Industrial networks Published 4 min read

Short answer

On a Micro850, the MAC address is the Ethernet (MAC ID) address printed on the side label, and it is also the twelve characters after the hyphen in the device name that an EtherNet/IP browse shows in RSLinx. A MicroLogix 1100 carries its fixed MAC on the side label too. Take the serial numbers from the nameplates: the documented software path returns the MAC, not the serial.

On this page
  1. What each nameplate carries
  2. Read both numbers in five steps
  3. Worked example: check a browse against a label
  4. When logic needs the MAC
  5. Decide by what the number is for
  6. Questions asked

Both numbers live on the controller, and one of them also travels on the network. A Micro850 prints its Ethernet (MAC ID) address on the side label and repeats that MAC in the device name it answers a browse with: the product type 2080LC50, a hyphen, then twelve characters that are the MAC. A MicroLogix 1100 carries its MAC on the side label of a unit whose MAC is fixed and whose IP is settable. The serial number on both controllers comes from the same nameplate — read it at the panel, because the documented software path returns the MAC, not the serial.

What each nameplate carries #

Controller MAC address Serial number
Micro850 Side label, printed as the Ethernet (MAC ID) address Same nameplate, beside the catalog number
MicroLogix 1100 Side label; fixed for the life of the unit Same nameplate, beside the catalog number

The manufacturer's procedure for setting a Micro800 Ethernet address starts at this label: record the Ethernet (MAC ID) address from the side of the Micro850 before touching BOOTP or Connected Components Workbench. The Micro830 and Micro850 user manual defines the device name used on the network as two parts, product type and MAC address, separated by a hyphen — 2080LC50 followed by the twelve MAC characters is the example it gives. That is why the same twelve characters appear on the hardware and in software.

Read both numbers in five steps #

  1. Stand at the panel and copy the twelve characters of the Ethernet (MAC ID) address from the Micro850 side label exactly as printed, leading zeros included.
  2. Copy the serial number from the same nameplate, beside the catalog number, into the asset record for that one physical unit.
  3. Repeat both reads on the MicroLogix 1100 side label; its twelve characters are the MAC that port keeps for its life.
  4. At the desk, open RSLinx and browse RSWho over the EtherNet/IP driver. The Micro850 answers with its device name — product type, hyphen, MAC — so the characters after the hyphen must match the step 1 note exactly.
  5. If the 1100 never appears under the driver, suspect the browse before the controller, and work through why RSLinx shows no processor name for a MicroLogix 1100.

A missing or painted-over Micro850 label costs nothing: the browse in step 4 prints the full MAC. On a MicroLogix 1100 still asking the network for an address, the BOOTP/DHCP utility used to set these controllers' IP addresses lists it by MAC while it waits.

Worked example: check a browse against a label #

All values in this example are illustrative. An RSWho browse returns a device named 2080LC50-001B634A2FC1. Remove the product type 2080LC50 and the hyphen: 001B634A2FC1 remains. Count the characters — 0, 0, 1, B, 6, 3, 4, A, 2, F, C, 1 — twelve, which is 12 / 2 = 6 octets and 6 x 8 = 48 bits, the exact length of a MAC.

Written in pairs the way labels print it: 00:1B:63:4A:2F:C1. The side label of that controller reads 00:1B:63:4A:2F:C1, so the label and the network agree and either source can go into the record. The whole device name is 8 characters + 1 hyphen + 12 characters = 21 characters, so anything shorter lost a digit in copying. If a single character differs, you are looking at two different controllers — find the spare Micro850 in the panel before the value goes into a switch allow-list.

When logic needs the MAC #

Connected Components Workbench can put the MAC into the program: Rockwell Automation support answer 1140440 publishes sample code that reads the MAC address of a Micro800 controller, so a startup routine can compare the connected controller against an expected value. The serial number has no equivalent documented read on these controllers — the nameplate is the source. On other platforms the address hides in memory instead of on the label, and reading a CP1W-CIF41 IP address from PLC memory over USB is that same job on an Omron expansion card.

Decide by what the number is for #

  • Asset record, warranty or repair case: the serial number, from the nameplate, one value per physical controller.
  • Switch allow-list, DHCP reservation or an Ethernet devices driver entry: the MAC, from the label, confirmed against the RSWho device name on a Micro850.
  • A check inside the program: the MAC again, through the Connected Components Workbench sample code in support answer 1140440.
  • Destroyed label: Micro850, the browse; MicroLogix 1100, the BOOTP/DHCP utility while the unit still requests an address.

Questions asked

Where is the MAC address label on a Micro820?

On the front of the controller. The manufacturer's procedure for setting a Micro800 Ethernet address has you record the Ethernet (MAC ID) address from the front label of a Micro820, and from the side label of a Micro850, so on the smaller controller check the face of the unit first.

Is the PLC series number the same as the serial number?

Often that is what is meant, but the two are different fields. The catalog number names the model you ordered and matches the manual; the serial number names the one physical unit, and it is what a warranty or repair case asks for. Record the serial from the nameplate against the controller's panel location.

Can the MicroLogix 1100 MAC address ever change?

No. The Ethernet port has a fixed MAC address and a settable IP address, so re-addressing the controller never touches the MAC. The value changes only when the hardware is swapped, and any switch allow-list, DHCP reservation or driver entry keyed to the old MAC has to be updated after that swap.

Why does my controller not appear in the BOOTP/DHCP utility?

The utility sees only controllers asking the network for an address. A MicroLogix 1100 or a Micro800 already set to a static IP sends no BOOTP request, so it never joins the list even though it is on the wire. For those units, read the side label or browse with an EtherNet/IP driver instead.

Does Connected Components Workbench display the serial number?

The documented identity path in Connected Components Workbench reads the MAC address; Rockwell publishes the sample code as support answer 1140440. There is no equivalent documented read that returns the unit's serial number on these controllers, so capture it from the nameplate while you are standing at the panel.

Keep reading

  • How-to

    Why RSLinx shows no processor name for a MicroLogix 1100

    The MicroLogix 1100 Ethernet port reports its IP address and module type to RSWho, not the processor name, and no RSLinx or controller setting changes that. Label machines by creating one Ethernet Devices driver per machine, named for the machine, holding only that machine's addresses in its station mapping.

    Industrial networks

  • Selection guide

    Connecting ControlLogix to RS232 and RS485 serial devices

    Convert the RS232 devices to RS485 at the electrical layer, then pick one master for the whole pair: 1734 ASCII modules for fixed-length or delimited frames, an in-chassis Modbus RTU module for a pure Modbus bus, or an EtherNet/IP-to-serial gateway with a protocol builder when variable-length checksummed frames share the wire with Modbus RTU. One master serializes every transaction behind the 3.5-character silent gap, 3.65 ms at 9600 baud.

    Industrial networks

  • How-to

    Reach a CompactLogix through a ControlNet bridge in RSLinx

    When autobrowse through a 1784-U2CN ControlNet path lists the bridge's EtherNet/IP module but no CompactLogix or third-party EtherNet/IP devices, add the target IP address manually under that module's Ethernet port in RSWho or the FactoryTalk Linx browse tree, then select the resulting device as the online path in the Logix programming software. The devices are reachable; only discovery fails, and a manual entry needs no discovery.

    Industrial networks