Two different brand VFDs on one Modbus RTU network

Drives and motion Published 6 min read

Short answer

Two different-brand drives can share one Modbus RTU network with an S7-200 SMART ST30 acting as the Modbus client. The requirement is not a common manufacturer: both drives must support RTU on the same electrical interface, accept one common baud, parity and stop-bit combination, keep distinct node addresses, and be polled from their own register maps one transaction at a time.

On this page
  1. Confirm both drives speak RTU on the same interface
  2. Set one common serial format and two distinct addresses
  3. Prove each drive alone before polling both
  4. Build one register map per drive
  5. Serialize transactions on the shared port
  6. Worked example: poll cycle for both drives at 9600 baud 8E1
  7. The decision for each case
  8. Questions asked

Yes: an S7-200 SMART ST30 can control a Siemens V20 and an LS SV008iG5A-4 over one Modbus RTU network, polling each drive as its own separately addressed server. The common requirement is not the manufacturer. Both drives must support Modbus RTU on the same electrical interface, accept one common baud, parity and stop-bit combination, hold distinct node addresses, and be read through their own register maps, one transaction at a time on the shared port.

Modbus RTU standardizes the frames, not the drive. The PLC is the client and issues every request; each drive is a server that replies only when the frame carries its address. That division is why two different brands coexist on one bus easily, and why the PLC program needs one mapping per drive.

Confirm both drives speak RTU on the same interface #

Read the communication section of each drive's manual and the S7-200 SMART Modbus RTU library documentation. A connector that looks like RS-485 is not a protocol capability: check that the V20 offers a selectable Modbus operating mode with documented serial settings, and that the SV008iG5A-4 provides RTU server capability on its installed interface. Some drives put the RS-485 port on an option board; if the board is not fitted, the shared-bus design stops until one is installed.

On the PLC side, confirm you have the Modbus RTU master library available for the ST30 and STEP 7 Micro/WIN SMART. The library supports the standard read and write function codes; anything a drive needs outside those codes cannot run through it.

If either drive lacks RTU on a compatible interface, do not try to fix it with addressing. Add the vendor's communication option or a protocol gateway instead.

Set one common serial format and two distinct addresses #

Addressing selects which server may answer; it does not give any device its own baud rate. Pick one baud, parity and stop-bit combination that the PLC port and both drives all list as supported, and set all three devices to it. Then set the V20 and the iG5A to different node addresses. Duplicate addresses produce overlapping replies, CRC errors and intermittent faults that look like wiring problems.

Wire the bus as one linear trunk with short branches, matching each manual's documented D+ and D- polarity; terminal letters differ between brands, so check the signal names, not the silkscreen. Put termination at the two physical ends of the trunk only, not at every device, and follow each manufacturer's instruction for the signal common and shield. If the bus idles unreliably, add the biasing the manuals call for.

Prove each drive alone before polling both #

A lit communication LED proves nothing by itself. A valid transaction means the intended address replied, the frame passed its cyclic redundancy check, and the data parsed correctly.

  1. Connect only the V20 and issue a documented read request to it. Expect a plausible status or monitored value. If nothing comes back, check protocol mode, node address, framing, polarity and port initialization before questioning register meaning.
  2. Repeat with only the iG5A connected, using its own documented request and address. Do not reuse the V20's register address unless the LS map explicitly assigns the same meaning.
  3. Read the transaction result codes. Valid data, a reported failure, or a Modbus exception each point somewhere different: an exception means the server decoded the request but rejected the function or address, which calls for a map check, not a rewiring.
  4. Record the working settings and requests for each drive. That record is the baseline for the combined test.

For a second drive that times out on the combined bus but answers alone, suspect duplicate addressing, missing end termination, an overlong branch or a broken common; these are the same failure modes you would chase on any shared serial port.

Build one register map per drive #

Modbus standardizes transactions, not a drive control word, speed scale or status layout, so the two drives need separate mappings even with identical serial settings.

Mapping item Check on each drive Result of copying across brands
Function and address Supported read or write operation, and the addressing convention the PLC library expects Exception response, or valid-looking data from the wrong location
Speed reference Units, scaling, valid range, data format Requested speed silently applied wrong
Run command Required command bits and start/stop sequence No start, wrong direction, improper stop
Status feedback Ready, running, fault and reference-read meaning Broken interlocks or false alarms
Command authority Remote control and remote reference selection bits Registers change while the drive keeps following local commands

One recurring trap: some manuals print human-readable register numbers, others print protocol offsets, and the difference shifts every address. Compare each manual's convention against the library's address input before believing a successful read. A wrong offset often returns plausible data, so a clean transaction is not commissioning evidence on its own. The run-bit and sequencing details matter enough that they deserve their own check, as covered in the article on why a VFD ignores Modbus RTU start commands from a PLC.

Serialize transactions on the shared port #

One RS-485 port runs one transaction at a time. Write a scheduler that initializes the port, selects one request, waits for completion or timeout, processes the result, and only then issues the next request. Overlapping requests corrupt response ownership and confuse the library. The article on polling many Modbus RTU slaves with one queued function block shows one structure that does this, and the article on Modbus RTU drive polling on one serial port explains what the cycle time costs.

Worked example: poll cycle for both drives at 9600 baud 8E1 #

Inputs: bus at 9600 baud, 8 data bits, even parity, 1 stop bit (a combination both the V20 and iG5A documents list); one read of one holding register per drive per cycle; assumed drive response delay of 20 ms each, a typical RTU drive figure you should replace with each manual's stated response time. RTU framing adds 1 start bit per byte, so a byte is 11 bits, and the inter-frame gap is 3.5 character times.

Rule in words: transaction time equals frame bits divided by bit rate, plus the gap, plus the drive's response delay.

Arithmetic: a one-register read request is 8 bytes and its response is 7 bytes, so 15 bytes times 11 bits per byte equals 165 bits. At 9600 bit/s that is 165 divided by 9600, about 17.2 ms. The gap is 3.5 characters times 11 bits, or 38.5 bits, about 4.0 ms. Per drive: 17.2 plus 4.0 plus the 20 ms response delay, about 41 ms. Two drives, one after the other: about 82 ms per full poll cycle.

Result and decision: the two-drive cycle lands near 100 ms at 9600 baud. That is fine for status monitoring and speed reference updates; it is not enough for a fast torque or positioning loop, which should run on hardwired analog or pulse references. Moving the bus to 19200 baud roughly halves the 21 ms of framing per transaction, leaving the drive response delay as the dominant term, so doubling baud buys less than half the cycle time once responses dominate.

The decision for each case #

Both drives RTU-capable on RS-485 with a common serial format: share the bus, assign distinct addresses, keep two register maps, serialize the polling, and expect roughly one 100 ms cycle for two drives at 9600 baud. A drive without RTU or with an unfitted option board: install the vendor's option or use a protocol gateway, because no address or framing choice repairs a missing protocol. Serial settings that cannot overlap: still shareable only through a gateway that converts between the two formats; otherwise give the odd drive its own port.

Questions asked

Can two different brand drives share the same Modbus RTU bus wires?

Yes, provided both drives expose an RS-485 port with Modbus RTU server capability, one baud, parity and stop-bit combination is supported by the PLC and both drives, and their node addresses differ. The bus carries frames addressed to each server; the brand is irrelevant as long as the electrical interface and framing match. Each drive still needs its own register map in the PLC program.

What happens if both drives are set to the same Modbus address?

Both servers try to answer the same request on the same wires. The overlapping drive currents corrupt the frames, so the client sees CRC errors or timeouts that appear and disappear with load and wiring. No software change fixes it while the addresses collide. Set each drive to a distinct address in the range its own manual allows before any other troubleshooting.

Why does one drive run fine from the PLC but the other times out?

Test the second drive alone on a short connection first. If it answers alone, the drive itself works and the shared-bus problem is usually duplicate addressing, missing termination at the far end, a branch that is too long, or a broken signal common between cabinets. If it does not answer alone, fix protocol mode, node address, framing and polarity before touching the bus.

How many transactions per second can one Modbus RTU port handle?

It depends on baud rate, frame length and each drive's response delay. At 9600 baud with short read frames, one transaction takes roughly 40 to 60 ms including drive response time, so two drives poll in about 80 to 120 ms. Faster baud rates and single-register reads shrink that. Plan the poll cycle around the slowest control loop that actually needs drive data.

Does Modbus define a standard run command and speed scaling for drives?

No. Modbus standardizes the transaction format only. Run bits, speed units and scaling, and status layouts come from each drive's own register map. A register address that works on one drive is meaningless on the other, and copying a control word between maps can stop, reverse or trip a drive. Build one mapping per drive from its own manual.

Keep reading

  • How-to

    How to commission five VFD drives on one Modbus gateway

    Prove the link in three passes: open the Modbus TCP connection to the gateway, verify one read from one drive against its own display, then run one serial transaction at a time across all five. A TCP-to-RTU gateway must serialize every RS-485 request, so schedule run commands ahead of power reads instead of polling all five at once.

    Drives and motion

  • How-to

    Configuring S7-300 PROFIBUS control for an MM420 drive

    Hardware configuration alone moves no drive data. An S7-300 reads and writes an MM420's cyclic PROFIBUS area with SFC14 and SFC15 whenever the consistent area is too large for direct access, maps every control-word and status-word bit to the configured telegram, and switches the drive's command and setpoint sources to the fieldbus before the first enable. Judge drive readiness from the status word, not from a completed bus transfer.

    Drives and motion

  • How-to

    Connect an S7-300 to a DCM drive over PROFIBUS or PROFINET

    Yes: an S7-300 controls a DCM over PROFIBUS or PROFINET by installing the drive's GSD or GSDML description, selecting the same supported telegram on both sides — standard telegram 1 (PZD-2/2) is the safe first choice — exchanging the 4-byte records with SFC14 and SFC15, and trusting the link only once cyclic exchange runs fault-free. A clean link still will not move the motor while the drive's command source is local or an enable is missing.

    Drives and motion