Earlier articles
How-to
Latch two level inputs for pump start and stop control
Use one reset-dominant latch: set the pump when the low level probe reads dry and reset it when the high probe reads wet, so the pump holds its state between the probes. A rung that only compares the inputs drops out the moment water covers the low probe; the latch turns the probe spacing into hysteresis.
How-to
How to build ladder logic practice projects in STEP 7
Get STEP 7 ladder practice projects from the vendor's own support portal and from the samples the installer already placed on your PC, not from a copy of a book's bundled disk. Then rebuild three circuits yourself: a start/stop latch with overload interlock, an on-delay timer sequence, and an up/down counter.