Troubleshoot CC-Link inputs working but no digital outputs
Short answer
Working inputs with dead outputs on a Version 1 remote device station are an RY mapping fault, not a broken link. Three occupied stations give RY offsets 00–5F — 96 bits at Y1000–Y105F — and the digital-output channels sit where the head station's output process image puts them, not where the inputs suggest. Set the master's rack entry to 32 points, confirm RY refreshes to Y1000, read the output image table, then trace one bit.
On this page
Inputs arriving in the Q03 CPU with no error LED on either CC-Link station mean the cable, the baud rate and the RX refresh path are good. Digital outputs that never register at the remote device on top of that are a mapping fault in the output path, and two numbers usually decide it. A Version 1 remote device station occupying 3 stations receives 96 RY bits spanning offsets 00–5F, not 00–4F, and its output image is filled from the installed module order, not from the input layout. Correct the master's rack entry to 32 points, confirm RY refreshes to Y1000, read the head station's output process-image table, then trace one bit from the CPU to the terminal.
What working inputs prove — and what they do not #
Healthy input data and normal status indicators prove the data link is cyclic and the RX refresh assignment works. They prove nothing about the output path, because CC-Link assigns the input image and the output image independently.
Writing Y1000 and seeing the value appear in the master's buffer memory proves exactly one more thing: the CPU-to-master auto refresh of that single bit. It does not prove that offset 00 of the remote output image belongs to a digital-output channel. Outputs that stay off while inputs flow are the same one-direction pattern as IO-Link hub outputs that stay off despite a valid process image: the transport works and the address does not.
Correct the master module rack entry #
The master appears in the configuration twice, and both entries must be right before the output path can work. In the PLC parameter I/O assignment, set the QJ61BT11N as:
- An intelligent function module.
- Start I/O 00D0, identical to the start I/O entered in the CC-Link network parameters.
- 32 occupied points, not 128. These 32 points size the module's own presence in the rack image; remote I/O capacity comes from the station allocation, never from this entry.
Correcting this entry alone rarely restores outputs, because the rack entry governs CPU access to the module, not the remote mapping. Set it to 32 points and continue down the path.
Verify the auto-refresh assignment #
Open the CC-Link network parameters and read the effective refresh assignment rather than the intended one. The master module's documentation specifies device Y for the RY refresh parameter; an M or L in that position is a configuration fault, so remote outputs belong on Y devices. Check four lines:
- RX refreshing from X1000 — proven working by the arriving inputs.
- RY refreshing from Y1000, with the assignment long enough to cover all 96 bits of a 3-station device.
- RWr from D500, carrying the 12 analog input channels.
- The second word range beginning at D600 — confirm whether it is RWw, the remote-write words. Recording RWr twice is a common transcription error. It affects word outputs, not the digital outputs under test, which travel in RY.
Then open the remote-device-to-refresh mapping display in GX Works2 and read the table it generates for the configured stations. That generated table, not the quick-start example, is the record of which local device carries which remote offset.
How Version 1 fills the remote image #
CC-Link Version 1 mode grants every occupied station 32 RX bits and 32 RY bits, and a remote device station a further 4 RWr and 4 RWw words per occupied station. Because X and Y devices number in hexadecimal, each 32-bit block spans 20 hex and the next occupied station begins 20 hex higher. A remote device occupying 3 stations from Y1000 lays out like this:
| Occupied station | RY offsets | Local devices |
|---|---|---|
| First | 00–1F | Y1000–Y101F |
| Second | 20–3F | Y1020–Y103F |
| Third | 40–5F | Y1040–Y105F |
The occupied-station count is right for this module set: the 12 analog channels need 12 RWr words, and 3 stations supply exactly 3 × 4 = 12. The fault is not the station count.
The head station then maps its installed slices into that span, and it fills the input image and the output image separately, in module order. Thirty-two inputs observed at 00–1F say nothing about where the 8 output points sit; only the output process-image table generated for the actual module order says that. The same documentation defines the system and initialization area inside the span, and that initialization must have run before outputs respond. An FX3U CC-Link remote station setup walkthrough with this head station family shows the configuration end to end.
Worked example: the 3-station STL-BT1 with RY at Y1000 #
Inputs, with the source of each:
- Occupied stations: 3 — the recorded station configuration, a Version 1 remote device station.
- RY bits per occupied station: 32 — the Version 1 allocation rule.
- RY refresh base: Y1000 — the auto-refresh parameter.
- Digital inputs observed: 32 points at remote offsets 00–1F.
- Digital-output module: 8 points, one installed slice.
- Bits commanded during the failed test: Y1000 through Y104F.
Rule in words: the total RY allocation equals occupied stations multiplied by 32 bits; the last offset is that total minus one, written in hex; and each local device equals the RY base plus the remote offset, added in hex.
The arithmetic:
- 3 × 32 = 96 bits.
- 96 − 1 = 95 = 5F hex, so the span runs 00–5F and lands on Y1000–Y105F.
- The failed test reached Y104F, which covers 4F − 00 + 1 = 50 hex = 80 bits.
- Untested by that sweep: 96 − 80 = 16 bits, Y1050–Y105F.
Result: the station owns 96 output bits, and the sweep stopped 16 bits short, inside the third occupied station's block.
Decision:
- Any output test on a 3-station Version 1 device must run through Y105F; a sweep ending at Y104F is incomplete by definition.
- Before sweeping again, read the printed DO offset from the head station's output process-image table and command Y1000 plus that offset. If the table places the 8 output points at 50–5F, the earlier sweep never touched them.
- If the table places them inside 00–4F and the traced bit still dies between the master's buffer memory and the output LED, the fault is on the remote side: installed slice order differs from the configured layout, or the head station's initialization never completed. Fix the layout or finish the initialization, then trace again.
Trace one bit through the output path #
Sweeping a range cannot show which boundary failed; one traced channel can. Work the same layer-by-layer method used to trace an HMI command that never reaches the PLC output:
- Choose one digital-output channel and compute its device as Y1000 plus the offset printed for that channel in the head station's output process-image table.
- Turn the device on and watch it across several scans. If it will not stay on, stop: a duplicate coil, a reset, a block move or initialization logic is overwriting it in the PLC program.
- Confirm the same bit in the master module's buffer memory. Device on, buffer bit off: the auto-refresh assignment is wrong — correct the CC-Link parameters.
- Confirm the bit at the remote station on the module's output LED or its output-image diagnostic. Buffer bit on, remote bit off: the fault sits between master and remote — station allocation, slice order, output enable or unfinished initialization.
- LED on but the load dead: leave the network parameters alone and troubleshoot the field side — output supply, common wiring and the load circuit, measured at the terminal.
Forcing output bits can start machinery, so do it only with the machine in a safe state or the field supply isolated, and release the force before resuming operation. For faults that land on step 4 or 5, a troubleshooting walkthrough for CC-Link faults on STL-BT1 slaves covers the head-station side in detail.
The settings that must match #
The resolved configuration, in one list:
- Rack entry: intelligent module, start I/O 00D0, 32 occupied points.
- CC-Link network start I/O: 00D0, matching the rack entry.
- Auto refresh: RX from X1000, RY from Y1000 covering 96 bits, RWr from D500, RWw confirmed against the D600 range.
- Remote station: Version 1 remote device station, 3 occupied stations, RY span 00–5F.
- Digital outputs: the device equal to Y1000 plus the DO offset printed in the head station's output process-image table, tested through Y105F.
Questions asked
Why do my 32 inputs appear at X1000 to X101F?
Version 1 grants 32 bits per occupied station, and X and Y devices number in hexadecimal, so 32 points exactly fill offsets 00–1F and the next block starts at X1020. The 12 analog channels do not use this bit image at all; they arrive as RWr words from D500 onward.
Are 3 occupied stations correct for 32 DI, 8 DO and 12 AI?
Yes. The 12 analog channels need 12 RWr words, and 3 stations supply exactly 3 times 4, or 12 words; 2 stations would supply only 8. The 40 bit channels fit easily inside the 96-bit span. Keep the count at 3 and look elsewhere for the fault.
Y1000 changes show in the master buffer memory, so why do no outputs switch?
That observation proves only the CPU-to-master refresh of that one bit. The remote station applies only the RY offsets its own output process image assigns to output channels, so a bit can refresh correctly and still command nothing. Take the DO offset from the head station's output table and trace that device instead.
Do remote outputs have to refresh to Y devices?
The master module's documentation specifies device Y for the RY refresh parameter, so with this master remote outputs belong on Y devices — Y1000 here. Inputs may sit on X devices and word data in data registers, but an M or L entry on the RY line is a configuration fault before any mapping question.
Which Y device drives the first digital output?
Take the DO slice's remote offset from the head station's output process-image table and add it to the RY base in hexadecimal. A slice mapped at offset 20 hex, where the second occupied station's block begins, lands on Y1020. Never assume offset 00 just because the inputs start there.