Selection guide

IO-Link master device version selection for grippers

Industrial networks Published 6 min read By IMDHMI controls team

Short answer

Pick the IODD-supporting device version, 4.11.0.0 or higher, when the scan dialog offers a choice and any connected device needs parameter access through its IODD. Reserve the byte-oriented slot-module revision, 16#00000100 or higher, for projects that rule out IODD files. Every later step follows from that single scan-dialog selection.

On this page
  1. The two versions the scan offers
  2. What the IODD-supporting version unlocks
  3. The per-port power budget
  4. Worked example: a gripper with a 450 mA peak on Ch1
  5. The commissioning sequence after the scan
  6. What the wrong version looks like later
  7. Questions asked

When the scan dialog in the EtherCAT master offers two device versions for a four-channel IO-Link master, the choice is not cosmetic: it decides whether the connected gripper can be parametrized by name or only addressed as raw bytes. Pick the IODD-supporting version, 4.11.0.0 or higher, whenever any device on channels Ch1 to Ch4 needs structured parameter access through its IODD. Pick the byte-oriented slot-module revision, 16#00000100 or higher, only when the project standard rules out IODD files. Loading IODDs, plugging devices, ISDU reads, forwarded diagnostics and the import of real-time data into the PLC project all depend on that one dialog selection.

The two versions the scan offers #

Add the XI510004 4Ch. IO-Link Master to the project and run Scan for Devices in the ctrlX EtherCAT Master. The module sits on the EtherCAT ctrlX I/O line behind the XB-EC-12 bus coupler and appears in the scan below the coupler. The dialog then offers a device-version choice: the two versions describe the same hardware with different structures, and the scan records whichever you pick.

Criterion IODD-supporting version Byte-oriented slot modules
Version to select 4.11.0.0 or higher Revision 16#00000100 or higher
Parameter interface IODD-based read and write, plus ISDU by index ISDU by index only
Process data Named fields from the IODD Raw bytes in slots; the byte layout is yours to document
Device diagnostics Forwarded from the connected devices Module level only
Fit Any connected device that ships an IODD Configurations where IODD support is not required

The decision: a gripper is a parametrized device whose maker publishes an IODD and dedicated PLC blocks, so the IODD-supporting version is the pick. Take the byte-oriented revision only when IODD files are excluded by the project, and then document every parameter index and every process-data byte yourself.

What the IODD-supporting version unlocks #

Load the IODD for every connected device type before you plug anything, because the plug list is built from the loaded files. Two sources carry the files: the IODD finder portal and the device maker's website, where you enter the device code printed on the nameplate. The maker's documentation shows two codes for related grippers, GEP2010IL-03-B and GEP2000IL_43, and the suffix style differs between families, so match the variant exactly and take the IODD and the PLC block for the same variant. The same discipline holds on other fieldbuses: why an IODD file will not plug into a PROFINET IO-Link master walks through what a plug failure looks like on a PROFINET master.

Connect the gripper to one of channels Ch1 to Ch4, navigate to XI510004 → Ch1 in the project tree, and select Plug Device. With the IODD installed, parameters read and write as named fields. For anything outside the predefined list, ISDU reaches the parameter by index: the tool fills in well-known indices for you, so selecting Vendor Name enters 0x0010, and a user-defined index can be typed by hand. A Vendor Name read is the first test worth running on any newly connected device, because that index exists on every IO-Link device and a failed read points to the channel, cable or version choice rather than a gripper-specific parameter. The module's ISDU behavior is covered in more depth in whether the ctrlX I/O XI510004 can read IO-Link ISDU parameters.

For parameter reads straight from a running program, read IO-Link parameters over EtherCAT AoE from a ctrlX PLC shows the same access from the controller side. The gripper maker also publishes two function-block sets, Basic Gripping and Advanced Gripping; download them together with the IODD for the same variant.

The per-port power budget #

Each of the four channels carries its own Class A supply over 3-wire M12 wiring. Class A ports are meant for devices up to roughly 500 mA at 24 V DC; Class B ports add a fifth conductor that feeds auxiliary power to high-current devices, which is why their cables use 5-pin M12 connectors. These channels are Class A, so a device whose peak demand sits above that level does not run from the channel supply alone. For larger grippers and linear axes, the device maker sells the matching auxiliary-supply accessories. Verify the total 24 V DC budget in the cabinet before adding such a supply, because the extra load lands on the same feed as the coupler and the rest of the I/O.

Worked example: a gripper with a 450 mA peak on Ch1 #

The inputs:

  • Gripper peak current at 24 V DC: 450 mA. This is an illustrative example value; take the real figure from your gripper's datasheet.
  • Port class: Class A, one independent supply per channel, four channels on the module (module documentation).
  • Class A level: about 500 mA per port (industry port-class description).
  • Parameter requirement: the gripper ships an IODD and dedicated PLC blocks (device maker documentation).

The rule in words: a Class A channel carries the device on its own while the device's peak current stays under the roughly 500 mA Class A level, and any device described by an IODD forces the IODD-supporting version at scan time.

The arithmetic: 500 mA − 450 mA = 50 mA of headroom on the channel. If all four channels later carry devices of this size, the cabinet supply must deliver 4 × 450 mA = 1800 mA, that is 1.8 A at 24 V DC, for the grippers alone.

The result: the gripper runs from its Class A channel without auxiliary-supply accessories, and the parameter requirement fixes the scan pick at 4.11.0.0 or higher.

The decision: below 500 mA of peak demand, wire the device straight to the channel; above it, fit the maker's auxiliary-supply accessories. Either way, an IODD-described device means the IODD-supporting version in the scan dialog.

The commissioning sequence after the scan #

  1. Run Scan for Devices in the ctrlX EtherCAT Master and select the IODD-supporting device version.
  2. Load the IODD for each connected device type; the plug list builds from the loaded files.
  3. Wire the device 3-wire to one of channels Ch1 to Ch4, per the Class A port.
  4. Under XI510004 → Ch1, select Plug Device and choose the device.
  5. Run a Vendor Name read over ISDU as the first parameter test.
  6. Check the configuration and select Online → Download. The download comes before the import for a reason: the Data Layer offers the module's variables only after the controller holds the configuration.
  7. Open ctrlX PLC Engineering, navigate DataLayer_Realtime → Select realtime data → selectively from ctrlX CORE, enter the controller's IP address if the dialog asks, then select All → Apply. The selected real-time data is then available in the PLC project.

What the wrong version looks like later #

  • No entry under Plug Device for the variant: the IODD is not loaded, or the byte-oriented revision was scanned. Check the recorded scan version and the loaded files against the exact device code on the nameplate.
  • Only raw byte slots appear in the project tree: the byte-oriented revision was selected. Repeat the scan, pick the IODD-supporting version, then re-check every process-data binding made under the old description.
  • A Vendor Name read returns nothing: the device sits on a different channel, the master sees no device, or the index was mistyped. Run the IOL-D scan to confirm detection, then check the cable on the channel.
  • Parameters lost after a device swap: save the device parameter set before the swap with the I/O Connect app's backup and restore for IO-Link data storage, and restore it onto the replacement.

Questions asked

Can you change the device version after commissioning?

Yes. Run the scan again and select the other version of the module in the dialog. Every binding to process data made under the old description then has to be checked again, because the two versions describe the same hardware with different structures. Deciding the version before the first download avoids that rework.

What does ISDU stand for?

Indexed Service Data Unit. It is direct access to one device parameter by its index, used for parameters outside the structured IODD view or for a quick identity check on a newly connected device. The engineering tool fills in well-known indices for you and accepts any user-defined index typed by hand.

Which function blocks exist for the grippers?

The gripper maker publishes two sets for the PLC engineering environment: Basic Gripping and Advanced Gripping. Download the set you need together with the IODD for the same device variant, since names differ between families. Read the function description delivered with each set before choosing; the set you pick determines which gripper functions your program can call.

Keep reading

  • How-to

    Setting up IP67 EtherCAT remote I/O modules on a soft PLC

    Setting up IP67 EtherCAT remote I/O on a soft PLC is four moves: install the vendor's device description XML in the fieldbus configurator's device repository, scan the bus and insert the scanned devices, plug every occupied IO-Link port with its send and receive data allocation, then import the master, ports and channels into the PLC project through the controller's Data Layer and map the raw bytes in the program.

    Industrial networks

  • Explainer

    What an EtherNet/IP IO-Link master exposes to your PLC

    Full access to every port is decided by three documented items: the mode each port is configured in, the master's EtherNet/IP data map, and your PLC's client functions. Process data travels on the cyclic I/O connection; parameters need explicit CIP requests, and at 100 devices polled every 10 ms you would need 10,000 transactions per second, so bulk data belongs on the assembly connection.

    Industrial networks

  • Explainer

    Why the PLCnext IO-Link library will not run with a third-party master

    The PLCnext IO-Link library only runs against Phoenix Contact IO-Link master hardware, so no block or setting makes it drive a SICK or ifm master. IEC 61131-9 standardizes the master port to the device, not the fieldbus layout, so each master's own PROFINET cyclic mapping plus its documented acyclic parameter service is the supported route. The library becomes an option only if the project changes to a Phoenix Contact master.

    Industrial networks