Getting NX1P2 tags into Ignition without OPC UA
Short answer
On an NX1P2 without OPC UA and without FINS/TCP, connect Ignition with the Omron NJ (EtherNet/IP) driver, set Network Publish on every Sysmac global variable you need, and import the variable list as tags, because neither Omron driver browses. A Bound FINS/UDP device only means the gateway bound its own local UDP port; a read that returns Good quality is the proof.
On this page
- Use the Omron NJ driver, not FINS/UDP
- Why a Bound FINS/UDP device proves nothing
- Create the Omron NJ device in the gateway
- Network-publish every variable Ignition needs
- Import the global variable list as tags
- Example: importing three NX1P2 globals into Ignition 8.1.10
- Prove one boolean end to end
- Which route to take
- Questions asked
An NX1P2 with no OPC UA and no FINS/TCP still reaches Ignition: create an Omron NJ (EtherNet/IP) device in the gateway, set the Network Publish attribute on every Sysmac global variable you need, and import the variable list as tags. Neither Omron driver that connects to this controller supports browsing, so there is no browse to fix — the import is the route. And the Bound status on the FINS/UDP device never proved a connection: it only says the gateway claimed its own local UDP port. The steps below run from device creation to a boolean that moves on both ends of the link.
Use the Omron NJ driver, not FINS/UDP #
Two drivers installed with Ignition can open this controller: the Omron FINS driver, which speaks FINS over UDP, and the Omron NJ (EtherNet/IP) driver. Both connect, and neither browses. An empty browse on a driver that supports browsing is its own fault with its own fix — ControlLogix tags missing from an Ignition OPC UA browse is one we traced separately — but on these two drivers there is no browse to troubleshoot at all.
Choose the NJ driver for named variables. It addresses controller variables by their Sysmac names, which is exactly how the global variable table is organized. The FINS driver addresses memory areas, and its manual examples document memory-area addressing only, with no route to a named global — which is why hand-entered tags against the global variable table came up empty. Decision: named globals go through the NJ driver; keep FINS/UDP only for data that already lives at a memory-area address.
Why a Bound FINS/UDP device proves nothing #
Bound means the gateway succeeded at binding its own local UDP port — the port FINS over UDP uses, 9600. UDP is connectionless: there is no session to establish, so the status carries no information about the controller until a request draws a reply. A device can sit at Bound against an unreachable controller indefinitely.
The two uncertain settings, FINS Source Unit and FINS Destination Network, are fields in the FINS frame header, not connection switches. Mismatched values get requests dropped or answered with an error. The controller's expected values are part of its own FINS setup: the NX-series FINS manual puts the FINS server settings in Sysmac Studio under Configurations and Setup → Controller Setup → Built-in EtherNet/IP Port Settings in the Multiview Explorer, and the client fields must match that setup. The same two fields decide FINS reads from any client, not just Ignition; matching them against an NX1P2 is laid out in fixing Citect SCADA FINS errors to an Omron NX1P2.
If the goal is named globals, stop tuning: no header value turns a named global variable into a memory-area address. Move to the NJ driver.
Create the Omron NJ device in the gateway #
- On the gateway's Devices page, create a new device of type Omron NJ (EtherNet/IP).
- Set the hostname to the NX1P2's IP address — the address configured for the CPU's built-in EtherNet/IP port in the controller project.
- Leave every other setting at its default for the first attempt.
- Save and wait until the device status reads Connected, not merely created. The NJ driver holds an EtherNet/IP session over TCP 44818, so Connected means that session is up — the standard of proof the Bound status never met.
- If it stays faulted, check three things: the IP matches the running project, nothing between gateway and controller blocks EtherNet/IP traffic, and the controller's Ethernet port is enabled in that project. Do not start on tags until the device connects.
Network-publish every variable Ignition needs #
EtherNet/IP symbolic access only reaches variables the controller exposes. In Sysmac Studio, open the global variable table and set the Network Publish attribute on each variable Ignition will read or write. Transfer the project to the controller afterward — the attribute takes effect on the controller with the transfer, not with the save.
Name matching is exact, including case. A variable left unpublished returns bad quality or an unknown-tag result even though the device shows Connected, which reads exactly like the fault chased on the FINS side.
Import the global variable list as tags #
Neither driver browses, so build the tags by import instead:
- In Sysmac Studio, open the global variable table, select the rows Ignition needs, and copy them out with their data types.
- In the Designer, run the tag import and supply the copied list. Each row becomes one tag: the OPC server is the Ignition OPC-UA server, the device reference is the NJ device just created, and the item path is that device name followed by the Sysmac variable name, in Ignition's
[device]nameform. - Confirm every imported tag's device reference points at the new NJ device and every path spells the Sysmac name exactly.
This import moves simple variables by name. Structure-typed globals do not come across as a single tag — their members have to be handled individually, and that behavior on an NJ is its own case, covered in why structure tags are missing from HMI tag import on an NJ.
Example: importing three NX1P2 globals into Ignition 8.1.10 #
Inputs:
- Controller: an NX1P2 with no OPC UA and no FINS/TCP, programmed in Sysmac Studio — the desk case this article answers.
- Ignition: version 8.1.10 with the Omron drivers installed — the reader's own install.
- Device: one Omron NJ (EtherNet/IP) connection named
nx1p2_line1; an illustrative name of my own, not a documented one. - Variables: three network-published globals from the Sysmac global variable table —
Conv_Run(BOOL),Part_Count(DINT),HMI_Speed(REAL); illustrative names and types.
Rule: one imported row creates one Ignition tag addressed by that variable's Sysmac name, and a row reads Good only when its variable is network-published and the tag path spells the name exactly.
Arithmetic: rows copied from the global variable table: 3; rows imported: 3 × 1 = 3 tags created; tags still to address by hand: 3 - 3 = 0. After the project transfer and an online toggle of Conv_Run: tags reading Good: 3 of 3 = 100%; tags reading Bad: 3 - 3 = 0.
Result: all three tags track the controller — Conv_Run follows the toggled bit, and Part_Count and HMI_Speed return values with their types intact (a DINT is a 32-bit signed integer and a REAL is 32-bit floating point).
Decision: with 3 of 3 Good, build screens and scripts against the imported set. The threshold separating the two faults: on a Connected device, 1 Bad tag of 3 points at that one variable — a missing Network Publish attribute or a spelling mismatch — while 3 Bad of 3 point back at the device connection.
Prove one boolean end to end #
Run this once before building anything on top of the imported tags:
- Toggle the boolean online in Sysmac Studio, or from program logic, and confirm the Ignition tag value follows within a scan or two.
- If the tag is writable, write the opposite value from the Designer's tag editor and confirm it in the Sysmac Studio watch window.
- Unplug the cable briefly: quality must drop, then return to Good when the link comes back — quality following the link is the proof.
- Repeat once with a non-boolean variable to confirm the import mapped its data type.
One safety note: an imported tag is writable from the SCADA side, so keep operator writes on variables meant to receive them and keep them out of interlocks — putting standard tags into a safety program is a mapped, reviewed exercise of its own, covered in mapping standard PLC tags into a safety program.
Which route to take #
For a Sysmac project with named globals on an NX1P2 without OPC UA or FINS/TCP, the route is fixed: Omron NJ (EtherNet/IP) device, Network Publish on each needed variable, project transfer, then import of the variable list — on the desk case, the imported tags worked with no further edits once the device connected. For data that already lives at memory-area addresses, FINS/UDP stays usable: match FINS Source Unit and FINS Destination Network to the controller's FINS setup and judge the link only by a Good read. Both routes share one test — one read, Good quality, the value matches the controller.
Questions asked
Can I browse NX1P2 tags in Ignition without OPC UA?
No. The Omron NJ (EtherNet/IP) driver and the FINS driver over UDP both need tags addressed by hand or brought in by import; neither lists the controller's variables. A browse only shows what a controller itself publishes for a client, and this NX1P2 publishes neither an OPC UA address space nor a browsable tag list to either driver. Publish the globals and import the names instead.
Does Bound on the FINS/UDP device mean the controller answered?
No. Bound is the gateway reporting that its own local UDP port opened; UDP keeps no session, so the status says nothing about the controller. It also stays Bound through the whole fault: a mismatched FINS header shows up as errors or silence on reads, not as a status change. The first real proof is one read of a network-published variable returning Good quality.
Can the Omron NJ driver reach an NX1P2 with no FINS/TCP?
Yes. EtherNet/IP is a separate protocol from FINS, and the NJ driver never opens a FINS/TCP session. A controller that serves FINS over UDP only still exposes its named variables over EtherNet/IP, provided the transferred project has those globals set to Network Publish and the names in Ignition match the Sysmac spelling exactly.
What happens to imported tags after a Sysmac Studio variable rename?
The tag breaks. Ignition addresses the variable by name, so after a rename the imported tag points at a name the controller no longer holds and its quality goes bad until the tag is re-imported or its path is edited to the new name. Rename in Sysmac Studio and update the tag provider in the same change so nobody builds on a dead tag.
Does this route need extra hardware on the controller?
No. It uses the CPU's built-in EtherNet/IP port that already serves the network, the Network Publish attributes, and a project transfer. Nothing is added to the cabinet and no controller-side server is switched on beyond what the transfer itself sets. The OPC UA server other integration routes rely on simply never enters this path.