Selection guide
IO-Link master device version selection for grippers
Short answer
Pick the IODD-supporting device version, 4.11.0.0 or higher, when the scan dialog offers a choice and any connected device needs parameter access through its IODD. Reserve the byte-oriented slot-module revision, 16#00000100 or higher, for projects that rule out IODD files. Every later step follows from that single scan-dialog selection.

On this page
When the scan dialog in the EtherCAT master offers two device versions for a four-channel IO-Link master, the choice is not cosmetic: it decides whether the connected gripper can be parametrized by name or only addressed as raw bytes. Pick the IODD-supporting version, 4.11.0.0 or higher, whenever any device on channels Ch1 to Ch4 needs structured parameter access through its IODD. Pick the byte-oriented slot-module revision, 16#00000100 or higher, only when the project standard rules out IODD files. Loading IODDs, plugging devices, ISDU reads, forwarded diagnostics and the import of real-time data into the PLC project all depend on that one dialog selection.
The two versions the scan offers #
Add the XI510004 4Ch. IO-Link Master to the project and run Scan for Devices in the ctrlX EtherCAT Master. The module sits on the EtherCAT ctrlX I/O line behind the XB-EC-12 bus coupler and appears in the scan below the coupler. The dialog then offers a device-version choice: the two versions describe the same hardware with different structures, and the scan records whichever you pick.
| Criterion | IODD-supporting version | Byte-oriented slot modules |
|---|---|---|
| Version to select | 4.11.0.0 or higher | Revision 16#00000100 or higher |
| Parameter interface | IODD-based read and write, plus ISDU by index | ISDU by index only |
| Process data | Named fields from the IODD | Raw bytes in slots; the byte layout is yours to document |
| Device diagnostics | Forwarded from the connected devices | Module level only |
| Fit | Any connected device that ships an IODD | Configurations where IODD support is not required |
The decision: a gripper is a parametrized device whose maker publishes an IODD and dedicated PLC blocks, so the IODD-supporting version is the pick. Take the byte-oriented revision only when IODD files are excluded by the project, and then document every parameter index and every process-data byte yourself.
What the IODD-supporting version unlocks #
Load the IODD for every connected device type before you plug anything, because the plug list is built from the loaded files. Two sources carry the files: the IODD finder portal and the device maker's website, where you enter the device code printed on the nameplate. The maker's documentation shows two codes for related grippers, GEP2010IL-03-B and GEP2000IL_43, and the suffix style differs between families, so match the variant exactly and take the IODD and the PLC block for the same variant. The same discipline holds on other fieldbuses: why an IODD file will not plug into a PROFINET IO-Link master walks through what a plug failure looks like on a PROFINET master.
Connect the gripper to one of channels Ch1 to Ch4, navigate to XI510004 → Ch1 in the project tree, and select Plug Device. With the IODD installed, parameters read and write as named fields. For anything outside the predefined list, ISDU reaches the parameter by index: the tool fills in well-known indices for you, so selecting Vendor Name enters 0x0010, and a user-defined index can be typed by hand. A Vendor Name read is the first test worth running on any newly connected device, because that index exists on every IO-Link device and a failed read points to the channel, cable or version choice rather than a gripper-specific parameter. The module's ISDU behavior is covered in more depth in whether the ctrlX I/O XI510004 can read IO-Link ISDU parameters.
For parameter reads straight from a running program, read IO-Link parameters over EtherCAT AoE from a ctrlX PLC shows the same access from the controller side. The gripper maker also publishes two function-block sets, Basic Gripping and Advanced Gripping; download them together with the IODD for the same variant.
The per-port power budget #
Each of the four channels carries its own Class A supply over 3-wire M12 wiring. Class A ports are meant for devices up to roughly 500 mA at 24 V DC; Class B ports add a fifth conductor that feeds auxiliary power to high-current devices, which is why their cables use 5-pin M12 connectors. These channels are Class A, so a device whose peak demand sits above that level does not run from the channel supply alone. For larger grippers and linear axes, the device maker sells the matching auxiliary-supply accessories. Verify the total 24 V DC budget in the cabinet before adding such a supply, because the extra load lands on the same feed as the coupler and the rest of the I/O.
Worked example: a gripper with a 450 mA peak on Ch1 #
The inputs:
- Gripper peak current at 24 V DC: 450 mA. This is an illustrative example value; take the real figure from your gripper's datasheet.
- Port class: Class A, one independent supply per channel, four channels on the module (module documentation).
- Class A level: about 500 mA per port (industry port-class description).
- Parameter requirement: the gripper ships an IODD and dedicated PLC blocks (device maker documentation).
The rule in words: a Class A channel carries the device on its own while the device's peak current stays under the roughly 500 mA Class A level, and any device described by an IODD forces the IODD-supporting version at scan time.
The arithmetic: 500 mA − 450 mA = 50 mA of headroom on the channel. If all four channels later carry devices of this size, the cabinet supply must deliver 4 × 450 mA = 1800 mA, that is 1.8 A at 24 V DC, for the grippers alone.
The result: the gripper runs from its Class A channel without auxiliary-supply accessories, and the parameter requirement fixes the scan pick at 4.11.0.0 or higher.
The decision: below 500 mA of peak demand, wire the device straight to the channel; above it, fit the maker's auxiliary-supply accessories. Either way, an IODD-described device means the IODD-supporting version in the scan dialog.
The commissioning sequence after the scan #
- Run Scan for Devices in the ctrlX EtherCAT Master and select the IODD-supporting device version.
- Load the IODD for each connected device type; the plug list builds from the loaded files.
- Wire the device 3-wire to one of channels Ch1 to Ch4, per the Class A port.
- Under XI510004 → Ch1, select Plug Device and choose the device.
- Run a Vendor Name read over ISDU as the first parameter test.
- Check the configuration and select Online → Download. The download comes before the import for a reason: the Data Layer offers the module's variables only after the controller holds the configuration.
- Open ctrlX PLC Engineering, navigate DataLayer_Realtime → Select realtime data → selectively from ctrlX CORE, enter the controller's IP address if the dialog asks, then select All → Apply. The selected real-time data is then available in the PLC project.
What the wrong version looks like later #
- No entry under Plug Device for the variant: the IODD is not loaded, or the byte-oriented revision was scanned. Check the recorded scan version and the loaded files against the exact device code on the nameplate.
- Only raw byte slots appear in the project tree: the byte-oriented revision was selected. Repeat the scan, pick the IODD-supporting version, then re-check every process-data binding made under the old description.
- A Vendor Name read returns nothing: the device sits on a different channel, the master sees no device, or the index was mistyped. Run the IOL-D scan to confirm detection, then check the cable on the channel.
- Parameters lost after a device swap: save the device parameter set before the swap with the I/O Connect app's backup and restore for IO-Link data storage, and restore it onto the replacement.
Questions asked
Can you change the device version after commissioning?
Yes. Run the scan again and select the other version of the module in the dialog. Every binding to process data made under the old description then has to be checked again, because the two versions describe the same hardware with different structures. Deciding the version before the first download avoids that rework.
What does ISDU stand for?
Indexed Service Data Unit. It is direct access to one device parameter by its index, used for parameters outside the structured IODD view or for a quick identity check on a newly connected device. The engineering tool fills in well-known indices for you and accepts any user-defined index typed by hand.
Which function blocks exist for the grippers?
The gripper maker publishes two sets for the PLC engineering environment: Basic Gripping and Advanced Gripping. Download the set you need together with the IODD for the same device variant, since names differ between families. Read the function description delivered with each set before choosing; the set you pick determines which gripper functions your program can call.