Reading ATV71 drive parameters into Ignition over Modbus TCP

Drives and motion Published 7 min read By IMDHMI controls team

Short answer

A networked ATV71 is read by protocol and register map, never by rack or slot. Poll it directly with Ignition's native Modbus TCP/IP driver through a VW3A3310 Modbus TCP/IP module, or let the PLC that already talks to the drive expose the values; the hardwired control and shutdown wiring stays untouched. Every address, data format and scaling comes from the drive's Communication Parameters manual.

On this page
  1. A networked drive is a register map, not an I/O point
  2. Choose the read path before opening Ignition
  3. The procedure, from card to verified tags
  4. Proving one tag: 12 mA on a 4 to 20 mA reference scaled 0 to 60 Hz
  5. When the values come in wrong
  6. The decision for each installation
  7. Questions asked

Your ATV71 is already on the network, so the values you want — energy consumption, voltage and current — are Modbus registers, not rack, slot and channel references, and Ignition reads them with its native Modbus TCP/IP driver. Two read-only routes work: poll the drive directly if its Ethernet card is the VW3A3310 Modbus TCP/IP module, or let the PLC that already talks to the drive read the parameters and expose them. Either way the hardwired control and shutdown wiring stays exactly as it is; monitoring rides on top. The job comes down to three things: establish what protocol the installed card actually speaks, take every address and data format from the drive's Communication Parameters manual, and prove one tag at a time against the drive's own display.

A networked drive is a register map, not an I/O point #

On hardwired I/O the chain is physical: a terminal, a channel, a card in a rack and slot, and a SCADA address that points at them. A networked drive has none of that. It answers a protocol at a node address, and every value it exposes sits at a documented register with a documented data format and unit.

Two consequences follow. The Ethernet cable and the switch prove only attachment; they say nothing about which protocol the installed card speaks, and Modbus TCP is only one of the protocols an Ethernet card can carry. And no amount of address guessing recovers a register that was never looked up: the register list for the ATV61 and ATV71 is published in their Communication Parameters manuals, and that document is the only source for the addresses, formats and units of energy, voltage and current.

Choose the read path before opening Ignition #

Three routes can put drive data into Ignition. Pick by what already exists:

  • Direct polling. The drive carries the VW3A3310 Modbus TCP/IP module and Ignition's native Modbus TCP/IP driver polls it as a Modbus TCP device. This is the shortest chain — drive, switch, Ignition — and it keeps the PLC out of the data path.
  • Through the PLC. The controller already owns the drive link; its program reads the parameters into a data table and Ignition reads the controller. No new hardware, but valid only if the PLC program actually reads those parameters — sharing a switch with the drive does not put drive data into the PLC.
  • Through a gateway. Where the drive's only channel is serial Modbus RTU and the PLC cannot expose the values, a gateway polls the serial port and serves Modbus TCP to Ignition. It adds a serial leg, with the wiring, termination and cabinet noise that come with it; how a large motor starter couples noise into nearby control wiring is the failure mode to design against.

Pick the route that adds the fewest new links between the drive and Ignition. For monitoring only, with the Modbus TCP/IP module available, that route is direct polling.

The procedure, from card to verified tags #

  1. Identify the card. Record the communication card's part number and how it is addressed on the network. If the installed card speaks something other than Modbus TCP and direct polling is wanted, the part to fit is the VW3A3310 Modbus TCP/IP module.
  2. Pull the map. From the ATV71 Communication Parameters manual, copy for each wanted value — energy, voltage, current — its register address, data format (16-bit or 32-bit, integer or float), engineering unit and scaling. That table is the whole project; Ignition is where it gets typed in.
  3. Set the node address. In the drive's Communications menu, under the MODBUS NETWORK submenu, the parameter Add (Modbus address) is adjustable OFF to 247. Give every drive its own address; a drive left at OFF does not answer.
  4. Configure the Ignition device. With the native Modbus TCP/IP driver, create the device at the card's IP address and TCP port 502, the port registered to Modbus, unless the card's documentation sets a different one, with the unit identifier that documentation calls for.
  5. Read in blocks at one scan rate. Request each documented contiguous range in a single message: the Modbus application protocol specification caps a holding-register read (function code 3) at 125 registers per request. A block that strays into unmapped registers is refused with exception 02, the failure traced in Modbus exception 02 when a read crosses a register map gap. The arithmetic for choosing the scan rate is the one in What decides Modbus TCP polling speed to a CLICK PLC.
  6. Map one known parameter first. Give the tag exactly the address and data type from the manual. A 32-bit value occupies two consecutive registers, and the word order must match the manual; a swapped pair reads as nonsense, the signature of a wrong word-order setting. Ignition's driver also has its own addressing convention, and a tag aimed one register off, or past the top of the map, fails the way it does in Why Ignition Modbus TCP tags read a Click PLC wrong.
  7. Keep it read-only. The hardwired control and shutdown path is the machine's control architecture and stays untouched; a monitoring project maps no command registers, so nothing configured in Ignition can move the drive.
  8. Prove each tag, then add the rest. With the drive in a stable state, compare the Ignition value with the same parameter on the drive's own display; then map energy, voltage and current one at a time, checking each the same way.

Proving one tag: 12 mA on a 4 to 20 mA reference scaled 0 to 60 Hz #

The fastest end-to-end proof uses the one drive input you control directly: the analog speed reference. By the drive's documented behavior, that input maps linearly from the low speed, LSP, at the bottom of the signal range to the high speed, HSP, at the top; with LSP at zero, a 0 to 10 V or 4 to 20 mA reference spans 0 to 60 Hz, the case in the manufacturer's own guidance on ATV61 and ATV71 input scaling.

The inputs:

  • Signal range: 4 to 20 mA on the drive's analog input — the documented range.
  • Drive settings for the test: LSP 0 Hz and HSP 60 Hz — the configuration used in that manufacturer guidance.
  • Test signal: 12 mA from a calibrator — an example test point, chosen because it is exact mid-scale.
  • Where it is read: the drive's frequency reference, at the register the Communication Parameters manual assigns it, seen both on the drive display and in the Ignition tag.

The rule in words: the reference equals LSP plus the signal's position within the span, multiplied by the speed span.

  • Span of the signal: 20 mA − 4 mA = 16 mA.
  • Position of the test point: (12 mA − 4 mA) ÷ 16 mA = 8 ÷ 16 = 0.5.
  • Reference: 0 Hz + 0.5 × (60 Hz − 0 Hz) = 30 Hz.

The drive's reference stands at 30 Hz, so a correctly mapped Ignition tag shows 30 Hz.

The decision: if tag and display agree at that value, the tag's address, data type and scaling are proven, and you move on to energy, voltage and current. Any other reading — zero, full scale, or a number unrelated to the display — is a mapping fault, not a drive or network fault, because the drive itself shows the right value; fix that one tag before adding the next. Only LSP and HSP move the expected number: 12 mA is exact mid-scale, so a correct tag always reads the midpoint of the two speed settings, and once LSP sits above zero the bottom of the signal no longer means zero speed — the exact behavior that scaling guidance exists to explain.

When the values come in wrong #

  • Nothing at all from the drive: a wrong endpoint — card protocol, IP address, unit identifier, a port other than 502 where the documentation says 502, or the node address left at OFF. Link lights prove attachment, nothing more.
  • One value wrong while its neighbors read correctly: that tag — its address, data type, word order on a 32-bit pair, scaling or unit.
  • Values right but frozen: the poll has stopped, or the parameter only updates in a drive state the machine is not in.
  • A gateway route that drops in and out: treat the serial leg as the suspect — routing away from motor leads, termination, shield grounding — before blaming Modbus.

The decision for each installation #

  • The card is, or will be, the Modbus TCP/IP module and the goal is monitoring: poll directly, read-only, with Ignition's native Modbus TCP/IP driver — the right default for a new installation.
  • The PLC already reads these parameters, or can with a program change, and no new hardware is wanted: read through the PLC and leave the drive link untouched.
  • The drive's only channel is serial Modbus RTU and the PLC cannot expose the values: use a gateway and engineer its serial leg as the fragile part it is.

In every case the register map governs. No address, format or scaling is typed into Ignition from anywhere but the drive's Communication Parameters manual, and the hardwired stop chain is not part of the project.

Questions asked

Can the PLC and Ignition both talk to the ATV71 at the same time?

On Modbus TCP, yes: each client opens its own TCP session, and the only real limit is how many simultaneous sessions the communication card supports, a number stated in the card's documentation. Keep the PLC's session and Ignition's read-only session inside that limit. On a serial Modbus RTU link the answer is no, because one master owns the wire, which is why a serial drive is read through the PLC or through a gateway rather than by adding a second master.

Is Modbus RTU over TCP the same as Modbus TCP?

No. Modbus TCP frames each request in a TCP packet with a seven-byte MBAP header and no CRC, because TCP already checks delivery. RTU over TCP wraps the serial RTU frame, CRC included, inside a TCP connection, and its character timing depends on the converter in between. Configure the Ignition device for whichever framing the drive or converter actually speaks; a Modbus TCP device pointed at an RTU-over-TCP converter returns nothing but timeouts.

Can Ignition write to the ATV71 later, for example with a speed command?

Yes, but treat it as a separate project. Writes use function code 6 for a single register or function code 16 for a block, and the command registers sit in the same Communication Parameters manual as the monitoring registers. Two rules before the first write: only one client may command the drive, and the hardwired stop chain stays in place no matter what the software does. A monitoring tag set should contain no writable addresses at all, so a mistaken configuration change in Ignition cannot move the drive.

Keep reading

  • How-to

    Control an ATV12 drive from a TM200 PLC over Modbus RTU

    The ATV12 takes start/stop from register 8601 (CMD) and speed from register 8602 (LFRD, in rpm) once you set Fr1 to Mdb in the CtL- menu and match address, baud, parity and stop bits at both ends. The ladder then writes both words cyclically, one request at a time, gated on completion. Start from the TVDA sample project in Machine Expert Basic.

    Drives and motion

  • How-to

    How to commission five VFD drives on one Modbus gateway

    Prove the link in three passes: open the Modbus TCP connection to the gateway, verify one read from one drive against its own display, then run one serial transaction at a time across all five. A TCP-to-RTU gateway must serialize every RS-485 request, so schedule run commands ahead of power reads instead of polling all five at once.

    Drives and motion

  • Explainer

    Reading SunSpec Modbus devices into SCADA over Modbus TCP

    A standard Modbus TCP driver reads SunSpec devices. SunSpec only defines the register layout: a chain of model blocks starting at the device's documented base address, each block carrying a model identifier, a length, and int16 values you decode with per-block scale factors. The engineering work is block location and scaling, not a new transport.

    SCADA and data logging