, whatever the software says.
Set the baud rate explicitly at every node — 125, 250 or 500 kbps, identical throughout — instead of leaving the scanner on autobaud, which needs a live node to listen to and a dead network has none. Set node addresses one device at a time in the range 0 to 63, all unique; most slaves ship set to node 63, so two unconfigured slaves both fail the duplicate-address check and drop off, which looks exactly like a dead network.
Check the physical run against the ODVA DeviceNet media limits for the baud you chose: trunk up to 500 m at 125 kbps, 250 m at 250 kbps or 100 m at 500 kbps, each drop no longer than 6 m, and a cumulative drop length of 156 m at 125 or 250 kbps, 39 m at 500 kbps. The cumulative drop budget is the one that gets blown.
In RSNetWorx for DeviceNet, point the browse path through the scanner's DeviceNet port — the route runs laptop to ENBT to controller to scanner to port — then browse and upload the network before you build any scanlist. Getting the DeviceNet configuration connection path right is the difference between an empty browse window and a live network map.
Worked example: a drop budget that fails by one metre #
Take the common default of 500 kbps on a network with the scanner and eight slaves, a 90 m trunk and eight drops of 5 m each. Trunk first: 90 m sits inside the 100 m limit at that baud rate, so the backbone passes. Cumulative drop next: 8 × 5 m = 40 m against the 500 kbps budget of 39 m — over by 1 m, and networks fail on margins exactly this thin. Two fixes, both arithmetic: shorten two drops to 4 m, giving 6 × 5 m + 2 × 4 m = 38 m inside the budget; or run the whole network at 250 kbps, where the trunk limit rises to 250 m and the drop budget to 156 m and the layout passes as built. Decision: this layout is invalid at 500 kbps and valid at 250 kbps.
The decision in each case #
- X on the scanner and all discrete modules, ENBT clean, controller never had a project: load matching firmware, download a project whose I/O tree matches the bank, browse again, and confirm with a toggled input tag. Do not replace modules.
- One discrete module still X after a good download: the tree does not match the physical bank. Compare slot by slot and correct the tree; the icon follows the tree, not the wiring.
- Controller clean but RSNetWorx shows an empty network with no error: the browse path points at the backplane. Repoint it to the DeviceNet port under the 1769-SDN.
- Scanner clean but slaves missing and the network status LED dark: no trunk power. Measure V+ to V- at the farthest drop and expect 24 VDC nominal there, 11 to 25 VDC usable.
- Slaves appear, then drop off in groups: duplicate node addresses or a blown drop budget. Set addresses one device at a time and redo the media arithmetic at the baud in use.
Questions asked
What is the difference between a red X and a yellow question mark in RSWho?
A red X means the device stopped answering a browse that had succeeded before. A red X drawn together with a yellow question mark means RSLinx has never received a reply from a device it expects to exist, so the icon marks hardware the software knows should be there but has never talked to. In both cases the icon reports a communication state, not a failed module; judge hardware by its LEDs and the controller's fault status.
RSLinx reports Failed to show RSWho before I even browse — what does that mean?
That error appears before any device is polled, so it says nothing about the PLC network. It is a failure of the RSWho display component on the PC, and the usual trigger is a recent Microsoft Windows 10, 8 or 7 update. Treat it as a computer problem first: clear it at the PC, then reopen the browse and apply the red X diagnosis to the 1769 modules.
RSNetWorx finds the scanner but shows the slaves as unknown devices — what is missing?
The slaves are answering, so the trunk is alive; what is missing is each device's EDS file, the description file RSNetWorx uses to turn a node's electronic identity into a product name and its parameters. Register the EDS file for every slave model through the EDS wizard, then browse again. Without them the network can still be scanned and configured, but devices show generic names and setup is slower.
What should the 1769-SDN two-digit display show when the network is healthy?
On a healthy scanner the display holds one steady number, which is its DeviceNet node address. A value that alternates between the address and another number is an error code: read it in the scanner's manual table to tell a duplicate node address from a bus-off fault before touching wiring. The steady address alone confirms the scanner is powered and running on the trunk.