Opening a Micro/WIN 2.11 project in Micro/WIN V4.0

PLC programming Published 6 min read

Short answer

Open the project in a Micro/WIN 2.1 editor, deselect Symbolic addressing, switch to the STL view and save; Micro/WIN 2.0 cannot read the 2.11 format, so its ERROR OPENING PROJECT message means the editor predates the file, not that the project is damaged. Then open the saved file in Micro/WIN V4.0 with PRJ selected as the file type and save it as a V4.0 project.

On this page
  1. What the error is and is not
  2. Work on a copy and pin down the versions
  3. Bring Micro/WIN V4.0 to its documented service pack
  4. Convert the project through Micro/WIN 2.1
  5. Worked example: prove the copy byte for byte
  6. Open the converted file in Micro/WIN V4.0
  7. Check the conversion before it touches a machine
  8. When Micro/WIN 2.1 refuses the file too
  9. Questions asked

A STEP 7-Micro/WIN16 2.11 project opens in Micro/WIN V4.0 only after a pass through the 2.1 editor: open it there, deselect Symbolic addressing, switch the view to STL, save, and then open the saved file in V4.0 with PRJ selected as the file type. Micro/WIN 2.0 cannot parse the 2.11 save format, so its ERROR OPENING PROJECT message tells you the editor predates the file; it is not evidence that the project is damaged. Work on a copy, keep the original sealed, and treat the V4.0 open as a conversion that still has to be checked rung by rung.

What the error is and is not #

Three facts define this situation:

  • The project was created with STEP 7-Micro/WIN16 version 2.11, the 1998 build; the program dates from 2000.
  • Opened with Micro/WIN 2.0, the .prj file is refused with ERROR OPENING PROJECT.
  • Opened with Micro/WIN V4.0, the same file is refused with a different opening error; capture its exact text before changing anything.

An opening error is the reader's verdict, not the file's. Version 2.0 cannot parse a 2.11 save, so it fails at the format check before it can judge the contents; the message reports the editor, not the project. V4.0 reads later formats and refuses a raw 2.11 save for a different reason. Two editors, two refusals, one conclusion: the file needs to pass through an editor that both understands the old format and can hand a file to V4.0, which is what the 2.1 bridge below does. The failure shape is not unique to this editor line, either: this walkthrough of a PRJ file that reports an error on open a PRJ file that reports an error on open ends in an editor-version mismatch rather than corruption too.

Work on a copy and pin down the versions #

Nothing in this procedure writes to the original file. Do these four things before any conversion attempt:

  • Copy the .prj file and anything that travels with it into an archive you never open; every attempt below runs on a working copy.
  • Record the filename, the size in bytes, the creation environment and any printed program listing you still have.
  • Read each editor's exact version from its help or about display rather than trusting the shortcut name; Micro/WIN16 2.11 and Micro/WIN 2.0 are different generations and behave differently, as the reported failure shows.
  • If the STEP 7 family naming is part of the fog, the explainer on what STEP 7 is in a PLC project, and which one you need clears it up.

Bring Micro/WIN V4.0 to its documented service pack #

Install the service pack before the conversion attempt. The manufacturer publishes Service Pack 4 for STEP 7-Micro/WIN V4.0, build V4.0.4, on its official support portal as entry 23545703, delivery release dated 19 June 2006, and its guidance for exactly this failure class is to apply the update right after installing V4.0. Get the pack, and any legacy editor, only from that portal or an authorized distributor; retained original installation media are equally legitimate. Matching an exact Micro/WIN build to an S7-200 CPU is its own exercise, and the walkthrough on getting the right Micro/WIN version for an S7-200 CPU 224 shows how that match is made.

Convert the project through Micro/WIN 2.1 #

The bridge editor is Micro/WIN 2.1. It shipped on the same installation media as later Micro/WIN releases, so check any retained media before hunting further. On the working copy, in this order:

  1. Open the .prj file in Micro/WIN 2.1 and let it load; you should see recognizable project contents.
  2. Deselect Symbolic addressing so operands display as direct addresses.
  3. Switch the program view to STL.
  4. Save under a new name, for example PUMP21.PRJ, leaving the archived original untouched.
  5. Close the project and reopen the saved copy in 2.1. If it reopens with the same instruction content you inspected before saving, the bridge file is sound; if not, re-copy from the archive and repeat this section.

Worked example: prove the copy byte for byte #

Say the archived original PUMP.PRJ reads 57,344 bytes. The working copy must read the same: 57,344 − 57,344 = 0 bytes difference. The size also fits a file saved in 2000: 57,344 / 1024 = 56 KiB, and 57,344 / 512 = 112, a whole number of the 512-byte sectors that period floppy and early hard-disk formats allocated, so nothing points to a truncated transfer. If the working copy instead read 57,340 bytes, that 4-byte shortfall means data was lost in copying and the file is not a safe conversion source. These figures are an illustrative example: substitute the byte count your own file reports and apply the same two checks, equality and a plausible sector multiple.

Open the converted file in Micro/WIN V4.0 #

  1. Start Micro/WIN V4.0 and open its project-open dialog.
  2. In the file-type selector, choose PRJ. The dialog defaults to the current format and does not list the legacy file otherwise; this is the step most often skipped.
  3. Select the converted copy and open it, recording any conversion message word for word.
  4. Save immediately as a new V4.0 project so no later work ever touches the legacy file again.
  5. Switch the view back to ladder (LAD) and begin the comparison below.

Check the conversion before it touches a machine #

A clean open proves V4.0 can read the file; it proves nothing about equivalence. Walk the converted program against the original listing: network count, every address, timer and counter numbers and presets, and each contact and coil type. Where V4.0 shows a network as statement list instead of a rung, the STL text is still the complete program, but that rung has to be redrawn in ladder before you trust the visual check. Then the one safety note that matters here: do not download the converted program to a machine that runs until the walk-through is finished and the I/O response has been verified against the original behavior on a bench, because a conversion that opens cleanly can still change how one network executes.

When Micro/WIN 2.1 refuses the file too #

If 2.1, the editor that understands the format, also reports an opening error, the editor route is exhausted and the file itself is the suspect: damage, a partial copy, or a file that is not a 2.11 save despite the extension. Report the exact error text from both editors, both editor versions and the file size to the manufacturer's support, and send a file copy where your company's policy allows it. If the PLC still holds the program, an upload keeps you informed meanwhile, but keep expectations calibrated: uploading a PLC program is not full source recovery, because comments and symbol information do not survive the trip.

Questions asked

Does the .prj extension tell me which Micro/WIN version saved the file?

No. The extension names the file category, not the internal format revision, so a 2.11 save and a V4.0 save can both arrive as .prj files. That is why the migration record matters: note the creation environment, the year the program was developed and the file size in bytes. Those three facts let support, or you, infer the real format when an editor refuses the file.

Where do I get Micro/WIN 2.1 and the V4.0 service pack from a legitimate source?

Retained original installation media first: the 2.1 editor shipped on the same media as later Micro/WIN releases. Service Pack 4 for STEP 7-Micro/WIN V4.0, build V4.0.4, is published on the manufacturer's official support portal as entry 23545703. An authorized distributor can supply media too. Unofficial download sites repack installers nobody can verify, so they are out of bounds for a program that runs a machine.

Why does the converted program show raw addresses instead of my symbol names?

The bridge method deselects Symbolic addressing before the STL save, so the converted file carries direct addresses from that point on. Your symbol names stay in the original archived project, which is exactly why the archive remains sealed. If names matter for maintenance, keep the original project as the reference copy and record the address-to-symbol mapping beside the converted file rather than editing symbols back in on day one.

Can I skip the 2.1 bridge and open the 2.11 file straight in V4.0?

The documented path runs through Micro/WIN 2.1, and a raw 2.11 save was refused by V4.0 in the reported case, so plan on the bridge. Selecting PRJ as the file type in the V4.0 dialog is still required even after conversion; it only controls which files the dialog lists, and it does not repair contents or translate the project by itself.

Keep reading

  • How-to

    How to get the right Micro/WIN version for an S7-200 CPU 224

    STEP 7 V5.4 cannot program an S7-200 CPU 224. The tool for that CPU is STEP 7-Micro/WIN, whose final service packs are V4.0 SP8 and SP9, downloadable from Siemens Industry Online Support entry 58523240 alongside the S7-200 System Manual.

    PLC programming

  • How-to

    Do-more Designer compare PLC project with disk project

    Open the controller project through COMM LINK in one Designer instance and the disk project in a second, release the shared link with PLC->Disconnect or a NEW LINK on Ethernet, and run the PROGRAM Designer's COMPARE from the disk project to walk the differences. Copy the reviewed changes into the controller instance and SAVE-AS the result as the original project name plus _ONLINE_EDITED.dmd. The comparison is interactive only — it writes no report file.

    PLC programming

  • Troubleshooting

    Fix block format not recognised when uploading an S7-200 program

    A completed upload that Micro/WIN V4.0 cannot display means the transfer worked and the parser failed: the block in the CPU belongs to an older toolchain generation. Save the upload untouched, open the original project in the Micro/DOS or Micro/WIN release that created it, and convert a copy in V4.0. Download nothing until the recovered project opens, compiles and matches the block inventory you recorded.

    PLC programming