Fix a FANUC robot CIP Safety fault after adding a second robot
Short answer
Change the Time field in the Safety Configuration Signature from the 1:00:00am shown in the FANUC setup video to 12:00:00am and re-apply the Safety Network Number; that cleared the fault in a reported two-robot cell. Give each robot its own IP address and module entry, and convert PLC 8-bit sizes to robot 16-bit words — 44 becomes 22.
On this page
- Why does the first robot fault when you download changes for the second?
- Do you have to set up both robots at the same time?
- What does each robot need in the PLC?
- What settings replace the AOP in a Generic Ethernet Module?
- Why does 44 in the PLC become 22 on the robot?
- How do you change the Safety Configuration Signature time?
- What do you check after the final download?
- Questions asked
When a second FANUC R-30iB Plus robot on one Compact GuardLogix faults the first robot's CIP Safety connection at download, the fix is one field: the Time in the Safety Configuration Signature goes to 12:00:00am, not the 1:00:00am shown in the FANUC setup video, and the Safety Network Number is re-applied with the Set action in the Add-On Profile. Around that fix, each robot needs its own IP address on Port 2 (with option R713 installed) and its own PLC module entry, and PLC 8-bit sizes must be converted to robot 16-bit words. The values here come from a reported working two-robot cell and from FANUC's and Rockwell's setup documentation, scoped to that arrangement.
Why does the first robot fault when you download changes for the second? #
The Safety Configuration Signature Time was set to 1:00:00am, the value shown in the FANUC setup video; changing that field to 12:00:00am and re-applying the Safety Network Number restored both robots in the reported cell. The signature is the culprit, not the wiring.
The symptom pattern points there: robot 1 communicated fully, and its safety connection faulted the moment the PLC changes for robot 2 were downloaded. FANUC's procedure builds the robot side against a fixed signature, and the PLC side presents a value built from the configured date and time. A Time field with a nonzero component lets that value move between downloads; midnight pins the time component at zero, so what the PLC presents stays put for both robots. The reported outcome matches: 1:00:00am faulted on the second download, and the zero-time value ran both robots from then on.
Treat the cell as down while a CIP Safety connection is faulted — that robot's safety function is unavailable until the connection is healthy, and the finished two-robot configuration still needs its own validation against the machine's risk assessment.
Do you have to set up both robots at the same time? #
No — each robot is an independent safety endpoint, and the reported cell was commissioned one robot at a time; what you cannot do is let a download for robot 2 change the identity or the signature that robot 1 already trusts.
Before touching safety settings, clear the physical path for each robot separately:
- Link status at the robot's Ethernet interface, at the cell switch, and at the PLC's Ethernet interface.
- One unique IP address per robot, differing in the last octet.
- The switch path from each robot to the PLC, with no duplicate address anywhere on it.
- Each PLC module entry resolving to the robot it names.
Trace each connection on its own: robot Ethernet interface, cell switch, PLC Ethernet interface, configured module. A signature change cannot repair a dead link, so this layer comes first. On a cell that runs a different safety protocol, the connection checks differ; why an FSoE connection is not established on a safety PLC covers that protocol's version of the same diagnosis.
What does each robot need in the PLC? #
One module entry per robot, each resolving to that robot's unique IP address and carrying its own module name; the shared PLC never means a shared identity, and the connection parameters match only when both robots move the same I/O count.
Use the FANUC Add-On Profile (AOP) when it installs: it is the documented path in FANUC's procedure, written against robot software V9.40, and it is what the working cell used. Configure a separate module entry for each robot, matching the entry to the robot's IP address and mapped I/O sizes. When the sizes are correct on both sides, apply the AOP's Set action for the Safety Network Number before downloading.
Decision: the AOP is the plan, and the Generic Ethernet Module is the fallback, not the first choice.
What settings replace the AOP in a Generic Ethernet Module? #
Assembly instances 101 for input, 151 for output and 100 for configuration, with sizes 2, 2 and 0 in one working application and a communication format of Data - Dint — the fallback one engineer settled on after the specific FANUC module would not connect on the Allen-Bradley side.
| Setting | Reported value | Commissioning rule |
|---|---|---|
| Input / output / configuration assembly instance | 101 / 151 / 100 | Belongs to the Generic Ethernet Module arrangement only |
| Input / output / configuration size | 2 / 2 / 0 | Example map; match your robot's actual I/O map |
| Communication format | Data - Dint | Match the module configuration |
| Module name and last IP octet | Different for each robot | Never shared between robots |
The 2 / 2 / 0 sizes are that application's map, not a universal value: converted the way the next section shows, 2 × 8 bit = 16 bit, which is 1 word on the robot side. For another device on the same module type, sizing a Generic Ethernet Module connection for WAGO 750 I/O walks through how that connection size is worked out. Decision: fall back to the generic module only when the AOP will not install or connect, and keep one module entry per robot either way.
Why does 44 in the PLC become 22 on the robot? #
Because the PLC takes sizes in 8-bit units and the robot takes them in 16-bit words: 44 × 8 bit = 352 bit, and 352 bit ÷ 16 bit per word = 22 words — copy the number without converting and the connection fails or the mapped data is wrong.
Worked example, using the documented example mapping:
- PLC side, input size: 44 (8-bit units).
- Convert: 44 × 8 bit = 352 bit.
- Robot side, input size: 352 bit ÷ 16 bit per word = 22 words.
- Check both ways: 22 words × 16 bit per word = 352 bit = 44 × 8 bit.
Check the input and output directions independently, and compare each side's configured size against the intended map before you apply the Safety Network Number. A size mismatch shows up as a connection that will not open or as data that lands in the wrong place.
How do you change the Safety Configuration Signature time? #
Open the Safety Configuration Signature settings for the faulting robot, change the Time field from 1:00:00am to 12:00:00am, re-apply the Safety Network Number, download, and watch the connection recover — that one field change cleared the fault in the reported cell.
- Record the fault text from the robot and from the PLC module diagnostics before changing anything.
- Open the Safety Configuration Signature settings for the affected robot's configuration.
- Read the Time field: 1:00:00am is the setup-video value, and the one that faulted in the two-robot cell.
- Change the Time field to 12:00:00am.
- Apply the Set action for the Safety Network Number so both endpoints present the same value.
- Download, then check both robots' safety connection states, not only the robot you edited.
Decision: if both connections recover and hold through a repeat download, the signature time was the fault. If they do not, stop changing settings, capture the exact fault indication, and compare the two module entries side by side before the next edit.
What do you check after the final download? #
Both robots together: each module entry's diagnostics healthy, each I/O map updating in its intended direction, and the Time field still reading 12:00:00am after a project save and reload — a check on one robot alone proves nothing about the second.
- Both module entries side by side: IP address, module name, I/O sizes and safety settings, confirming robot 2's edits never overwrote robot 1's.
- Each module's diagnostics showing a healthy connection to its own robot, with both robots active on the shared PLC at the same time.
- Each mapped I/O table moving in the direction it was configured for.
- The Time field unchanged at 12:00:00am after the project is saved, reloaded and downloaded again.
Repeat the checks after any later edit to either robot. Faults that originate in the safety I/O rather than the network are a different layer; how fail-safe I/O modules detect their own faults covers that diagnosis. The decision for the reported case: two R-30iB Plus robots, one Compact GuardLogix, AOP-configured module entries, unique addresses, converted sizes, and the zero-time signature — both safety connections held through repeated downloads.
Questions asked
What does the robot side need before CIP Safety will run?
FANUC's R-30iB Plus CIP Safety setup material covers option R713, Port 2 on the controller, DCS signatures and the SNN, and the Add-On Profile procedure was written against robot software V9.40. Confirm the option is installed and Port 2 is configured before you troubleshoot the PLC side.
What is the Safety Network Number made of?
Rockwell's ControlLogix 5590 controller documentation defines the time-based format as the date and time the number was generated, taken from the clock of the computer running the configuration software. That structure is why a nonzero Time field can move the value between downloads, and why midnight, with its zero time component, stays put.
Can one Compact GuardLogix own both safety connections?
Yes. The reported cell runs two R-30iB Plus robots on one Compact GuardLogix, each with its own module entry, IP address and mapped sizes. The PLC carries multiple safety connections; the constraint is that each endpoint's identity and signature stay distinct and stable across downloads.
Is 12:00:00am required for every FANUC-to-GuardLogix safety link?
Use it for this arrangement: R-30iB Plus robots on a GuardLogix, configured with the FANUC AOP or the 101/151/100 generic module. The 1:00:00am value from the setup video faulted in the two-robot cell, the zero-time value held, and it costs one field entry to set first.