Replacing a 1746-BAS module in a ControlLogix migration
Short answer
There is no drop-in 1746-BAS replacement: a 1756-DHRIO carries DH+ and DH-485 only. Recover the BASIC program through the terminal port first, then choose from what it polled on PRT2. Where the ComSTATE setting confirms or can enable Modbus on the Honeywell controllers, an in-chassis Modbus master over the existing RS-485 wiring replaces the module, and the 64-word M1-to-N7 copy becomes mapped controller tags.

On this page
There is no drop-in equivalent for a 1746-BAS module, so a migration into the planned 1756 chassis has to replace the function, not the catalog number. The 1756-DHRIO in the parts list carries DH+ and DH-485 traffic only; it cannot reproduce what the BASIC module did on PRT2. Decide the replacement from what that program actually polled: recover the BASIC program through the terminal port, read the ComSTATE setting on every Honeywell controller the cable reaches, and where Modbus is confirmed or can be enabled, put an in-chassis Modbus master on the existing RS-485 multidrop. The M1-to-N7 copy rung disappears and its words become mapped controller tags in the new controller.
What the 1746-BAS was actually doing #
The module in this rack is a 1746-BAS-5/02, the M0/M1-capable BASIC module: an Intel 8051 running a BASIC interpreter, three serial ports, support routines for the DH-485 network, and a backplane interface that maps the module's M0 and M1 files into SLC data tables. The SLC program holds one rung that copies 64 words from #M1:1.0 in the M1 file into N7. That copy is only the visible half of the function.
The other half is the polling program in interpreted BASIC. Rockwell's installation instructions for the SLC 500 BASIC and BASIC-T modules, publication 1746-IN009, describe PRT2 as a serial port that accommodates RS-232/423, RS-422 and RS-485 modes, with documented full-duplex rates including 300 and 600 baud. With the jumpers set for RS-485 mode, the connections are pin 1 for Data(-), pin 9 for Data(+), and pin 5 for data common, matching the RS-485 wiring diagram in publication 1746-UM004 — and matching how this port 2 lands on the blue multidrop cable to the controllers.
Hold the wire standard and the protocol apart. RS-485 and RS-422 define electrical signaling only; DH-485, Modbus RTU and Honeywell's MB3K protocol define frames. The jumper positions tell you how bits cross the cable. Only each controller's own communication configuration tells you what the frames mean.
Why the 1756-DHRIO is not the replacement #
The planned chassis — a 1756-L81E controller, a 1756-PB75 power supply, a 1756-A4 chassis and a 1756-DHRIO — is a sound migration target, and the DHRIO is the right module for one half of the job. It carries DH+ and DH-485 links into the ControlLogix chassis, taking over the DH+ connectivity the 1747-L541 SLC 5/04 (OS401, 16K memory) provided on its own port. Where the plant still has to reach PLC-5 and SLC 500 data across that legacy network, Reaching PLC-5 and SLC 500 data through a ControlLogix DH+ bridge covers the routing side.
It covers nothing on the multidrop. The DHRIO has no BASIC interpreter and no Modbus master firmware, so it will never poll a UDC or DCP controller, and nothing else already in that chassis will either. The serial master is a deliberate addition: a Modbus master module in the rack, or a gateway host outside it.
The processor size is a separate decision, and here it is settled by the customer. An L81E is far more controller than the SLC 5/04 required — the case for right-sizing is made in Sizing a CompactLogix to Replace Four SLC 500 Processors — but this customer specified the 1756-L81E for future upgrades, so keep it and move on. None of that touches the serial function.
Recover the BASIC program first #
Read the module before you buy anything, because the listing decides the architecture. Two cautions belong up front: stopping the program interrupts polling, so schedule downtime; and upload and archive what is still reachable first, which is the discipline behind Back up an SLC 500 program by upload before you lose it.
The recovery sequence:
- Photograph the jumper positions, JW1 through JW4, before moving anything.
- Wire an ordinary RS-232 terminal cable to PRT1 and set the terminal to the command-mode defaults the 1746-BAS manual documents. The recorded session used no parity, 8 data bits, 1 stop bit and XON/XOFF flow control. Treat a field note that reads 1200 KB as an ambiguous unit and take the rate from the manual.
- Send Control-C to stop the running program. Typing LIST while the interpreter is still executing can return a misleading result.
- Enter LIST and capture the complete RAM listing as plain text.
- Check the memory hardware and the documented RAM and ROM commands. In the condition described here, LIST returned no program, the ROM command answered ERROR: PROM MODE, and the 28-pin socket on the board was empty: the module ran from battery-backed RAM, and the program is gone.
- If a valid program appears, enter RUN to return it to operation, then capture it again for the archive.
Do not download a test program until recovery is complete. A hello-world test proves the interpreter works, but it can overwrite the only surviving RAM copy.
Identify the protocol on every controller #
The multidrop carries four nodes, wired in pairs. Node 1 holds a UDC3000 VersaPro with a UDC2000 Mini Pro; node 2 holds a UDC3300 with a UDC2000; node 18 holds a DCP102 with a UDC500; node 19 holds a DCP102 with a UDC2000 Mini Pro. The second controller in each pair is the high-limit unit, and the communication cable lands on the first controller only — eight devices exist in the field, and four sit on the wire.
Confirm every node on its own screen, because model-specific option cards decide what each unit can do. On the bench, the single controller fitted with a Modbus card communicated through an in-chassis module, while the other responding controllers used proprietary ASCII. A success against one unit is not a network-wide result.
The decisive screen is the communication setup group. In the UDC 3300 Basic model manual (DC330B) it sits on page 34, PDF page 42, and ComSTATE is the fork: Modbus enabled means the device speaks classic Modbus; disabled means it speaks MB3K, Honeywell's proprietary protocol. Record the whole group while you are there — the checked UDC3300 read Comstate RS422, Shedtime 30, Parity Even, Baud 9600, Duplex Half, Shedmode Last, Shed SP TO LSP — and preserve those values through the migration, confirming the time unit behind Shedtime in the model manual before trusting the number.
Choose the replacement architecture #
The function to buy is a serial master, and three paths cover every case:
| Replacement path | What it replaces | Hardware that carries it | Wiring impact |
|---|---|---|---|
| In-chassis Modbus master | The whole polling program: node selection, requests, reply validation, register extraction | A Modbus master module in the 1756 chassis | None: pin 1 Data(-), pin 9 Data(+), pin 5 common stay as wired |
| Standalone gateway host | Polling and protocol decoding, moved outside the PLC | A protocol converter host in the cabinet | The gateway becomes the multidrop master; the PLC consumes its data |
| Controller-side protocol switch | The need to decode MB3K anywhere | Front-panel configuration on each Honeywell unit | Unchanged; re-verify each loop after the switch |
The first path is the direct successor to the BASIC program. An in-chassis Modbus master module for the ControlLogix chassis — ProSoft Technology's in-chassis Modbus master/slave family is one source of the category — does in firmware what the interpreter did in BASIC, and the same questions that decide Choosing a Modbus RTU bridge for an iQ-R DCS migration apply here: which side masters the link, which signal types the module terminates, and how the register map lands in controller tags.
The second path earns its place when a node speaks a protocol no module can parse. The polling brain moves out of the chassis into a cabinet-mounted host — the role of an industrial mini PC — and the controller simply consumes the gateway's data.
The third path is the shortcut this migration can take precisely because there is no BASIC program to preserve: if a unit sits on MB3K, enabling Modbus on it costs nothing you were not going to rebuild anyway.
Move the M1 copy into controller tags #
The rung that copies the M1 block into N7 retires with the module. A Modbus master writes controller registers straight into controller tags, so the staging file and the backplane copy both disappear. Build the new tag map from traced usage, not from the old block size.
Worked example from this installation: the transfer moved a 64-word block, and eight addresses — N7:0 through N7:3 and N7:34 through N7:37 — sat frozen while the process ran. That leaves 64 - 8 = 56 words that demonstrably carried live data, spread over the four polled nodes, which averages 56 / 4 = 14 words per node. Treat the average as a sanity check only, because status words and padding are never distributed evenly; the per-node word counts come from the trace.
Build that trace before you map anything. Search every reference from N7:0 through the end of the block in the SLC program, then search the HMI database for the same addresses and record display ranges, decimal positions, alarm limits, write permissions and operator labels. Then decide what the new system writes. Start read-only. If the old system changed setpoints or drove profile selections, make every write its own function with a permissive condition and a bench test. Older UDC practice kept frequently changing remote setpoints in CSP mode so repeated writes landed in RAM instead of wearing EEPROM write cycles, and high-limit variants can reject remote setpoint writes outright. One safety note: prove any remote setpoint or profile command on the bench or with the loop in manual before it can move a live process — a miswritten setpoint is a process excursion, not a communications fault.
The decision, case by case #
- Every node the cable reaches reads Modbus in ComSTATE: order an in-chassis Modbus master for the 1756 chassis, keep the multidrop wired as it is, and map the traced words into controller tags.
- The BASIC program proved unrecoverable and the nodes sit on MB3K: enable Modbus on each polled unit and buy the same master; reverse-engineering MB3K buys nothing the migration needs.
- A node cannot run Modbus at all: give that node a gateway host, or replace the controller.
- The 1756-DHRIO stays in the chassis for DH+ and DH-485 in every case; it was never the 1746-BAS replacement.
Questions asked
Does the 1756-DHRIO replace the 1746-BAS?
No. The 1756-DHRIO moves DH+ and DH-485 traffic into the ControlLogix chassis, and a DH-485 network interconnects up to 32 devices, but nothing on that module speaks to process controllers. It takes over the SLC 5/04's DH+ port; the polling function the 1746-BAS provided on PRT2 needs a Modbus master module or a standalone gateway.
What do the shed settings on the Honeywell controllers mean?
They govern what a loop does when the polling master goes quiet: after the shed time expires, Shedmode and the shed setpoint selection decide whether the controller holds its last value or drops to its local setpoint. The checked UDC3300 read Shedmode Last with the shed setpoint to LSP, so that loop falls back locally, and the recorded shed time of 30 means nothing until the model manual says whether it counts seconds or minutes.
Will a 1747-PIC converter help reach the Honeywell network?
No. The 1747-PIC converts the RS-232 serial port of a personal computer into RS-485 format so a PC can join a DH-485 network. The Honeywell multidrop carries process-controller protocols, not DH-485, so the PIC belongs to the SLC and DH-485 side of the plant, not to polling the UDC and DCP controllers.
Can a gateway or HMI box replace the module instead of a PLC module?
Yes, when a device speaks proprietary ASCII that no PLC module can parse. A gateway with a raw serial driver lets you write the request and decode the reply yourself, which is the same job the lost BASIC program did in interpreted BASIC. For controllers confirmed on classic Modbus, the in-chassis master stays simpler, because register mapping replaces hand-written decoding.