Replace a 16-branch ELSIF chain with one indexed array read

PLC programming Published 3 min read

Short answer

When A is an INT and B is an array of INT, replace the whole ELSIF chain with IF COUNT >= 1 AND COUNT <= 16 THEN A := B[COUNT - 1]; END_IF. COUNT is one-based while the array runs from B[0] to B[15], so the subtraction maps the selection and the range check keeps the index inside the array.

On this page
  1. Replace the chain with one guarded assignment
  2. Map COUNT to the array index
  3. Why the range check stays
  4. Worked example: verifying the replacement for COUNT = 16
  5. Questions asked

A 16-branch ELSIF chain that copies B[0] through B[15] into A is one assignment wearing sixteen conditions. Because A is an INT and B is an array of INT, select the element with the counter itself: COUNT is one-based (COUNT = 1 selects B[0]) while the array runs from B[0] to B[15], so subtract 1 and guard the range between 1 and 16. One line replaces the chain and never addresses outside the array.

Replace the chain with one guarded assignment #

Write the replacement as a single IF statement:

IF (COUNT >= 1) AND (COUNT <= 16) THEN
    A := B[COUNT - 1];
END_IF;

The assignment A := B[COUNT - 1] reproduces every branch of the original chain: COUNT = 1 reads B[0], COUNT = 2 reads B[1], COUNT = 8 reads B[7], and COUNT = 16 reads B[15]. A scan that once evaluated up to sixteen comparisons now evaluates two: COUNT >= 1 and COUNT <= 16.

Map COUNT to the array index #

COUNT Calculated index Assigned element
1 1 - 1 = 0 A := B[0]
2 2 - 1 = 1 A := B[1]
7 7 - 1 = 6 A := B[6]
8 8 - 1 = 7 A := B[7]
15 15 - 1 = 14 A := B[14]
16 16 - 1 = 15 A := B[15]

The expression is the whole mapping; no branch table in code is needed. Every row follows the same rule, index = COUNT - 1, from 0 up to 15. When you later extend B to more elements, the only change is the upper limit in the guard.

Why the range check stays #

The referenced array covers only B[0] through B[15]. Without the guard, COUNT = 0 produces index -1 and COUNT = 17 produces index 16; neither index exists. What a controller then does is platform specific: some raise an "Array index out of range" fault at runtime, which on some Logix controllers is a major fault, and some environments run a bounds check on every access. Keep the range check unless other logic guarantees COUNT stays between 1 and 16 on every scan, and the question never comes up. A failed bounds check at runtime is the kind of fault you find at 2 a.m., not in the code review.

If you want the counter selection to drive more than a copy, for example a timer per step, the same indexed approach works there too; see how a REPEAT loop runs in PLC structured text for stepping through the array itself.

Worked example: verifying the replacement for COUNT = 16 #

Inputs: the original chain from the logic being replaced, where COUNT is an INT selector running 1 to 16, A is an INT destination, and B is an array of INT with elements B[0] to B[15].

The rule: a one-based selection value N maps to the zero-based index N - 1, and the assignment runs only when N is inside 1 to 16.

The arithmetic for the last step:

  • COUNT = 16, so the index is 16 - 1 = 15.
  • The guard evaluates 16 >= 1 (true) AND 16 <= 16 (true), so the assignment executes.
  • A receives B[15], the last element, exactly as the original ELSIF COUNT = 16 branch did.

The decision: adopt the guarded one-line assignment, and prove it with a four-step online test before the chain is deleted:

  1. Put distinct values in B[0] and B[15].
  2. Set COUNT to 1 and confirm A receives B[0].
  3. Set COUNT to 16 and confirm A receives B[15].
  4. Set COUNT to 0 and to 17; with the guard, the assignment does not execute and A keeps its previous value.

If all four steps pass, delete the ELSIF chain. If step 4 ever faults or changes A, the guard was dropped or mistyped; fix the range check, not the array bounds.

Questions asked

What does the controller do when COUNT goes out of range without the guard?

The referenced array covers only B[0] through B[15], so COUNT = 0 gives index -1 and COUNT = 17 gives index 16, and neither index exists. What happens next is controller specific: some platforms raise an array index out of range fault at runtime, which can be a major fault, and some environments perform a bounds check on every access. Keep the range check so the question never arises.

Can I drop the IF and write only the assignment?

Only when other logic in the program guarantees COUNT stays between 1 and 16 on every scan. If an operator entry, a communication write or a counter overrun can push COUNT outside that range, keep the guard; it costs one comparison pair and prevents an invalid index.

Does the same replacement work for arrays of REAL or BOOL?

Yes. The indexed read is independent of the element type: A := B[COUNT - 1] works when A matches the element type of B, whether INT, REAL or another type. Declare A with the same type as the array elements and keep the same range check on COUNT.

Keep reading

  • How-to

    How CODESYS FBD accepts two box outputs on one box

    Yes, CODESYS FBD accepts two outputs from separate boxes on different inputs of one box, but the wiring order decides whether the editor takes the branch. Connect the second source to the destination first, attach the first source to the second source's second input connector until the plus sign appears, or assign the shared result to an intermediate variable and feed that variable to both inputs.

    PLC programming

  • Explainer

    How a REPEAT loop runs in PLC structured text

    In IEC 61131-3 structured text, a REPEAT loop executes its body first and evaluates the UNTIL condition after it, so the body always runs at least once and the whole loop completes inside one task invocation. With i := 0 and UNTIL i >= 10, the body runs 10 times and i ends at exactly 10; the test position is what explains the off-by-one cases and when WHILE fits better.

    PLC programming

  • How-to

    How to migrate derived function blocks to Machine Expert

    No tool converts Control Expert derived function blocks into Machine Expert. Migrate them as a manual code port: copy the Structured Text body, rebuild every declaration and dependency by hand, resolve the two environments' differences, and test each block; blocks written in other languages are recreated. IEC 61131-3 keeps the language portable, not the project or the libraries.

    PLC programming