IMDHMIControls LibraryShop main store

Troubleshooting

Software you need to download a MicroLogix 1400 program

PLC programming Published 7 min read By IMDHMI controls team

Short answer

You need RSLogix 500 to open and download the program, and RSLinx to provide the communication path; the RSLinx Lite edition installed with RSLogix 500 is enough. RSLogix 5000 and Studio 5000 cannot download to a MicroLogix 1400 because they target the ControlLogix and CompactLogix families.

On this page
  1. Which software downloads a program to a MicroLogix 1400?
  2. Can RSLogix 5000 or Studio 5000 download to a MicroLogix 1400?
  3. Is RSLinx Lite enough, or do you need a bigger RSLinx edition?
  4. Where do you get RSLogix 500 for the download?
  5. What should you check before you download anything?
  6. How do you download the program step by step?
  7. Why does the machine still not run after a successful download?
  8. Which mistakes turn this recovery into a second outage?
  9. Questions asked

Download the program with RSLogix 500, and let RSLinx carry the connection. That is the whole answer: RSLogix 500 opens the supplier's .RSS project and writes it into the controller, and the RSLinx Lite edition, which the RSLogix 500 installer normally puts on the computer, provides the driver that finds the MicroLogix 1400 on the wire. RSLogix 5000 cannot do this job because it does not target the MicroLogix family at all. Before you download anything, confirm the program really is gone, upload whatever the controller still holds, and put the machine in a safe state, because a download replaces everything in controller memory. The sections below give the checks, the settings and the exact sequence.

Which software downloads a program to a MicroLogix 1400? #

You need two pieces: RSLogix 500, which opens the project and performs the download, and RSLinx, which supplies the communication driver between your computer and the controller.

RSLogix 500 is the editor for the SLC 500 and MicroLogix processor families. Rockwell Automation's release note for version 12.00.01, released December 2018, lists support for exactly those two families. For a MicroLogix 1400 the Micro edition of the package is the one identified for this controller class; whichever edition a distributor offers you, have them confirm that it covers the MicroLogix 1400 before you commit. The family-by-family mapping for older controllers is covered in which programming software each legacy PLC family needs.

The project itself arrives as a file with the .RSS extension. If the supplier's file carries that extension and opens in RSLogix 500 offline, you have the right family before you touch the machine.

Can RSLogix 5000 or Studio 5000 download to a MicroLogix 1400? #

No. RSLogix 5000 and its successor Studio 5000 target the ControlLogix and CompactLogix controller families, and neither package can open a MicroLogix project or download to a MicroLogix 1400.

The families store their projects in different formats with different processor databases, so there is no download path and no useful conversion. Why you cannot import a PLC project into another platform covers what actually happens when you try to carry a project across families. If the plant already owns Studio 5000 for its Logix controllers, that purchase does not help here: the MicroLogix 1400 needs its own package.

Is RSLinx Lite enough, or do you need a bigger RSLinx edition? #

RSLinx Lite is enough. The download needs only a driver that browses to the controller and carries the transfer, which the Lite edition provides; the larger RSLinx editions add OPC and data-collection features this job never touches.

You usually get it without a separate step: the RSLogix 500 installer normally puts RSLinx on the computer as a component, so check the installer's component list before you go looking for another package.

That split also tells you where a stall lives. If RSLinx cannot browse to the controller, the problem is the driver, the cable, the address or controller power, and reopening the project a fifth time changes none of those. If RSLinx shows the controller and RSLogix 500 still refuses the download, the problem has moved to the project: wrong processor, wrong family, or a prompt you have not read.

Where do you get RSLogix 500 for the download? #

Get RSLogix 500 through Allen-Bradley's official channels, meaning a distributor or the manufacturer's own licensing route, with RSLinx Lite riding along in the installer, and confirm the edition covers the MicroLogix 1400 before you commit. How to get RSLogix 500 through official channels walks those routes step by step, including what each purchase entitles you to install.

If this is a one-time recovery on a machine you will not touch again, there is a legitimate alternative to owning the package: send the controller to the machine supplier and have them reload their own approved project on their bench. You give up the ability to go online yourself next time, but you skip the entire software acquisition for a single download.

What should you check before you download anything? #

Confirm the program is actually gone before you overwrite anything: a stopped machine with a faulted controller, an open safety circuit or dead field power looks exactly like an empty controller from the outside.

Work through these checks before a download prompt appears:

  • Record the controller indicators and any fault text before clearing anything; a cleared fault cannot tell you anything later.
  • If the controller still answers, upload its contents and save them as the current image, labeled with the machine and the date. Even a project that will not run carries configuration and data values worth comparing against the supplier's file. The upload-first habit is the same one in back up an SLC 500 program by upload before you lose it.
  • Have the supplier confirm the file is an RSLogix 500 project for a MicroLogix 1400, and keep one untouched copy of exactly what they sent.
  • Pull the communication settings from the machine documentation, meaning address, serial rate and protocol, instead of guessing at them on a live network.
  • Identify the physical link you will use, the serial channel or the Ethernet port, and the cable or network connection it needs.

Put the machine in its safe state under your site's lockout procedure before the download: the controller can energize outputs the moment it returns to Run, and a reload is exactly when unexpected motion happens.

How do you download the program step by step? #

The sequence is: install, connect, browse, verify the controller's identity, open the project, upload what is still there, then download, and stop at any prompt you cannot explain.

  1. Install RSLogix 500 and confirm RSLinx appears among the installed components.
  2. Connect the programming computer to the controller over the link the documentation names, using the recorded settings.
  3. In RSLinx, configure the driver that matches that physical link, then browse in RSWho until the controller appears and stays visible.
  4. Verify identity before anything else: if the path shows several controllers, match the target against the machine documentation and the physical installation, not against convenience.
  5. Open the supplier's project and confirm it loads cleanly with a MicroLogix 1400 as the configured processor.
  6. Upload and save the controller's current contents if it still responds.
  7. Select the RSLinx communication path from RSLogix 500 and start the download, reading every processor-mismatch and mode-change prompt, and stop on any you cannot explain.
  8. Return the controller to the mode the approved startup procedure calls for, with people clear of the machine.

Run the sequence once with real values as a check on yourself: the supplier's file is a .RSS project; you install RSLogix 500 version 12.00.01; RSLinx Lite lands with it; you configure the driver for the documented link; the controller appears in the browse; the project opens showing a MicroLogix 1400; the upload of the old contents is saved; the download prompt reports no processor mismatch. Two pieces of software, one file, one path. Anything beyond that short list is a fault to chase, not a step you missed.

Why does the machine still not run after a successful download? #

Because a download replaces only the user application: it does not restore field power, close a guard circuit, fix an HMI address or clear a faulted drive, and one of those is now your problem.

Stay online after the transfer. Confirm the connection holds and the controller stays in the intended mode without a recurring fault; a fault that returns immediately after clearing points at configuration or hardware, and another download of the same file will not touch it. Compare the online project against the approved file, check inputs against actual sensors and guard conditions, and confirm the permissives come true in the expected order before you allow motion. Run one complete automatic sequence while watching the first condition that stops progression, because that first false permissive or active fault is your diagnostic boundary. Replacing the battery again or reinstalling the software past that point is motion, not progress.

Which mistakes turn this recovery into a second outage? #

The recurring ones are using RSLogix 5000 for a MicroLogix family controller, downloading before uploading what was left, and trusting a file from a similar machine instead of the supplier's approved project.

  • Downloading the same file a second and third time after the transfer already succeeded.
  • Skipping the identity check on a shared network and writing the program into the wrong controller.
  • Guessing the controller's address or serial settings instead of using the documented ones.
  • Taking an edition on the distributor's word without confirming MicroLogix 1400 coverage.
  • Clearing faults before recording them, which erases the only description of the original failure.

The decision, case by case: a MicroLogix 1400 on the bench means RSLogix 500 plus the RSLinx Lite that installs with it, full stop. A one-time recovery with no future need to go online can go to the supplier's bench instead. Anything already on the Logix side of the cabinet stays with Studio 5000, because that is a different controller, a different file and a different download.

Questions asked

How can you tell whether the program is really gone?

Go online with RSLinx and RSLogix 500 and attempt an upload: if a project comes back, the program was never lost and the stoppage is a fault, a mode issue or field wiring. A controller that reports a major fault or an empty memory is the real download case. Judge it by what the upload returns, not by when the battery was swapped.

What should the supplier's program file look like?

An RSLogix 500 project for this controller family is an RSS file. Open it offline before you connect anything: it should load without a processor-family complaint and show a MicroLogix 1400 as the configured processor. A file that RSLogix 500 refuses to open belongs to another family, so take it back to the supplier rather than converting it yourself.

Can you download over Ethernet or only over the serial cable?

Either, as long as the driver matches the link you physically use. If your controller has the built-in Ethernet port, configure an Ethernet driver in RSLinx with the documented address and browse from there. Otherwise use the serial channel with the matching cable and a serial driver. An Ethernet driver pointed at a serial link is a common reason the controller never appears.

RSLinx sees the controller, so why will RSLogix 500 not download?

The communication side is done; the project side is not. Check that the processor configured in the project is a MicroLogix 1400 matching the hardware, that the file really is an RSLogix 500 project, and read the exact wording of the download prompt. A processor-type mismatch between project and hardware is the usual cause, and it is fixed in the project, not in the driver.

What should you ask the machine supplier for before the next outage?

Ask for the approved RSLogix 500 project file, the controller's exact catalog number, the communication settings, and the startup sequence that returns the machine to Run safely. Store all of it together with the upload you took before this download. The next recovery then begins with a known file and known settings instead of a call to the supplier.

Keep reading

  • Explainer

    Why a MicroLogix 1200 has no read-only password for techs

    No. RSLogix 500 gives SLC 500 and MicroLogix controllers a single controller-level password, set in Controller Properties: whoever holds it can view, edit, and download, and whoever does not is locked out. Clear online edits per ladder file and treat the memory module as recovery — monitoring access must be solved procedurally, because no read-only login exists.

    PLC programming

  • How-to

    Back up an SLC 500 program by upload before you lose it

    An SLC 500 backup is an upload: read the program out of processor memory into a new RSLogix 500 offline file over a working RSLinx driver, save that file, then run a compare against the processor to prove the copy matches. Work the sequence below on the live processor and never download or clear memory to get there.

    PLC programming

  • Troubleshooting

    Why only Studio 5000 programs a ControlLogix 5571

    A ControlLogix 5571 is programmed only with Studio 5000 Logix Designer (RSLogix 5000 in older releases) over an RSLinx or FactoryTalk Linx driver path. The USB port feeds that driver, not a terminal: PuTTY, minicom or picocom never reach a prompt on this VxWorks-based runtime. A controller missing from a device list means you check installed Studio 5000 revisions and the communications path first, and you flash firmware only to match an installed release's major revision — never to cure a browse fault.

    PLC programming