IMDHMIControls LibraryShop main store

Selection guide

Thermal flow element or wind sensor for a PLC wind input

Controllers and I/O Published 7 min read By IMDHMI controls team

Short answer

The FS701L195 is a sensing element, not a wind-speed transmitter: it needs external excitation, bridge conditioning and open-air calibration before any PLC can read it. Specify an outdoor instrument with a documented 0-10 V, 4-20 mA or 24 VDC pulse output and a stated icing rating, then prove the PLC analog input endpoints against the transmitter span.

On this page
  1. The FS701L195 is a sensing element, not a transmitter
  2. What the IEC 61400 series expects of a wind instrument
  3. The four candidates compared
  4. Matching the trip point on a 0 to 100 km/h current loop
  5. Analog, pulse or bus: choosing the signal
  6. Wiring, power and icing monitoring on the mast
  7. The decision
  8. Questions asked

Specify an outdoor wind instrument, not a bare sensing element. The FS701L195 part named for this application is a thermal element: a resistor whose value shifts with airflow. It has no excitation, no bridge, no linearization and no output stage, so it cannot feed a PLC analog input as delivered. Choose instead an instrument with a documented 0-10 V, 4-20 mA or 24 VDC pulse output, a stated outdoor operating range and published icing provisions, then prove the analog input's endpoint readings against the transmitter span before trusting the trip logic. This article compares the four candidate approaches, works the trip-point arithmetic for a current loop on the tower, and ends with the decision for each case.

The FS701L195 is a sensing element, not a transmitter #

A constant-temperature thermal anemometer holds a heated element a fixed amount above the air temperature. Moving air carries heat away, and the electronics measure the electrical effort needed to hold that temperature difference. The result is not a wind-speed voltage: the relationship between heat loss and air velocity is non-linear and shifts with air temperature and density, so every assembly needs its own calibration against a reference measurement.

The element datasheet includes an example circuit, and building it is a legitimate bench exercise. What that circuit does not give you: a stable regulated bridge, temperature compensation, linearization across the wind range, an output stage your analog input can accept, and, critically for a mast that must lower itself in freezing weather, demonstrated behavior under ice, water film and contamination. Heating the element by itself is not an icing rating for an instrument.

The decision is simple: treat the bare element as a laboratory part. It goes on the mast only if you are prepared to build, calibrate and environmentally validate a complete instrument, and that is engineering work the packaged alternatives already include.

What the IEC 61400 series expects of a wind instrument #

The IEC 61400 series is the standards family the wind industry uses for turbine measurement and safety. Its measurement part, IEC 61400-12-1, sets the benchmark worth borrowing for any wind-speed installation: the anemometer is calibrated, its measurement uncertainty is documented, and it is mounted so the mast and nearby structure distort the airflow as little as possible.

Borrow those requirements for the lighting tower. The candidate instrument should carry a published calibration, a stated operating range that covers outdoor freezing conditions, and a mounting position clear of the mast's own wake. An interface that merely produces a voltage fails that test before any wiring starts, because the measurement behind the voltage is what the trip logic depends on.

The four candidates compared #

Candidate PLC interface What decides it Verdict for the mast
Bare thermal element such as the FS701L195 None as delivered; needs external excitation, bridge and output circuitry Calibration, direction sensitivity, weather and icing validation of the whole assembly Reject: you would be designing and validating an instrument, not wiring a sensor
Packaged thermal air-velocity transmitter Documented 0-10 V, current-loop or bus output Most are built for a pipe or duct with a developed flow profile Only if the manufacturer explicitly supports open-air installation
Heated cup anemometer 0-10 V, 4-20 mA or 24 VDC pulse output, depending on model Heater performance and bearing operation under the site's weather Strong choice: proven outdoor wind measurement plus a heater against icing
Heated sonic anemometer Analog or bus output, depending on the instrument Outdoor and icing rating, heater supply, mounting geometry Valid, but reserve it when response time or wind direction data justify the extra supply and integration work

Matching the trip point on a 0 to 100 km/h current loop #

The inputs, and where each comes from:

  • Trip setpoint: 80 km/h, the speed at which the tower must lower its mast.
  • Transmitter span: 0 to 100 km/h, chosen to match the tower's rated maximum, so the span covers every wind the tower is rated for.
  • Loop signal: 4 to 20 mA, with 4 mA as the live zero and a 16 mA span.

The rule in words: for a linear transmitter, loop current equals the live zero plus the measured speed divided by the span, multiplied by the span current.

The arithmetic:

  • 80 km/h divided by 100 km/h = 0.80 of span
  • 0.80 multiplied by 16 mA = 12.8 mA
  • 4 mA + 12.8 mA = 16.8 mA

Result: at the trip speed the loop carries 16.8 mA, measured at the input terminals.

The decision this leads to: at commissioning, prove the endpoints before the setpoint. With the loop connected and the range configured per the Modicon X80 analog input/output module user manual for your exact module, confirm the calm-air trim gives 4 mA at the terminals and the raw value the manual assigns to the low end of the configured range, confirm the top of span gives the loop's full-scale current and the matching high raw value, and only then enter the trip setpoint as a compare in engineering units. A loop current inside the module's documented fault band, or a raw value pinned at the low endpoint while the sensor is visibly turning in wind, means a wiring fault rather than calm weather. That distinction is the reason a live-zero loop earns its place in a fail-to-descend application.

Analog, pulse or bus: choosing the signal #

A 0-10 V instrument is the simplest to wire and works well when the transmitter and the input share a clean signal reference over a short run. Its weakness on a mast is a near-zero reading, which can mean either calm air or a broken conductor. If the same cabinet also holds 0-10 V drive outputs, the shared-reference rules in Wiring 0-10 V sensor and drive outputs to one analog common apply to this circuit too.

A current loop is the better pick for the mast drop because current is unaffected by cable voltage drop and the live zero exposes wiring faults. How the module turns that current into raw counts is the subject of how PLC analog input and output modules convert signals, and the scaling you enter in the program must match the configured range, not a value quoted for a different module.

A pulse output is common on cup sensors and costs little. The conversion in the PLC is pulses per second multiplied by the manufacturer's constant when the transfer is linear, otherwise the documented transfer function. Before choosing an ordinary digital input, check the sensor's maximum output frequency and minimum pulse width: a plain input sampled by the scan can miss pulses at high wind, and a high-speed counter input avoids that. The counting behavior behind this choice is covered in why a PLC misses short input pulses.

A Modbus or Ethernet instrument avoids analog scaling entirely, but the protocol name does not establish compatibility. Check the interface and data documentation for your controller role, select the wind-speed data rather than an accumulated flow total, and confirm what the PLC sees on communication loss so the trip logic fails toward lowering the mast.

Wiring, power and icing monitoring on the mast #

Wire from the selected transmitter's diagram together with the input module's terminal diagram. The existing cup sensor's 24 VDC supply and 0-10 V output describe the old device, not the replacement: confirm the new transmitter's supply requirement, its sink or source arrangement, and its terminal list before cutting cable. Terminate the shield where both documents say to terminate it.

For icing, the heated cup's heater is a real electrical load: size its supply for it and monitor it so a failed heater becomes an alarm rather than a silent iced sensor. If you stay with an unheated instrument, add one temperature input at the sensor: when the case tracks the ambient temperature below 0 °C while a wind reading persists, assume icing, alarm it, and command the descend after a timeout. That second channel costs one analog input and is the cheapest honest mitigation. One safety note belongs here: if the automatic descend protects people from a mast failure, treat the sensor, the input and the trip logic as one machine function and validate it end to end, because a rating on the sensor alone is not validation.

The decision #

  • For the tower as described: specify a heated cup anemometer with a published outdoor and icing rating and a current-loop output matched to the module's current range; keep a pulse-output cup as the alternate only after checking the counter input against the sensor's maximum frequency and pulse width.
  • If the bare thermal element stays on the table: it is a bench experiment. Bridge, regulation, calibration and icing validation are all on you, and none of it is delivered by the element.
  • If a duct-style thermal transmitter is offered: accept it only with the manufacturer's explicit support for open-air mounting, otherwise the flow-profile assumption behind its calibration invalidates the reading above a mast.
  • If the budget allows a heated sonic: it is a valid instrument, not a requirement, for a single-axis speed trip.
  • In every case: endpoint-verify the analog input against the transmitter span, and enter the trip setpoint in engineering units only after the endpoints agree.

Questions asked

Can I build the bridge circuit for a bare thermal element myself?

The element datasheet shows an example circuit, so the electronics are buildable on a bench. What you take on is everything else: stable regulation, temperature compensation, linearization across the wind range, an output the analog input accepts, and calibration of the whole assembly against a reference air-velocity measurement. Test the finished assembly across the airflow range before believing any scaling you enter, and accept that ice and contamination validation is still on you. A packaged transmitter delivers that work already done.

Why is 4-20 mA preferred over 0-10 V on a tall mast?

A voltage signal drops across the cable's own resistance, and the error grows with cable length, so the value at the module can sit below the value at the transmitter. A current loop is immune to that drop because the same current flows through the whole circuit. The 4 mA live zero also separates calm weather from a broken or shorted loop, which a near-zero voltage reading cannot do on its own.

What raw value will my analog input module show at full scale?

It depends on the module and the range you configure, and every range has its own raw-value limits. Read them from the user manual for the exact module and range, not from a number quoted in a discussion thread. The endpoint check at commissioning is what proves your specific configuration: trim the loop to its live zero and to the top of span and confirm the terminal measurements and the raw values both agree with the manual's table.

Keep reading

  • Selection guide

    How to Select PLC Inputs and Outputs From an I/O List

    Build the I/O list from the field devices, not the PLC catalog: classify every point as DI, DO, AI or AO, match PNP sensors to sinking inputs and NPN to sourcing inputs, choose relay outputs for mixed loads near 2 A per point and transistor outputs for fast DC loads near 0.5 A, and give analog channels the range and resolution your smallest required change demands.

    Controllers and I/O

  • Selection guide

    Add 4-20 mA analog inputs when the CompactLogix rack is full

    Swap the installed four-channel analog input card for an eight-channel one when channel isolation matches; that adds four inputs against a need of three, with no rack, power-supply or enclosure change. If isolation rules the swap out, reposition the existing power supply to free an end slot. When the cabinet itself is full, add a POINT I/O analog module or IO-Link converters over EtherNet/IP.

    Controllers and I/O

  • Selection guide

    Which analog inputs an S7-1200 water monitoring system needs

    An S7-1200 CPU carries only two onboard analog inputs, both voltage-type, so a water monitoring system with four to six analog sensors needs SM 1231 signal modules sized one channel per transmitter: current-range channels for loop-powered instruments, voltage channels for the rest, 12-bit on voltage and 11-bit on current. The data leaves over the built-in PROFINET port through the web server's CSV pages, WinCC, or SIMATIC NET OPC - no Modbus or PROFIBUS unless a sensor itself speaks one.

    Controllers and I/O