SLC 5/05 to 1336 PLUS drives: remote I/O rack addressing

Drives and motion Published 7 min read

Short answer

Racks 2 and 3 in that specification mean Allen-Bradley Remote I/O: a scanner-and-adapter serial link, not Ethernet and not 4-20 mA wiring. Each 1336 PLUS with its Remote I/O adapter occupies a quarter rack and works through one output word and one status input word. A PLC-5 scans the link on its own channel; an SLC 5/05 needs a 1747-SN scanner whose G file places each rack.

On this page
  1. What racks 2 and 3 are asking for
  2. Rack, group and quarter rack in the I/O image
  3. Why the SLC 5/05 is not a drop-in PLC-5
  4. Reading the original PLC-5 addresses
  5. Configuring the 1747-SN and the drive adapters
  6. Example: mapping the two quarter-rack drives at remote racks 2 and 3
  7. The decision for each case
  8. Questions asked

Racks 2 and 3 in that drive specification mean Allen-Bradley Remote I/O: a scanner-and-adapter serial link, not Ethernet and not a 4-20 mA reference. The wording only makes sense in PLC-5 terms, where a rack is a block of I/O image rather than a cabinet, and a 1336 PLUS fitted with a Remote I/O adapter — the 1203-GD1 module or the onboard 1336-GM1 — occupies a quarter rack on the scanner's link. The platform decides the path: a PLC-5 scans the link from its own channel 1B with no extra card, while an SLC 5/05 has no Remote I/O port and reaches the link only through a 1747-SN scanner configured in its G file. Decide that first; the addressing math is the same either way.

What racks 2 and 3 are asking for #

A specification that assigns drives to remote racks 2 and 3 is calling for a Remote I/O link: a daisy-chained trunk from the controller's scanner to each drive adapter, terminated at both ends, with the speed command and the status crossing as 16-bit image words instead of analog levels. Your familiar alternatives map onto the specification like this.

A hardwired 4-20 mA reference with discrete enable and running feedback puts the drive on terminals instead of on a link, so the drive occupies no rack at all; that analog path is the one described in wiring a 1769-OF2 analog output to a PowerFlex 753 input, and it contradicts a specification that hands the drive a rack number. An Ethernet connection commands the drive with a different data model entirely and leaves the rack numbers unused, so it does not satisfy a rack-based specification either. That leaves Remote I/O as the reading the specification intends.

The decision rule is short: rack numbers in a specification mean Remote I/O; terminal numbers mean field wiring. A drive can follow either, and the command and reference source selections decide which one is live — worth checking before you blame the network for a drive that keeps obeying its keypad.

Rack, group and quarter rack in the I/O image #

A Remote I/O rack is a fixed block of image: eight groups, and each group is one 16-bit input word plus one 16-bit output word. Every adapter on the link takes at least a quarter of that block. A quarter rack is two consecutive groups, starting at group 0, 2, 4 or 6, and that is exactly what a 1336 PLUS with its Remote I/O adapter requests. The drive then works through a command word on the output side — speed reference plus the run, stop and fault-clear logic — and a status word on the input side; which bit carries which signal is defined in the drive's Remote I/O documentation for the adapter fitted. The second word pair in the quarter rack belongs to the drive's image whether or not you use it.

Allocation Groups Input words Output words What fits there
Full rack 8 8 8 four quarter-rack drives
Half rack 4 4 4 two quarter-rack drives
Quarter rack 2 2 2 one drive: command word out, status word in

Why the SLC 5/05 is not a drop-in PLC-5 #

The original design names a 1785-L80E and a 1785-40E. Both are PLC-5 processors, and a PLC-5 scans Remote I/O from its own channel 1B, so the rack numbers were written against hardware that needs no scanner card. An SLC 5/05 processor has no Remote I/O scanner built in: the link exists only if a 1747-SN scanner sits in a chassis slot. The platforms also file the image differently — the PLC-5 folds remote racks into one digit-based addressing scheme, while the SLC places each scanned rack into its input and output files through the scanner's G file.

That makes the substitution a redesign, not a translation: RSLogix 500 cannot prove a PLC-5 rack allocation, and a G-file layout cannot be copied backwards into a PLC-5 project. Two honest paths exist — rebuild the design on the PLC-5 in the PLC-5 programming package, or keep the specification's drive-side rack numbers and remap the scanner side to the SLC. One thing never to do: install a 1747-ASB in a controller chassis to connect the blending and filling controllers. The ASB is an adapter, not a scanner — it makes a chassis answer to somebody else's scanner — and two adapters do not make a link.

Reading the original PLC-5 addresses #

In PLC-5 logical addressing the first digit of a word address is the rack and the second is the group: an input word at rack 2, group 0 is I:200, and its output partner is O:200. Rack 0 belongs to the processor's own chassis, so the transmitters the specification describes as being in rack 1 are that local I/O with the writer's label on it — rack 1 is not a setting you enter anywhere. What matters is whether racks 2 and 3 are actually free, which depends on the local chassis size and the addressing mode (2-slot, 1-slot or half-slot), because finer addressing makes local cards consume more groups. Read the local configuration, mark every input and output word the local cards consume, then confirm each drive rack starts on a free boundary. Only then does assigning a drive to rack 2 or 3 mean anything.

Configuring the 1747-SN and the drive adapters #

On the SLC side, add the 1747-SN in the I/O configuration screen of RSLogix 500, open its advanced configuration, and use the Edit G data button. The G file holds one entry per scanned rack, and each entry sets that rack's size — quarter, half or full — and where its words start in the SLC input and output files. The Remote I/O Scanner (1747-SN) User Manual charts the whole addressing layout in its appendix; copy that page and pencil in your assignments before typing any of them into the software.

On the drive side, set each adapter's address selection to the rack, starting group and rack size the scanner expects, and set each 1336 PLUS's command and reference source to the Remote I/O link. If a drive ignores the link, read those source selections before touching rack addresses: a drive following its keypad or an analog input is a source-selection problem, not a network fault.

One safety check belongs here: break the scanner connection deliberately and confirm each drive goes to a stop you chose, because the behavior on link loss is defined in the drive documentation and must be proven, never assumed.

Example: mapping the two quarter-rack drives at remote racks 2 and 3 #

Worked case: two 1336 PLUS drives with quarter-rack Remote I/O adapters, a 1747-SN in slot 1, slots 2 and 3 empty in this example panel, and each adapter set to start at group 0.

Link side. A quarter rack is two of the rack's eight groups, so each drive occupies groups 0 and 1 of its rack. Drive 1 is set to rack 2, group 0: its words carry the digits 2-0 and 2-1, which a PLC-5 would address as O:200 and O:201 for output and I:200 and I:201 for input — command and speed in the word numbered 200, status in its input partner, the 201 pair spare. Drive 2 is set to rack 3, group 0: O:300 carries its command, I:300 its status, and the 301 pair is spare.

SLC side. Place rack 2's G-file entry at slot 2, group 0, and rack 3's at slot 3, group 0. Rack 2's image then lands as input words I:2.0 and I:2.1 and output words O:2.0 and O:2.1, so you write drive 1's speed word to O:2.0 and read its status from I:2.0. Rack 3 lands as I:3.0, I:3.1 and O:3.0, O:3.1, giving drive 2 its speed word at O:3.0. Had rack 2 been placed at slot 5 instead, the same drive's speed word would be O:5.0 — the link rack number and the data-table word never have to agree, and the G file is the only thing that ties them together.

The decision for each case #

  • Deliverable must match the written specification: build on the PLC-5, scan the drives from the processor's Remote I/O channel, and keep racks 2 and 3 as written once the local image leaves them free. PLC-5 programming software is required; RSLogix 500 work does not prove this design.
  • The panel really runs SLC 5/05 hardware: fit the 1747-SN, set both drive adapters to quarter rack at racks 2 and 3, place both racks with the G file, and program against the mapped words — the two speed words from the example, never a rack-digit address.
  • A drive is meant for analog control: wire the reference and enable to terminals and leave that drive off the link, accepting that the rack sentence in the specification does not then apply to it.
  • The blending controller needs the filling controller's analog value: move it over a separate processor-to-processor route, message instructions as described in CompactLogix MSG to SLC 5/04 through a DH+ gateway, because drive racks never carry controller-to-controller data.
  • No 1747-ASB in a controller chassis as a stand-in for the scanner: it is an adapter, and adapters answer scanners; they do not scan drives.

Questions asked

Is the SLC 5/05 processor itself set up as rack 1?

No. A rack number in Remote I/O is a block of scanned image, not an attribute of a processor, and nothing on the SLC mirrors that phrase from the specification. In the original PLC-5 design the processor's local chassis holds rack 0, and the transmitters described as being in rack 1 are just that local I/O with the writer's label on it. On the SLC you assign rack numbers only to the drive adapters and map those racks wherever the 1747-SN's G file places them.

How many quarter-rack drives fit in the racks 2 and 3 space?

A full rack is eight groups and a quarter rack is two, so one rack holds four quarter-rack drives and racks 2 and 3 together hold eight. Two drives leave six quarter-rack positions free in those racks. The practical ceiling is what the scanner is configured to scan: the rack list and image sizes are charted in the appendix of the 1747-SN user manual.

Can I keep the speed reference on 4-20 mA and still put the drive on the link?

Pick one control path per drive. If the drive has a Remote I/O adapter and the specification assigns it a rack, the reference is expected to arrive in the drive's command word, and a parallel analog reference leaves two sources fighting over the drive unless the source selection deliberately switches between them. If the drive has no adapter, wiring the analog terminals is the legitimate design, but the drive then occupies no rack and the rack sentence in the specification does not apply to it.

What happens when the G file and the drive adapters disagree?

The link only works when both ends name the same rack, starting group and rack size. If an adapter answers at a rack the scanner is not scanning, the scanner sees that rack as not responding and the drive's image never updates, no matter what the ladder logic does. Recheck the G-file entry, the adapter's address selection and the drive's source selections, and make the numbers identical.

Do the two drive racks give the blending and filling controllers a data path?

No. Remote I/O is a link between one scanner and its adapters, and each processor owns its own link and its own drives. An analog value the blending controller needs from the filling controller must travel a separate processor-to-processor route, such as message instructions over the Ethernet port on a 5/05 or over serial or DH+ on processors that have it, designed and tested on its own. The drive rack assignments move no data between controllers.

Keep reading

  • How-to

    How to map a 1747-SDN scanner for DeviceNet drive control

    Seeing the drive in an RSNetWorx browse is not an I/O connection. Put the drive in the 1747-SDN scanlist, read the M-file words the scanner mapping assigns, and reference those mapped words in the SLC 5/04 ladder. A node address is not an integer-file offset: the mapping view, not node 10, decides where each command and status word lives.

    Industrial networks

  • How-to

    Configuring S7-300 PROFIBUS control for an MM420 drive

    Hardware configuration alone moves no drive data. An S7-300 reads and writes an MM420's cyclic PROFIBUS area with SFC14 and SFC15 whenever the consistent area is too large for direct access, maps every control-word and status-word bit to the configured telegram, and switches the drive's command and setpoint sources to the fieldbus before the first enable. Judge drive readiness from the status word, not from a completed bus transfer.

    Drives and motion

  • How-to

    Connect an S7-300 to a DCM drive over PROFIBUS or PROFINET

    Yes: an S7-300 controls a DCM over PROFIBUS or PROFINET by installing the drive's GSD or GSDML description, selecting the same supported telegram on both sides — standard telegram 1 (PZD-2/2) is the safe first choice — exchanging the 4-byte records with SFC14 and SFC15, and trusting the link only once cyclic exchange runs fault-free. A clean link still will not move the motor while the drive's command source is local or an enable is missing.

    Drives and motion