Troubleshooting
Fix Modicon 984 outputs that stay off in ProWorx32
Short answer
When every BDAP-210 output stays off while ProWorx32 shows the coils ON, treat it as one shared fault, not four dead modules: verify the Traffic Cop output assignment, then the CPU-to-I/O link, then the 124 VAC source power measured at the module. Logic solved on screen never proves the command reached the terminal.
On this page
Logic coils go ON in ProWorx32 while every BDAP-210 output point stays dark: treat that as one shared fault, not four modules that died together. Work the shared path in order — the Traffic Cop output assignment, the CPU-to-I/O link, and the field power at the module's source terminals — before you condemn any hardware. The 984 solves logic and talks to your programming laptop over one path while output data travels out to the racks over another, so a coil that reads ON proves the logic, never the terminal. Inputs that update while outputs do not put the fault squarely on the output side of that shared path.
What the symptom set proves #
Your machine arrived from another site on a new power feed, the 984-A131 boots, ProWorx32 goes online, discrete inputs follow every button and selector switch, and four BDAP-210 modules never move a point — by LED or by voltage at the terminal. Three facts follow.
First, the CPU, the user program, and the programmer link are healthy, because you watch logic execute. Second, the input path from field device to CPU is healthy, because you watch inputs change. Third, the break sits between solved logic and the output terminals. Four modules failing independently at the same moment is the least likely explanation on the table; one unmapped output block, one dead CPU-to-I/O link, or one lost shared source feed explains every dark point at once. The same gap between a software command and a switched terminal shows up when you trace an HMI command that never reaches the PLC output; here the break sits one stage further down, between the CPU and the output modules.
Check the Traffic Cop assignment first #
Traffic Cop is the I/O map in the ProWorx32 project: it ties each output reference in logic to a rack, a slot, and a point on a configured module. The online coil monitor reads logic memory, so a coil shows ON whether or not its reference is mapped to the point your load is actually wired to. After a relocation, that is the cheapest defect that reproduces this exact symptom.
- Record the output references that turn ON in the online monitor.
- Open Traffic Cop and confirm each of those references lands on the rack, slot, and point where its BDAP-210 physically sits now — not where it sat before the move.
- Confirm any drop or rack address settings on the hardware still agree with the map; a rack handled during the move can come back on a different address than the project expects.
- Where the map and the installed layout disagree, correct the map to match the layout, one assignment at a time, then retest.
Change one assignment per test. Fixing several at once tells you the machine runs again; it does not tell you which correction mattered.
Check the CPU-to-I/O link second #
The 984's programmer communication and its I/O scanning are separate functions. The CPU can serve ProWorx32 all day while the link that carries output data to the racks is down, which is why the online view looks completely normal. In systems of this class that connection is a module such as an S410 — identify the actual module and cable from your system documentation before testing anything.
- Read the controller and link status indications. The compact 984 manual's stopped-error table lists CPU to I/O Communication Failure at code 0x0008; if the controller logged it, no output test means anything until the link is restored.
- The same table lists NODETYPE, illegal node type used, at 0x0004 — what a rack or module sitting where the configuration does not expect it looks like after a move.
- Reseat and inspect every connector on that link that the relocation disturbed, then clear the indication and retest.
Now the decision your input data already makes for you: the inputs update. If the BDAP-210s share a rack or drop with the working input modules, that drop is alive — concentrate on the assignment and on module source power. If the four output modules sit in a rack of their own, that rack's drop address and its cable are the single most probable cause of the whole symptom, and that is where you work next.
Verify source power at each module #
A discrete output module is a switch: it applies the field power wired to its source-power terminals, and having how discrete PLC I/O modules isolate and switch field signals straight in your head keeps this part fast. Two defects hide here after a move:
- One shared feed lost — a tripped protective device or a conductor that never got re-landed darkens all four modules at once, which is why you measure at each module's source terminals, not once at the panel.
- An open return or common — the module can show a healthy source voltage and still switch nothing.
Measure with the outputs commanded and check the reading against the module nameplate. The worked check below settles whether the voltage you already measured is the problem; it is not.
Worked check: 124 VAC at the source terminals of a moved machine #
Inputs, with units and where each comes from:
- Measured at the BDAP-210 source-power terminals with your meter at the machine: 124 VAC.
- Nominal North American single-phase service voltage: 120 VAC.
- ANSI C84.1 Range A utilization band for a 120 V nominal system: 110 to 125 VAC — the band 60 Hz equipment is expected to operate within at the point of use.
Rule in words: compare the measured voltage against the nominal and against the Range A utilization ceiling. A reading inside the band with margin is not the cause of dark outputs; a reading at or above the ceiling means you stop and verify the module's rated range before any further testing.
Arithmetic:
- Deviation from nominal: 124 VAC − 120 VAC = 4 VAC high.
- As a percentage: 4 ÷ 120 × 100 = 3.3 % above nominal.
- Margin to the Range A utilization ceiling: 125 VAC − 124 VAC = 1 VAC.
Result: the supply sits 3.3 % above nominal and inside the Range A band, with 1 VAC of headroom.
Decision: cross supply voltage off the list — 3.3 % high does not darken four modules while the logic runs. Had the reading been above 125 VAC, you would instead verify the BDAP-210 nameplate range before forcing any test. Either way, re-measure with the outputs commanded so the reading is under load, not open-circuit.
The one-point test that separates the causes #
One safety note first: a forced output on a freshly moved machine is live machine motion — isolate the loads or confirm everyone is clear before you force anything.
Pick one correctly mapped output, force it, and read three things: the coil, the module LED, and the voltage at that output terminal relative to the circuit return. Record all three, then release the force.
| You observe | Where the fault is | Next move |
|---|---|---|
| Coil ON, LED off, all four modules dark | Command never reaches the modules | Assignment or CPU-to-I/O link; work the two sections above |
| Tested module's LED follows, terminal stays dead | Module output stage or its terminal wiring | Re-terminate; if it persists, that module is your one suspect |
| Terminal switches, load stays dead | Field side: the load, its return, its overload | Fix the load circuit; the module is healthy |
| One module dark while a neighbor on the same map responds | That module or its own source feed | Its source terminals and its wiring |
Order of work #
- Read the controller and link status; note any logged CPU-to-I/O or node-type error.
- Verify Traffic Cop against the installed rack layout.
- Verify drop and rack addresses and reseat every disturbed connector on the CPU-to-I/O link, starting with any rack that holds only outputs.
- Measure source power at each BDAP-210; reset or repair the shared feed if it is missing.
- Run the one-point test and record coil, LED, and terminal voltage.
- Only now evaluate a module for replacement — and only the one whose LED ignores a confirmed, correctly mapped force while its neighbor responds.
Four dead modules after a move is a mapping, link, or wiring problem until the one-point test says otherwise. Replacing the BDAP-210s before that test buys you four spare modules and the same dead machine.
Questions asked
Does the 124 VAC reading rule the supply in or out?
Out as the cause, in as a working supply. 124 VAC is 3.3 percent above the 120 VAC nominal and 1 VAC below the 125 VAC top of the ANSI C84.1 Range A utilization band, so it does not explain four dark modules. Read the BDAP-210 nameplate when the panel is next open, and re-measure with the outputs commanded so the reading is taken under load.
What does error code 0x0008 mean on a compact 984?
CPU to I/O Communication Failure, from the compact 984 manual's stopped-error table. If the controller logged it, the path between the CPU and the I/O hardware is down, and no output test is meaningful until the link is restored. With your inputs still updating, that points you instead at the output assignment or at the one rack that holds the output modules.
Could all four BDAP-210 modules have failed at once?
Not as a first conclusion. Four output modules failing simultaneously after a relocation is far less likely than one shared cause: an I/O map that no longer matches the racks, one dead CPU-to-I/O drop, or one lost source-power feed. Condemn a module only after its LED ignores a confirmed, correctly mapped force while a neighboring module on the same link responds.
The program never changed, so why check Traffic Cop?
Because the project can be unchanged while the hardware moved around it. A drop cable landed on the wrong connector, a rack address disturbed in handling, or a module reseated one slot over all break the agreement between the map and the plant. Assignment, installed layout, and link state are three separate facts after a move, and each one needs its own check.
Does running ProWorx32 version 2.1 SP1 on an old laptop matter here?
No. You are online, watching coils solve and inputs change, which proves the laptop, the software, and the programmer link are all doing their job. The dead outputs sit on the CPU-to-I/O side of the controller, which that laptop never touches. Rule the toolchain out and spend the time on the map, the link, and the source power.