IMDHMIControls LibraryShop main store

Troubleshooting

HART multiplexer loop resistance on a standard analog input

Controllers and I/O Published 6 min read

Short answer

A HART multiplexer needs 230 to 600 ohms of load between its sensing points, and a conventional 4-20 mA analog input documents far less, so the current reads correctly while HART fails. Add a series resistor sized to land the total inside that band, verify the transmitter still has voltage headroom at full current, select the resistor's power rating with margin, then mount it permanently between the multiplexer's sensing points.

On this page
  1. Why the current reads fine while HART fails
  2. The resistance band and where the resistor must sit
  3. Worked example: sizing the series resistor
  4. Voltage drop and heating at full current
  5. How to fix it
  6. The decision
  7. Questions asked

A HART multiplexer needs 230 to 600 ohms of load between its sensing points, and a conventional 4–20 mA analog input presents far less. The AI 8xI 2-/4-wire BA (6ES7134-6GF00-0AA1), for example, documents an input resistance of 100 ohms on its current ranges. That gap is why the loop current reads correctly while the multiplexer reports a communication error: the current measurement works at almost any burden, but the HART signal does not. The fix is a series resistor sized so the total load lands inside the multiplexer's band, installed between the points the multiplexer actually senses, with the transmitter's voltage headroom and the resistor's dissipation verified first. The steps below take you from diagnosis to a documented, panel-ready installation.

Why the current reads fine while HART fails #

The loop carries two signals on the same pair. The 4–20 mA current is the process measurement. HART superimposes a small frequency-shifted keying voltage on that current, and the voltage a receiver sees is proportional to the resistance in the loop: a modulation current flowing through a low burden produces a voltage below the detection threshold, so the multiplexer flags an error even though the current path and the transmitter are perfectly healthy.

The analog input never sees that problem. It measures the current through its internal shunt and converts it to a number — the conversion chain behind that reading is the same one described in how PLC analog input and output modules convert signals, and none of it depends on HART being decodable.

So treat the symptoms as a diagnostic split. A multiplexer error with a healthy current reading points at communication load, not at a failed transmitter or a dead channel. Detecting a failed analog input channel and reporting it to SCADA is the separate skill for the opposite case, where the current itself disappears. Before you condemn hardware, compare the resistance the multiplexer sees against what it specifies.

The resistance band and where the resistor must sit #

The HART physical layer needs enough loop resistance for the receiver to develop a detectable communication voltage. Published HART guidance puts the usable communication resistance between 230 and 600 ohms, with 250 ohms the common precision value in practice. A multiplexer datasheet applies that requirement to the resistance between its designated sensing points, which the vendor typically describes as the PLC-side load.

Placement matters as much as the value. A HART receiver senses the signal between two specific terminals. A resistor sitting outside the span between those terminals still burns loop voltage, but the modulation voltage it develops never appears where the multiplexer is looking. Read the multiplexer wiring diagram to establish exactly what its stated load includes before you pick a terminal — a verbal description of the resistor being "before" or "after" the multiplexer is not enough.

Worked example: sizing the series resistor #

The total load between the multiplexer's sensing points is the sum of the series resistances it spans. For the documented 100 ohm input plus a 250 ohm resistor added in series:

  • R_total = R_input + R_added
  • R_total = 100 ohms + 250 ohms = 350 ohms

350 ohms sits inside the required band, which matches the reported result: without the resistor the multiplexer errors, with it the multiplexer exchanges data with the instrument.

Solving for the resistor alone, the arithmetic permits any added value from 130 to 500 ohms. That interval is a resistance calculation, not a component selection: input tolerance, resistor tolerance, terminal and cable resistance, and the exact span the multiplexer senses all shift the real number. Aim for the middle of the band so those shifts cannot push you out of range.

Voltage drop and heating at full current #

Voltage headroom is the loop supply voltage left over after every series drop, and it is what the transmitter needs to operate. Adding resistance increases the total drop; it never creates supply voltage. Check it at the transmitter's maximum output current, which on many instruments exceeds 20 mA during an alarm condition — read that figure from the transmitter documentation and use it for the final checks.

At 20 mA, the drops and dissipations for the worked example follow from V = I × R and P = I² × R:

Loop element Resistance Voltage drop at 20 mA Dissipation at 20 mA
Analog input shunt 100 ohms 2 V 0.04 W
Added series resistor 250 ohms 5 V 0.10 W
Combined resistive load 350 ohms 7 V 0.14 W

The added resistor dissipates 0.10 W as an operating point, not a rating. Select a component rated well above it — a resistor terminal or body rated for at least five times that, 0.5 W or more, holds up at panel ambient temperatures with derating margin. Then close the headroom check: the minimum loop supply must exceed the transmitter's minimum operating voltage plus every series drop, including the resistor, the input, cable resistance and any barrier or isolator in the path.

How to fix it #

  1. Read the multiplexer's manual for the required resistance range and the two points between which it senses. Mark those points on your wiring drawing.
  2. Read the analog input's documented input resistance for the range your channel uses, from the module datasheet.
  3. Compute the added resistance: target total minus input resistance. Target mid-band so tolerances cannot push you out of range.
  4. Check the headroom at the transmitter's maximum current, including alarm behavior, against the loop supply voltage.
  5. Select the permanent component: a precision resistor terminal or industrial resistor assembly with a stated tolerance and a power rating at least five times its calculated dissipation, suitable for the panel environment.
  6. Isolate the loop before working on it, and where an intrinsically safe circuit or galvanic isolator is installed, treat the added resistance as a change to that circuit and confirm it against the loop's approved documentation before energizing.
  7. Install and update the drawings and loop identification so the next technician finds the load on paper, not by discovery.
  8. Verify before return to service: measure the sensed-span resistance with the circuit isolated and parallel paths disconnected, inject known currents with approved test equipment and read the drop across the added resistor, confirm HART data exchange in both directions, and check the analog scaling across the span.

The verification reading for the worked example is a resistance of about 350 ohms between the sensing points, within the combined tolerances, and a drop across the added resistor of roughly 1 V at 4 mA and 5 V at 20 mA. If the analog value agrees with the injected current at both ends of the span, the measurement and the communication both hold.

The decision #

For a conventional, non-IS loop with confirmed headroom: install the series resistor permanently between the multiplexer's sensing points, sized to land the total mid-band, as a rated component with updated drawings. That is the correct final design, not a workaround.

If headroom is short: reduce the added resistance toward the band floor, re-check that the drop fits the supply, and re-verify communication with the real transmitter before accepting it — the closer you sit to the floor, the less margin the FSK signal has.

If the loop is intrinsically safe or passes through an isolator: do not install anything until the loop's approved documentation allows the added resistance and the interface is confirmed to pass HART. If the multiplexer still errors with a compliant resistance in place, move the resistor into the span its sensing points actually cover — a resistor outside that span explains an error that survives a correct-looking total.

Questions asked

Why choose a value at the middle of the band instead of just above the minimum?

Mid-band placement buys margin in both directions. Resistor tolerance, the analog input's own tolerance, cable and terminal resistance, and any other series elements all shift the total the multiplexer actually sees. A value near the center of the specified range survives those shifts; a value placed right at the floor can fall out of range once real component tolerances and temperature drift are added, and a value near the ceiling eats loop voltage the transmitter needs.

Does the series resistor change the 4-20 mA reading?

No, as long as the transmitter can still drive full current. A current loop forces the same current through every series element, so the input continues to measure the true process current through its own shunt. The reading degrades only if the added drop exceeds the available headroom: the transmitter then saturates before reaching full scale and the top of the span reads low. That is why the headroom check comes before the permanent install and the scaling verification after it.

Can a handheld HART communicator be used on the loop without the resistor?

A handheld modulates the same loop, so it depends on the same burden as the multiplexer. Connected at the transmitter or at a junction, it still needs the loop resistance in place to generate a detectable signal. Some communicators provide an internal resistor intended for direct connection across a bench loop that has none; whether yours does, and when it applies, is stated in that instrument's manual. On an operating plant loop, keep your series resistor in the circuit.

What if my analog input resistance is not 100 ohms?

Use your module's documented figure and the same subtraction. The added resistance equals your target total minus the input resistance. For example, an input documented at 50 ohms needs 200 ohms added in series to reach a 250 ohm total, and one documented at 300 ohms already sits inside the band and needs nothing added. Read the resistance that applies to the range your channel is actually configured for, because some modules state different values per range.

Keep reading

  • How-to

    Wiring four drives to a shared 1756-OF8 analog return

    Yes, the four drives can share the return, because the 1756-OF8 already shares it internally: every RTN terminal is one common node, so all four loops sit on a single reference. Run a separate return conductor from each 1336 signal common to the module, and give each drive its own output channel.

    Controllers and I/O

  • Selection guide

    Add 4-20 mA analog inputs when the CompactLogix rack is full

    Swap the installed four-channel analog input card for an eight-channel one when channel isolation matches; that adds four inputs against a need of three, with no rack, power-supply or enclosure change. If isolation rules the swap out, reposition the existing power supply to free an end slot. When the cabinet itself is full, add a POINT I/O analog module or IO-Link converters over EtherNet/IP.

    Controllers and I/O

  • How-to

    Amplifying a 0-20 mA PLC output to drive a 165 mA solenoid

    No PLC analog output supplies 165 mA directly: the SM 1232 tops out at 20 mA, so you add a closed-loop current amplifier that draws solenoid power from the 24 V rail. The gain is 8.25, set by an 82.5 Ω input resistor over a 10 Ω sense resistor; a 102 Ω coil drops 16.83 V at full scale, leaving 5.52 V and 0.91 W in the pass transistor.

    Panel wiring and electrical