Which S7-300 modules TIA Portal V13 supports, and where to look

PLC programming Published 4 min read

Short answer

A STEP 7 V5.5 project proves nothing about TIA Portal V13. Check the exact CPU and modules in the installed hardware catalog under SIMATIC S7-300 > CPU in Network view, and against the vendor's supported-hardware list. A CPU missing there, such as the CPU315 in the reported case, is a no; a GSD file cannot add it.

On this page
  1. Where does TIA Portal V13 list the S7-300 modules it supports?
  2. Can a GSD file add a missing S7-300 CPU to TIA Portal V13?
  3. Which document lists the modules TIA Portal V13 actually supports?
  4. How do you check a whole STEP 7 V5.5 project before migrating?
  5. Questions asked

A STEP 7 V5.5 project proves nothing about TIA Portal V13. Whether an S7-300 CPU or module can be configured is decided by the hardware catalog installed with your TIA Portal version and edition, and in the reported V13 Professional case the wanted CPU315 was not in it, with no catalog-side way to change that. This article shows you where to look, what a Hardware Support Package can and cannot add, and which decision follows for each result.

Where does TIA Portal V13 list the S7-300 modules it supports? #

Open Network view in TIA Portal V13, open the hardware catalog, and expand the controller category: the list under SIMATIC S7-300 and then CPU is the complete set of S7-300 controllers this installation can configure. Click the little arrow or double-click each entry to expand it. If your exact CPU is listed, configure it; if it is absent, it is unsupported in this version, and no setting in the software changes that. There is no filter, view option or preference that hides supported CPUs, so an empty result is a real result, not a display problem.

The screen in the reported case showed the device view of an ET200S station, which has nothing to do with GSD files or CPU support. The device view shows the modules of that one station. Return to Network view and read the controller catalog, not the station.

Can a GSD file add a missing S7-300 CPU to TIA Portal V13? #

No. GSD files describe PROFIBUS and PROFINET I/O devices, not S7-300 CPUs, so importing one cannot make a CPU315 appear under SIMATIC S7-300. GSD import is a remedy for a missing I/O slave or device, never for a missing controller. When the CPU is absent from the catalog, the answer is a no, not an import problem. Where a GSD path genuinely applies to I/O, it has its own constraints, as with the FM 350-1 on the CP 342-5 GSD master path.

Which document lists the modules TIA Portal V13 actually supports? #

The vendor's Support Packages page for the TIA Portal hardware catalog carries the supported-hardware information: it includes a list of the modules contained in the Support Packages for TIA Portal V13, covering the S7-300 CPUs. A Hardware Support Package (HSP) is the documented way to configure modules that are not contained in the hardware catalog of your current STEP 7 installation, so it can add an older module only when that module is on the V13 package list.

Install the package with TIA Portal closed: download the HSP for your version from the support portal, close TIA Portal, run the installer, then reopen the catalog and look again under SIMATIC S7-300. For the compatibility of hardware already contained in a STEP 7 project, the vendor's Compatibility Tool for Automation and Drive Technology gives the compatibility statements for your exact components.

How do you check a whole STEP 7 V5.5 project before migrating? #

Write down the exact order number and firmware of every CPU and module in the STEP 7 V5.5 hardware configuration, then check each one twice: against the installed catalog in Network view, and against the V13 Support Package list. Only items that pass both are configurable in the migration target.

A worked example: the project holds a CPU 317-2 PN/DP with order number 6ES7 317-2EK14-0AB0 at firmware V3.2, plus a CPU315. The check runs as:

  1. CPU 317-2 PN/DP, 6ES7 317-2EK14-0AB0, V3.2: listed for TIA Portal V13, high-performance PN/DP. Pass: configure it.
  2. CPU315: absent under SIMATIC S7-300 > CPU in the installed catalog and on no V13 Support Package list. Fail: not configurable in V13.

The decision per result:

  • CPU present in the catalog and on the V13 list: proceed with the migration.
  • I/O module missing but present in a V13 HSP: install that package, reopen, proceed.
  • CPU absent from both: no. Either move to a newer TIA Portal version whose catalog lists that exact CPU and order number, or change the CPU in the machine before migrating. There is no third path.

Do this check before you touch the logic. A migration that fails on the hardware configuration wastes the time spent converting the code, and the catalog check takes minutes: two lookups per module, recorded next to the order number, so the result can be handed to whoever plans the machine change.

The same catalog-first rule applies when TIA Portal cannot migrate a project to an S7-1200 or when you migrate an S7-300 project from STEP 7 v5.5 to TIA Portal as a whole: the target catalog decides, not the source project.

Questions asked

Can a Hardware Support Package add an older S7-300 module to TIA Portal V13?

Only if that module is contained in a Support Package issued for V13. The download page lists the modules each package contains, so check the list before installing; run the installer with TIA Portal closed. A CPU that appears in no V13 package stays unsupported.

Why does the module show in an ET200S device view but not in the controller list?

The device view of an ET200S station shows the I/O modules of that station, not the CPUs the installed version can configure. Open Network view instead and expand the hardware catalog through SIMATIC S7-300 and CPU to see which controllers this installation supports.

Does the STEP 7 V5.5 project compile in TIA Portal V13 if the CPU is missing?

No. Migration imports the hardware configuration, and a CPU the target catalog does not contain cannot be configured or loaded. Resolve the CPU question first, either by a newer TIA Portal version that lists it or by changing the CPU, before migrating any logic.

Keep reading

  • Troubleshooting

    Fix STEP 7 V5.5 warning after TIA Portal wrote an S7-300

    Download the hardware configuration and blocks from a freshly created SIMATIC Manager project and the warning clears; a CPU 313C-2DP recovered exactly this way. Formatting the MMC with the mode switch (MRES held roughly 9 s until the STOP LED stays lit) does not clear the TIA-written state, so use it only when you also want the card empty.

    PLC programming

  • How-to

    Migrating S7-300 projects from STEP 7 v5.5 to TIA Portal

    You can migrate an S7-300 project from STEP 7 v5.5 into TIA Portal with the migration tool, but the converted project goes online without showing online blocks: timestamps in the CPU no longer match, so TIA treats the program as inconsistent and wants a full transfer after any change. Keep the classic toolset for large programs and firmware updates; use TIA for small S7-300 projects that gain a unified project with an HMI or an S7-1200.

    PLC programming

  • Troubleshooting

    MB_CLIENT version change after TIA Portal V16 migration

    A TIA Portal V13 SP1 to V16 migration does not by itself change the drive; it changes which MB_CLIENT revision, CPU firmware and request data the project carries. Compare the instruction version in both archived projects, read the online CPU identity (the replacement CPU may be V4.4 or V4.5), test the older revision in a project copy, and capture one request to confirm address, quantity and word order before judging homing failures as drive faults.

    PLC programming