Troubleshooting P1Exx fieldbus communication failure on a PSTX
Short answer
P1Exx is a watchdog trip: the PSTX received no valid telegram for longer than the fieldbus failure timeout in parameter 19.12, so a reset clears the latch but not the fault. Check the plug type and the Fieldbus Type parameter first, then address and baud, then a 60 Ω power-off termination check, then the master side.
On this page
- What does P1Exx mean on a PSTX softstarter?
- Why does P1Exx come straight back after a reset?
- Which plug and parameter checks come before anything else?
- What network settings must match the master?
- How do I measure bus termination with a multimeter?
- How do I tell a silent master from a wiring fault?
- When is the plug or the module itself the faulty part?
- Questions asked
P1Exx – Fieldbus Communication Failure on a PSTX softstarter is a watchdog trip, not a motor or power fault: the starter went longer than the fieldbus failure timeout in parameter 19.12 without a valid telegram from the master and tripped to prevent uncontrolled operation. A reset clears the latch, never the cause, so the fault returns at the next timeout while the link stays down. Work the tree in the order below — plug type and Fieldbus Type parameter first, address and baud next, then the power-off termination measurement, then the master side — because the first checks catch most commissioning-time trips and need nothing but eyes.
What does P1Exx mean on a PSTX softstarter? #
It means the softstarter received no valid fieldbus telegram for longer than the timeout configured in parameter 19.12, so it tripped to prevent uncontrolled motor operation; no thermal or current limit was exceeded. Nothing in the fault accuses the power section or the motor.
The PSTX exchanges control commands and status words with the master continuously and watches the link while it does. What decides the trip is the gap since the last valid telegram measured against parameter 19.12. Read the full event code from the display or the event list, not just the P1Exx pattern, and read the configured timeout value out of parameter 19.12 on the device before judging anything else. Parameter 19.4 (Fieldbus failure op) sets what the starter does the moment that timeout expires.
Silence arrives in two patterns, and they point differently:
- Constant, from power-up or after a module change. The master is stopped or offline, the plug is unseated or the wrong type, the Fieldbus Type parameter does not match the installed plug, the cable is open, or the module has lost its supply. The trip appears at the first timeout after the link drops.
- Intermittent, at random intervals. Marginal connectors, missing termination or coupled noise drop telegrams in bursts, and only a burst longer than the timeout trips the unit.
Why does P1Exx come straight back after a reset? #
Because the reset only clears the latched trip while the link stays down: with the master still silent, the timeout in parameter 19.12 expires again and the same fault returns, which is the expected signature of unrestored communication. Chasing resets wastes the time the fault tree below needs.
Four fixes get tried first, and each fails for a specific reason:
- Repeated fault resets. A reset clears the latch; it does not restore a single telegram. Reappearance after reset is expected behavior, not a new fault.
- Restarting the PLC and the starter immediately. A restart belongs after the cause is corrected, because it can mask an intermittent cable or termination defect for a few minutes and send you away before the real fault shows again.
- Swapping the Fieldbus Plug on suspicion. The plug is one of a dozen candidates. A wrong plug type, a wrong Fieldbus Type setting or a stopped master produce the same trip with a perfectly healthy plug.
- Running the motor locally from the keypad. Local control can still work with the link down, which proves the power and control sections are alive — useful knowledge, but the PLC still cannot start the motor.
Which plug and parameter checks come before anything else? #
Seat and screw down the Fieldbus Plug on the Fieldbus Plug Adapter (FBPA), confirm the plug is the correct type for your protocol, and confirm the Fieldbus Type parameter names that same protocol — all three checks need no instruments and catch the commissioning-time trips. They are the cheapest place a P1Exx ends.
The PSTX speaks Modbus RTU on its built-in electronics; the other protocols — PROFIBUS DP, PROFINET, Modbus TCP, DeviceNet and EtherNet/IP — each come from an optional plug module, one plug per protocol, so a network built for one protocol will not run on another's plug. Use the manufacturer's plug modules rather than substitutes.
The installation manual's first instruction for this fault is to make sure the fieldbus plug is connected correctly: seated on the Fieldbus Plug Adapter (FBPA), in the correct position, with the screw tightened. Check the plug label against the Fieldbus Type parameter next. A mismatch leaves the module powered but unable to exchange valid telegrams, and the starter trips one timeout later — a fault that looks like wiring and is not.
A visibly damaged connector, or a plug that still fails with type and parameter verified, is a replacement candidate. Hold that decision until the later checks close the rest of the tree.
What network settings must match the master? #
On the bus-type protocols the node address must be unique and match the master's configuration, and the baud rate must match the rest of the segment; on Ethernet-based protocols check the address assignment the master expects instead, since baud and termination checks do not apply. Split the work accordingly:
- PROFIBUS DP, Modbus RTU, DeviceNet: verify the node address is unique on the network and matches what the master is configured to talk to; verify baud rate and protocol settings against the network; check termination at both physical ends of the segment.
- PROFINET, Modbus TCP, EtherNet/IP: verify the network configuration the master expects for this device, including how the address is assigned. Confirm the physical link and the device's presence in the master's network diagnostics.
On EtherNet/IP, the adapter-side settings that let a Logix master see the starter are walked through in Set up a PSTX softstarter on EtherNet/IP with a ControlLogix. On Modbus RTU, remember the starter is the slave: its address is set on the starter, and the master must poll that exact address.
How do I measure bus termination with a multimeter? #
Power the segment down, then measure resistance across the signal pair: a correctly double-terminated PROFIBUS DP segment reads about 60 Ω, because its two 120 Ω terminators sit in parallel. That single number tells you whether both ends are terminated.
One safety note: an ohms reading is only valid and only safe with the bus powered down, so isolate the segment supply before probing. The IEC 61158-2 RS-485 physical layer used by PROFIBUS DP requires a 120 Ω terminator at each physical end of the segment, and the arithmetic for the parallel pair is:
R = (120 Ω × 120 Ω) ÷ (120 Ω + 120 Ω) = 14 400 ÷ 240 = 60 Ω
| Power-off reading across the pair | What it means | Decision |
|---|---|---|
| ≈ 60 Ω | both end terminators present | termination healthy; move to cable and master checks |
| ≈ 120 Ω | one terminator missing | fit the terminator at the open end, then re-measure |
| ≈ 40 Ω or lower | an extra terminator mid-segment: 120 Ω ÷ 3 = 40 Ω | remove it; only the two physical ends terminate |
Missing or doubled termination rounds the signal edges and drops telegrams mostly under load or in electrical noise — exactly the intermittent P1Exx pattern. For Modbus RTU and DeviceNet segments, measure against the termination value stated in that fieldbus's own specification; the method is identical.
How do I tell a silent master from a wiring fault? #
Let the master's own diagnostics decide it: if the PLC logs a communication timeout and shows the softstarter offline, work the master side and the path between before replacing parts at the starter; if the master reports nothing, start at the plug. One look at each controller's diagnostics splits the tree.
| Observation | Points to | First check |
|---|---|---|
| Fault at first power-up or after a module change | Wrong plug, wrong Fieldbus Type, wrong address or baud | Plug label against parameter and master configuration |
| Communication status LED shows a fault | Link-level fault at the plug or module | Plug seating, module supply, cable continuity |
| Master logs a timeout, device offline in diagnostics | Master stopped or the path between is broken | Master run state, then cable continuity |
| Losses at random intervals | Loose connector, missing termination, noise | Connector inspection, the 60 Ω check, cable routing and shielding |
| Fault returns immediately after reset | Link not restored | The full sequence again, not another reset |
| Keypad works, PLC cannot start the motor | Fieldbus path only | The whole path from master to plug |
Measure the fieldbus module supply at the module and confirm it sits within its rated operating voltage; a module that browns out drops the link and raises the same trip. Restart the PLC and the softstarter after the cause is corrected, never as the diagnostic. A Modbus RTU master that gets no answer at all usually has an addressing or serial-setting problem of its own, the failure shape traced in Why a CJ2M Modbus RTU master gets no answer from an S7-1200.
When is the plug or the module itself the faulty part? #
Only after the plug type matches, the Fieldbus Type parameter agrees, the cable and termination measure correct and the master provably transmits: then a damaged connector or a failed plug is the candidate, and an internal communication module fault is the last resort. Replacing parts before that point buys another timeout, not a fix.
Suspect the internal communication module only when a control-circuit or internal communication fault is logged alongside P1Exx and every external check above has passed; until then the evidence points outward, at plug, cable, configuration or master.
P16xx and P17xx entries in the same event list are supply events, not fieldbus diagnostics. An overvoltage-at-startup trip has its own cause set, worked through for PSTX P16xx overvoltage at startup. Undervoltage at startup is likewise its own fault, with its own path for PSTX P17xx undervoltage at startup. Treat them separately: sharing the event list with P1Exx does not link them causally.
Questions asked
Does a P1Exx trip damage the softstarter or the motor?
No. P1Exx is a communication watchdog trip: no thermal or current limit was exceeded, and repeated trips do not degrade the power section. Each trip is still an unplanned stop for the process, and the motor cannot be started from the PLC while the link is down, so find and fix the silent link instead of cycling resets. Read the rest of the event list before restarting.
Can I run the motor from the keypad while the link is down?
Yes, for diagnosis. Local keypad control can still work while the fieldbus link is down, which proves the power and control sections are alive and points the fault squarely at the fieldbus path. Use it to confirm the starter itself, then restore the link before handing the machine back, because the PLC cannot start or stop the motor until communication returns.
Where is the fieldbus timeout set, and how long should it be?
The timeout lives in parameter 19.12, the fieldbus failure time. Read its current value on the device rather than assuming a default. Size it comfortably above the master's slowest update interval: a timeout only a cycle or two longer than the update interval will trip on a single missed telegram, while a very long one delays the protective stop. Fix a silent master; do not stretch the timeout to hide one.
Do PROFINET, Modbus TCP and EtherNet/IP need termination resistors?
No. Termination resistors belong to the bus-type physical layers: PROFIBUS DP, Modbus RTU on RS-485 and DeviceNet. On the Ethernet-based protocols, spend the time on the cable and connectors instead: confirm the link LEDs at both ends, check that the device appears in the master's network diagnostics, and rule out a duplicate address before suspecting the plug.
Can I stop the softstarter from tripping on fieldbus loss?
Parameter 19.4, Fieldbus failure op, selects what the PSTX does when the timeout in parameter 19.12 expires, and it can be set to Off, which stops the trip from being raised. That is a commissioning convenience, not a repair: with it off, a dead link no longer produces a protective stop. Leave the failure operation active in production and repair the link instead.