Troubleshooting
Which runtime gives a WAGO PFC200 PROFINET and EtherCAT master
Short answer
Fieldbus roles on a WAGO PFC200 follow the installed runtime, not the hardware. WAGO's standard environment offers CANopen, PROFIBUS DP, EtherNet/IP and Modbus but no PROFINET or EtherCAT master; CODESYS Control for PFC200 SL adds PROFINET controller and device plus EtherCAT master, and no EtherCAT slave exists on this controller. The 750-8207's 3G modem has no CODESYS library: use the SMS service or Linux commands and AT commands.

On this page
- Why the fieldbus roles follow the runtime, not the hardware
- Which runtime the controller is actually running
- What CODESYS Control for PFC200 SL adds, and what it leaves out
- Match the exact order number and firmware before an install
- Which fieldbus role fits a servo group leaving CANopen
- Whether the controller keeps up with the servo cycle
- How the 750-8207's 3G modem reaches CODESYS
- Prove the migration before cut-over
- The decision for each case
- Questions asked
The fieldbus roles of a WAGO PFC200 come from the runtime installed on it, not from the hardware family. WAGO's standard environment documents the controller's fieldbus protocols as CANopen, PROFIBUS DP, EtherNet/IP and Modbus TCP/UDP/RTU — PROFINET master and EtherCAT master are not in that list, so servo amplifiers leaving CANopen cannot reach either bus from that environment. The runtime that adds the roles is CODESYS Control for PFC200 SL: its data sheet lists PROFINET controller (master) and PROFINET device (slave) plus EtherCAT master, and EtherCAT slave has no runtime on this controller. On the 750-8207 with the integrated 3G modem, the modem has no CODESYS library; the documented IEC-level access is the SMS service, and the direct route is Linux commands or serial AT commands. Work through the checks below; each one ends in a decision.
Why the fieldbus roles follow the runtime, not the hardware #
Two software layers live on a PFC200 and they do not offer the same fieldbus menu. The engineering PC downloads a project to whichever runtime is installed; that runtime owns the fieldbus stacks, so the bus roles a project can pick are the runtime's roles.
WAGO's own environment lists the controller's connectivity as the CANopen, PROFIBUS DP, EtherNet/IP and Modbus set quoted above. A project inside that environment cannot add a PROFINET controller or an EtherCAT master, on the 750-8207 or on any other PFC200 order number, because the runtime does not carry those stacks. CODESYS Control for PFC200 SL is a separate product: CODESYS documents it as a Linux-based SL runtime executed with specific user rights on the controller, installed beside the WAGO firmware image rather than instead of it.
Decision: when the application needs PROFINET or EtherCAT master, the change is a runtime change. No add-on module, coupler or firmware setting adds those master roles to the standard environment.
Which runtime the controller is actually running #
Identify the installed runtime from how the tooling behaves:
- The project opens in WAGO's engineering environment and its fieldbus tree offers CANopen, PROFIBUS DP, EtherNet/IP or Modbus masters but no PROFINET controller or EtherCAT master entry: the standard runtime is installed. There is nothing to configure — the roles are absent there by design.
- A CODESYS 3.5 IDE scans the controller's IP address and lists it as a device: an SL runtime package is installed. Compare its version against the data sheet, then run the role check below.
- The CODESYS IDE connects but the EtherCAT master or PROFINET controller entry is missing from the device tree: the runtime is present and the product option for that stack is not; the data sheet's product options section states what each option carries.
- No engineering tool reaches the controller: sort out address and network path first, because a runtime question cannot be answered across a link that does not connect.
What CODESYS Control for PFC200 SL adds, and what it leaves out #
The SL data sheet names its fieldbus product options exactly: CODESYS EtherCAT Master, and CODESYS PROFINET Controller / Device. Across the two environments, the role picture is:
| Fieldbus role | Standard WAGO runtime | CODESYS Control for PFC200 SL |
|---|---|---|
| PROFINET controller (master) | not offered | available |
| PROFINET device (slave) | not offered | available |
| EtherCAT master | not offered | available |
| EtherCAT slave | not offered | not available |
Decision: three of these four roles are licensable on this controller under the SL runtime; the fourth, EtherCAT slave, exists nowhere on it, so a topology that needs the PFC200 as a station under another EtherCAT master changes bus or controller.
Match the exact order number and firmware before an install #
The supported-platform list in the SL data sheet names PFC200 variants such as 750-8202 / 750-8212 (PFC200 CS 2ETH RS) and 750-8203. The integrated-modem 750-8207 is decided by the same document: supported when the current data sheet and release notes list that order number at your firmware, unsupported when they do not, and a report that the runtime ran once on an unlisted variant is not a release.
- Read the order number from the controller label and the firmware version from its web-based management page.
- Compare both against the supported-device list in the current CODESYS Control for PFC200 SL data sheet and its release notes.
- Listed: install the runtime package matching that firmware. Absent: do not install — the fieldbus move goes to a listed variant such as the 750-8202, or this controller keeps the standard runtime and the servo group stays on CANopen.
- Unlisted and unavoidable: obtain the release statement for that exact order number and firmware in writing from WAGO or the CODESYS store before a machine design depends on it.
Decision: the list decides per order number and firmware, not per PFC200 family.
Which fieldbus role fits a servo group leaving CANopen #
For servo amplifiers currently on CANopen, EtherCAT master is the natural target on this controller. EtherCAT is a single-master bus, so the PFC200 holds exactly the role the SL product provides; each amplifier needs its EtherCAT interface option and its ESI device description file in the IDE. Choosing PROFINET instead needs the amplifier's PROFINET option and its GSDML file, after which the controller exchanges cyclic I/O with every device by station name and IP address. The EtherCAT-master-with-drives pattern is the same one CODESYS documents on its other runtimes — for example the setup that runs CODESYS SoftMotion on ctrlX OS over EtherCAT — so axis structure and application code port with fewer changes than the bus swap suggests.
Decision: EtherCAT master for the servo group unless the plant standard is PROFINET; PROFINET device operation where another controller owns the ring; EtherCAT slave on this hardware nowhere.
Whether the controller keeps up with the servo cycle #
The power question is a task-load measurement, not a yes-or-no specification:
- Set the fieldbus task's cycle time to what the drives need, not the fastest value the IDE accepts.
- Run the complete application with every axis enabled and read the task's average and maximum execution time in the runtime's online view.
- Keep the bus diagnostics open through the run: lost frames, working-counter errors or dropped devices are the first sign the cycle is too tight.
Worked example with example numbers, not measurements: three servo drives on the EtherCAT master task at a 4 ms cycle, and the online view reports 1.2 ms average and 2.9 ms maximum execution time. The maximum consumes 2.9 ms of the 4 ms cycle, which leaves 1.1 ms per cycle free, or 1.1 / 4 = 27.5 percent of the cycle. With the diagnostics clean, that configuration stands: three drives at this cycle fit. Adding a fourth drive without re-measuring does not stand, because its cyclic data and diagnostic traffic land inside the remaining 1.1 ms. If the measured maximum crowds the cycle after any change, the options are a longer cycle, fewer drives, or motion moved to a controller sized for it — a large interpolated axis group does not belong on this controller class.
Decision: measured maximum execution time against the cycle time settles the fit; this example's three drives pass, and every added drive re-runs the measurement.
How the 750-8207's 3G modem reaches CODESYS #
CODESYS provides no library that drives the PFC200's GSM modem directly. The documented IEC-level path is the SMS service: the CODESYS store publishes its system requirements, and WAGO's firmware release notes for the 750-8x1x series describe SMS method calls and modem status requests passing from a CODESYS IEC application to the modem data service on the 750-8207 — in that path the application calls SMS methods and the service handles the modem.
The direct path is the Linux layer: call Linux commands from the application, or exchange AT commands with the modem over its serial interface, owning the framing, timeouts and error handling yourself. Put every such exchange in a low-priority task separate from the fieldbus cycle — an AT-command read that blocks without a timeout can stall the PLC task, and with it the bus. Test with the SIM in place and under weak signal before the application depends on the link.
Decision: SMS service for IEC-level messaging on the 750-8207; Linux or AT commands, in a low-priority task with timeouts on every read, for raw access.
Prove the migration before cut-over #
Run this sequence with the real drives attached:
- Scan the EtherCAT bus or load the PROFINET device names; every drive reaches its operational state with no working-counter or connection faults.
- Run each axis through enable, a slow move and a stop, with commanded position and actual position agreeing inside the drive's following-error window.
- Pull one drive's connection during operation: the controller flags the loss and the axis group executes the stop configured for that fault.
- Send a test SMS while the fieldbus runs and confirm the fieldbus task's maximum execution time stayed below its cycle.
- Treat an axis that enables but holds still when the setpoint changes as a separate fault with its own diagnostic path, covered step by step in the page on why an EtherCAT CSP stepper axis enables but does not move.
Steps one to four prove the runtime and the bus; a stationary enabled axis after that is a drive-mode or setpoint-format fault, not a reason to revisit the runtime choice.
The decision for each case #
- Standard WAGO runtime installed and PROFINET or EtherCAT master needed: move the application to CODESYS Control for PFC200 SL; nothing inside the standard environment adds those masters.
- Order number and firmware on the SL supported-device list: install the matching package. Not on the list: the bus change moves to a listed variant such as the 750-8202, and this controller keeps the standard runtime.
- Topology that needs the PFC200 as an EtherCAT slave: no runtime on this controller provides it — use PROFINET device operation or change the controller.
- Servo group leaving CANopen: EtherCAT master, one ESI file per drive, cycle time set to the drives' requirement and confirmed by measured execution time.
- Messaging over the 750-8207's 3G modem: the SMS service as the documented IEC path, Linux or AT commands in a low-priority task for raw access.
- Measured maximum execution time crowding the cycle: longer cycle, fewer drives, or a motion-sized controller.
Questions asked
Does CODESYS Control for PFC200 SL replace the WAGO firmware on the controller?
No. The WAGO firmware image stays the base layer: its services, including the web-based management page you read the firmware version from, remain reachable, and firmware recovery runs through WAGO's own tools rather than through CODESYS. CODESYS classifies Control for PFC200 SL among the Linux-based SL runtimes executed with specific user rights, which is why it can install alongside that firmware. Record both version numbers, because the supported-device list is tied to specific firmware.
Which description file does each drive need on the new bus?
An EtherCAT amplifier needs its ESI device description file and a PROFINET device needs its GSDML file, both from the drive manufacturer, and the file generation should match the amplifier's firmware. The file only tells the IDE which cyclic data the device exposes; it does not configure the drive, so set the station name or IP address and the drive's own bus parameters from its manual before the scan.
Can one 750-8207 run the SMS service and a fieldbus master together?
Yes, that pairing is what the documented design supports. The constraint to manage is task time rather than compatibility: keep the messaging work out of the fieldbus task's cycle and prove the pair with a live test message while the bus runs, reading the fieldbus task's maximum execution time afterward. Done that way, a slow mobile network shows up as a late message, never as a bus fault.
What does the PROFINET side need that EtherCAT does not?
Names and addresses. A PROFINET device is reached by station name and IP address, so each amplifier needs those set before the controller's device names resolve; the GSDML file then maps the cyclic data. EtherCAT sorts addressing out during the bus scan in physical order, so the same swap needs no addressing work, only the ESI file and a sensible drive order on the wire.