Explainer
What the RSLogix 5000 to TIA Portal conversion tool covers
Short answer
No import in TIA Portal opens an RSLogix 5000 project. Siemens Migration Studio converts Rockwell controller software to TIA Portal code for the S7-1200 and S7-1500, but only through your regional Siemens contact, and the converted project still needs section-by-section commissioning: tags, UDTs, AOIs and tasks map, communication links do not.

On this page
No function in TIA Portal opens an RSLogix 5000 project file, so a direct import is not the answer; the article on why you cannot import a PLC project into another platform explains why that door is closed in general. The documented route is Siemens Migration Studio, which Siemens describes as converting Rockwell controller software into code usable in TIA Portal on SIMATIC S7-1200 or S7-1500 PLCs. Siemens Industry Online Support entry 109476620 covers sources from Rockwell, Mitsubishi and Schneider, and the conversion runs through your regional Siemens contact rather than as a self-service download. The converted project is a starting point: you commission it section by section, because the tool maps some constructs cleanly and leaves others as handwork.
The route, hop by hop #
The project itself travels in three hops, and each hop has an owner and a check before you move on.
| Hop | Owner | Check before moving on |
|---|---|---|
| Logix project, the source of truth | You | Project opens and verifies with no errors in your current Rockwell software; archive a frozen copy |
| Export handed to Siemens | You and the regional Siemens contact | The contact confirms which source file format they need and which controller features are in scope |
| Converted TIA Portal project | Siemens output, then you | The project opens in TIA Portal and compiles; the converter's warning list becomes your rework list |
Get the contact to state which constructs fall outside the conversion scope before you commit to a schedule. A converter that maps one vendor's instruction set and tag model onto another's produces logic that needs review by design.
What maps and what stays manual #
Every Logix construct without a one-to-one Siemens equivalent becomes a rework item. Build this inventory from the frozen project, then reconcile it against the converter's warnings.
| Logix construct | TIA Portal counterpart | Rework concern |
|---|---|---|
| Controller-scoped and program-scoped tags | Global data blocks, block-local and static variables | Tag-based access becomes block-based; watch scope and naming collisions |
| User-defined data types (UDTs) | PLC data types | Member order and alignment change the layout for any external reader |
| Add-On Instructions (AOIs) | Function blocks with instance data blocks | Per-instance memory and parameter direction (in, out, in/out) |
| Continuous, periodic and event tasks | Cyclic OB1, cyclic interrupt OBs, event OBs | Task priority and watchdog become OB priority and cycle monitoring |
| STRING (a DINT length plus characters) | String (a two-byte header plus characters) | Different memory layout and maximum length; check every string copy and comparison |
| Produced/consumed tags and MSG instructions | Open user communication or PROFINET-based exchange | No direct mapping; redesign the exchange |
If your Logix project leans on UDTs and AOIs for its structure, the object-oriented ControlLogix design with UDTs and AOIs background explains the pattern the converter is translating from, which helps you read its warnings.
The string difference is where offsets bite. In Logix, a string carries a 4-byte DINT length followed by the characters; in Siemens, a string carries a 2-byte header (maximum length, actual length) followed by the characters, with a maximum of 254 characters. Worked example: a Logix STRING[40] occupies 4 + 40 = 44 bytes, while a Siemens String[40] occupies 2 + 40 = 42 bytes. An array of ten such strings differs by 10 × 2 = 20 bytes. So map every string explicitly by name; a raw block copy between the two layouts shifts everything after the first string.
Tasks, timers and data blocks after conversion #
Compile first, then compare behavior. A clean compile proves syntax and type consistency, not that scan-dependent logic works the same.
- Place each former Logix task in an OB with the intended trigger: the continuous task in OB1, periodic tasks in cyclic interrupt OBs with the same interval, event tasks in event OBs.
- Rewrite timer references. Logic that compares a Logix timer's
.ACCmember against a threshold moves to comparing the Siemens timer's elapsed timeETagainst a constant of type TIME. - Review data blocks that use optimized block access. Optimized DBs have no fixed byte offsets, so any external reader that addresses by offset needs standard (non-optimized) access or symbolic access instead.
- Work the converter's warnings one by one against your inventory until the compile shows zero errors and every warning is either fixed or deliberately accepted with a note.
Then check runtime: with the full I/O mapped, the CPU's cycle time monitoring must show the longest cycle well inside the configured watchdog.
The I/O path changes from EtherNet/IP to PROFINET #
Field devices that speak EtherNet/IP do not connect to a Siemens controller as-is, so trace each I/O point from the sensor to the CPU.
- List every I/O module and drive in the Logix I/O tree with its IP address, rack position and connection type.
- Select the replacement for each: Siemens I/O, or a third-party device with a PROFINET GSD file you install in TIA Portal.
- Reuse the copper or fiber run only if the replacement device supports the same medium and speed, and confirm the switch supports the protocol the new device uses.
- Build the hardware in the Devices & networks view, assign a PROFINET device name and IP address to each device, and match them to the physical devices on the network.
- Map the I/O addresses into the converted logic; converted code may reference tag names that no longer resolve, so fix those against the new I/O tags.
The proof is twofold: every device shows reachable in the online diagnostics view with no name or IP conflicts, and each input toggles in a watch table when you actuate the field device by hand.
Controller and HMI links get remapped by hand #
Produced/consumed tags and MSG instructions move data between Logix controllers over CIP, and neither exists on the Siemens side. Rebuild each link from the data direction outward: sender, network hop, receiver.
| Link in the Logix project | Action in TIA Portal |
|---|---|
| Produced/consumed tag between controllers | Define a data block on both ends with identical layout and exchange it cyclically over the plant network |
| MSG read or write to another device | Replace with a communication block matching the partner's protocol; confirm the partner speaks it |
| HMI or SCADA browsing tags by name | Repoint the HMI connection to the S7 controller and re-import the tags; check for renamed or moved tags |
| Third-party device reading raw registers | Check byte order: Siemens data is big-endian and Logix data is little-endian, so multi-byte values can arrive swapped |
For the last row, a DINT with value 16#12345678 leaves a Logix controller as bytes 78 56 34 12 and must be read on the Siemens side in the order 12 34 56 78; if a value looks absurd on the HMI, check the byte swap before anything else. Prove each link by writing a known test value on the sender and confirming value and quality at the receiver and on the HMI for BOOL, INT, DINT, REAL and STRING.
What proves the converted program matches #
Run the original and the converted logic against the same stimulus and compare outputs. Build the test matrix from your inventory: each digital sequence, each analog scaling, each alarm and interlock, each communication link.
- Record the Logix results for every test case: input state, output state, timer durations and scaled analog values.
- Replay the same cases on the TIA Portal program with a watch table on inputs, outputs and intermediate tags. Use force values only on a de-energized or isolated process; forcing I/O on a live machine can drive outputs you did not intend to move.
- Compare timer behavior by measuring elapsed time on a trace, not by reading the preset.
- Cut power to the CPU and restore it; confirm retentive values, startup OB behavior and the outputs' safe state match the original.
- Trip every interlock and every communication path one at a time and compare the response against the recorded Logix results.
The decision for your case #
- A Logix project built from tags, UDTs, AOIs and tasks with little cross-controller communication: hand it to Migration Studio through your regional Siemens contact, then commission the converted project section by section. That is the documented route, and it saves real time over a manual rewrite.
- A project whose value sits in produced/consumed tags, MSG traffic or motion: still convert, for the logic, but budget the communication redesign as handwork from day one, because the tool does not map it.
- A source project that is actually STEP 7 V5.x for an S7-300 or S7-400: you need a different tool altogether; the article on migrating S7-300 projects from STEP 7 V5.5 to TIA Portal covers that path, which you can run yourself without the conversion service.
- Any direction from TIA Portal back to Studio 5000: no equivalent documented converter exists, so plan a manual port.
Questions asked
Does the same conversion service take RSLogix 500 or PLC-5 projects?
The documented offering names Rockwell, Mitsubishi and Schneider as source vendors, and the published description covers Logix-style controller software; it does not list individual Rockwell controller families. Tell the regional Siemens contact the exact source controller and software you own, and treat anything they do not confirm in writing as manual rework.
Is the migration tool inside TIA Portal the same thing?
No. The migration tool you install for TIA Portal converts STEP 7 V5.x projects for S7-300 and S7-400 controllers; it does not open any Rockwell project file. Rockwell sources go through Migration Studio and the regional Siemens contact. If your source is an S7-300 or S7-400 project, you use the other tool and can run the migration yourself.
Is there a converter in the other direction, TIA Portal to Studio 5000?
No equivalent documented service exists from Rockwell for converting TIA Portal projects. That direction is a manual port: you rebuild the hardware configuration, redeclare the tags and data blocks, and rewrite the logic block by block. Budget it as a rewrite, not a conversion, because instruction sets, memory models and task systems differ in both directions.
Can you put a converted program straight into production?
No. A converted project that compiles only proves syntax and type consistency. Scan-order effects, timer behavior, string handling and every communication link must be verified against recorded results from the original program before the machine makes product. Commission the converted logic section by section, with forcing limited to a de-energized or isolated process.