Short answer
Yes, you can exchange it with the CPU powered: stop and secure the machine, leave control power on, and swap the BC 291 cartridge in one brief motion. Test any cartridge unplugged, at a minimum of 2.2 V through 100 kOhm between pins 2 and 6. Upload the program first, because the cartridge's life is estimated at about 10 years and it is not a copy of the program.
On this page
- Does the S7-200 CPU 224 have an internal battery?
- Can you replace the battery module while the PLC is powered on?
- How do you back up the program before the swap?
- What is the step-by-step replacement procedure?
- How do you test the battery cartridge with a meter?
- How long does the battery cartridge last?
- What can go wrong during the replacement?
- Questions asked
The battery you are looking for is not inside the CPU. An S7-200 CPU 224 has no internal cell: it holds the program with a capacitor, and long-term retention comes from the optional battery module BC 291 plugged onto the memory module on the CPU. The safe swap is to stop and secure the machine, keep control power on, and exchange the cartridge in one brief motion, because powered memory does not depend on the battery at all. Upload the program to a PC before the hardware work, and test any cartridge unplugged, at a minimum of 2.2 V through 100 kOhm between pins 2 and 6.
Does the S7-200 CPU 224 have an internal battery? #
No. The CPU 224 keeps its program and retentive data alive through a capacitor on the CPU board, and the only battery in the system is the optional BC 291 cartridge that plugs onto the memory module.
The order code on your unit, 214-1BD23-0XB0, is the CPU 224 itself, and no version of this CPU contains a cell to replace. The manufacturer's data sheet describes the BC 291, ordered as 6ES7291-8BA20-0XA0, as a battery module for long-term buffering of data, pluggable into the memory module, so the replaceable part is the whole cartridge. There is no documented procedure for opening one, so do not improvise a cell swap.
One consequence drives the rest of this job: while the CPU is energized, the battery is out of the data path entirely. The cartridge matters only when control power is off, and no hold-up time is documented for the capacitor alone, so treat every power-off as running on the cartridge.
Can you replace the battery module while the PLC is powered on? #
Yes on the data side, no on the machine side: a powered CPU keeps the program in powered memory without touching the cartridge, but the machine must be stopped and its motion energy isolated before the panel is opened.
Separate the two supplies before you decide. Control power, the supply feeding the CPU, stays on for the whole job, while motor power, hydraulics and pneumatics are locked out; that gives you a memory-safe CPU and a machine that cannot move. The manufacturer's own test procedure has you unplug the cartridge from the CPU, which tells you the connector is meant to be separated in service.
Do not do this during production with actuators live, and treat the open panel as energized work for qualified personnel only. Make the exchange quickly even so: if control power dipped during the seconds with no cartridge seated, and the old one was already spent, nothing would be holding the memory.
How do you back up the program before the swap? #
Upload the program from the CPU to a PC before any hardware work, because that upload, not the battery, is the only thing that makes a one-of-a-kind program recoverable.
You need a PC with Micro/WIN and the matching programming cable; the upload reads the program as it runs in the CPU, so the original project file is not required. Which version the CPU 224 accepts is covered in how to get the right Micro/WIN version for an S7-200 CPU 224, and if the transfer is refused, fix block format not recognised when uploading an S7-200 program walks through that fault. Save the uploaded project in two places away from the machine.
Do not count the module in the memory slot as a copy: why an S7-200 memory cartridge cannot transfer the user program explains why it is storage the CPU uses, not a takeaway backup. If Micro/WIN access cannot be arranged before the swap date, do the cartridge exchange anyway, since a powered exchange does not endanger the program, and keep chasing the upload.
What is the step-by-step replacement procedure? #
The exchange itself is one brief motion on a powered CPU: motion locked out, control power on, old cartridge off and new one on, then verify the CPU's status before anything is re-enabled.
- Confirm the replacement is the BC 291 cartridge, 6ES7291-8BA20-0XA0, matching the part installed; no substitute is documented.
- Finish the program upload and save two copies off the machine if access exists.
- Stop the machine, isolate and lock out every motion energy source it has, and leave the CPU's control supply energized.
- Check that the CPU stays in RUN, then locate the cartridge on the memory module and note its orientation before touching anything.
- Pull the old cartridge off and push the new one on in the same orientation, in one motion, without cycling control power.
- Confirm the CPU remains in RUN with no fault indication; if it faults, reseat the cartridge before investigating anything else.
- Write the fitting date on the new cartridge and in the maintenance log, since that date sets the next service.
- Restore motion energy per the site's restart procedure and watch a first cycle before handing the machine back.
How do you test the battery cartridge with a meter? #
With the cartridge unplugged, measure at least 2.2 V through a 100 kOhm resistor connected between pins 2 and 6 of the module; a lower reading means the cartridge is spent.
This is the manufacturer's own validation, published as FAQ entry 17490344, and the resistor is what makes it a real test: a nearly dead cell can still show a healthy open-circuit voltage, while a loaded measurement proves the cartridge can deliver current. Run it on the removed cartridge to confirm the diagnosis, and on the new one before it goes in.
Illustrative readings: a cartridge that shows 2.4 V across the test resistor is delivering 2.4 V ÷ 100 000 Ω = 0.000024 A, about 24 µA under load, and passes; one that shows 1.9 V delivers 1.9 V ÷ 100 000 Ω = 19 µA and fails, however good it looks off-load.
How long does the battery cartridge last? #
The manufacturer puts the cartridge's lifetime at about 10 years, and a cartridge that has reached that age gets replaced rather than trusted, because the figure is an estimate of service life, not a guaranteed interval.
On a machine whose builder is gone and whose source code exists only inside the CPU, an aged cartridge is all that stands between a power cut and a dead machine, which is exactly why the upload comes before the battery work. A cartridge at that age is at the end of the estimate even if it passes a bench test today; passing says nothing about next winter.
Date the new cartridge when you fit it and schedule its successor at the same age. For a cartridge of unknown age, let the loaded test decide: pass, and it stays with a retest at each maintenance visit; fail or untestable, and it goes.
What can go wrong during the replacement? #
Three realistic failures cover this job: a control-power dip while no cartridge is seated, a cartridge fitted in the wrong orientation or not fully seated, and a bench measurement taken at the CPU instead of at the unplugged module.
A power dip in the unplugged window leaves the memory with only the CPU's capacitor behind it, so the upload-first rule is what actually protects the program. A mis-seated cartridge shows up as a fault indication on the CPU after the exchange; reseat it before chasing anything else. Measuring at the CPU socket rather than at the module's pins risks shorting adjacent contacts with a probe tip, so the module comes off for the test, exactly as the procedure requires.
Questions asked
Should a new cartridge be tested before it goes in?
Yes. The cartridge is delivered unplugged, so the loaded measurement takes a minute on the bench before it goes anywhere near the machine. A spare that sat on a shelf for years may already be partway through its life, which is another reason to write the fitting date on it. Testing first also means a dead-on-arrival part is found while the old cartridge is still in service.
Does a passing battery test make the upload unnecessary?
No. The loaded measurement proves the cell can deliver current on the day you test it; it says nothing about where the program's second copy lives. A battery only keeps memory alive through power failures on that one CPU. The upload to a PC is what makes the program recoverable after a CPU failure, and no cartridge can do that.
Is the memory module in the CPU slot a backup of the program?
No. The battery cartridge plugs onto that module, but the module is storage the CPU itself uses, not a copy you can carry to another CPU and restore from. Treat the uploaded project file, saved in two places away from the machine, as the only real backup. Anything that exists only inside the panel is one fault away from being gone.
Can a look-alike replacement cartridge be used instead?
Order the manufacturer's part rather than a copy: the service-life estimate and the loaded test limit belong to the BC 291, and no equivalent is documented for anything else. If a non-original cartridge is already installed, date it, run the same loaded test on it, and shorten the replacement interval, because its aging behavior is unknown.