Feed one 4-20 mA transducer to a drive and a panel meter
Short answer
Put the transmitter, the drive's current input and the panel meter in one series loop: the transmitter regulates the current and both receivers read the same true signal. Do not feed the meter from the drive's analog output — it repeats a drive quantity, adds conversion error and goes dead with the drive. Set the drive's frequency source to the analog input, select the 4-20 mA range, and scale the meter over the same span.

On this page
Run the transducer, the drive and the panel meter on one current loop, wired in series. A two-wire transmitter regulates the loop current, so the drive's analog input and the meter's input each see the identical current, and both displays agree without any conversion sitting between them. Do not feed the panel meter from the drive's analog output. That output repeats a quantity the drive generates — output frequency, output current, and similar — so a meter hung on it shows a drive value instead of the process value, carries the drive's conversion error, and goes dark whenever the drive is powered down. On the GS3 the parameter work is short: set the frequency command source to the current analog input, select that input's 4-20 mA range, and map the input's live-zero and full scale to the drive's minimum and maximum frequency.
Wire the loop in series through both receivers #
A two-wire process transmitter behaves as a current regulator powered by the loop itself: it throttles the current between a live-zero of 4 mA and a full scale of 20 mA, and every device wired in series with it sees exactly that current, because a series circuit gives the current no other path. That is the whole argument for the topology — one transmitter, one true signal, and two receivers that cannot disagree.
Wire the string from the loop supply's positive terminal back to its negative:
- Transmitter: plus to minus per its terminal drawing.
- Drive: into the current-capable analog input — the GS3 manual's analog-input example uses the AI2 terminal — and out through the drive's analog common.
- Meter: into the panel meter's current input positive terminal, out of its negative.
- Loop supply: the negative terminal closes the loop.
Polarity decides everything: current must enter each receiver's positive terminal, and one reversed receiver reads nothing useful. Use shielded twisted pair for the loop, land the shield at one end only, and keep the loop away from the drive's output cables.
The two receivers sit in the transmitter's way as resistances. Add the drive input's resistance to the meter input's resistance and keep the sum inside the maximum loop resistance the transmitter's datasheet states for the supply voltage you chose. If the sum is too big, the loop hits the supply's limit before full scale: every receiver ceilings at the same fraction and the display stops rising below the transmitter's maximum. Fix that with a higher loop supply inside the transmitter's rated range, or with an active conditioner — never by re-scaling a receiver to hide the ceiling.
Isolate the drive and the loop supply and verify with a meter that the terminals are dead before landing wires; the control circuit is live whenever the drive is powered. To prove the string before the transmitter arrives, drive it with a loop simulator in two-wire transmitter mode so it sinks current from the loop supply, which is the requirement behind why a loop simulator needs a current sink output.
Set the drive parameters on the GS3 #
The GS3 user manual's analog-input section includes parameter examples, and one of them makes the output frequency follow a 4-20 mA signal on the AI2 terminal. Copy that example's shape: set the frequency command source to the analog input, set the wired terminal's input range to current, and map the input's live-zero to the minimum frequency and its full scale to the maximum frequency.
The quick reference lists the possible frequency sources: three analog inputs, the keypad's up and down keys, or the RS-485 serial port. Only the selected source drives the output frequency, so after wiring the string, confirm the source points at the terminal you wired — a drive left on keypad or serial source ignores the transmitter completely. The same inputs also accept voltage (the manual's input list includes 0-5 VDC selections), so make sure the wired terminal is set for current, by parameter or hardware selection exactly as the manual describes.
Scale the panel meter over the transmitter's documented span — live-zero at process zero, full scale at the transmitter's maximum — and both devices track the same current independently. Nothing in the meter needs the drive, and nothing in the drive needs the meter.
Why the drive's analog output is the wrong source #
The GS3's analog output is multi-function, but its functions report the drive: output frequency, output current and similar drive quantities. The transducer's signal is not a quantity the drive generates, so unless the manual documents an analog-output function that follows an analog input, that terminal cannot carry the transducer value at all — a meter hung on it shows whichever drive quantity the output is assigned. Even a documented copy is a re-scaled reproduction through the drive's output circuit, where typical drive analog-output accuracy runs from a few tenths of a percent to one percent of span, stacked on top of the transmitter's own error.
Two further penalties close the case. The analog output is fed from the drive's control circuits, so a powered-down drive leaves the meter dark even though the transmitter is healthy. And the copy inherits whatever scaling the output is configured with, so the meter's calibration now depends on two devices instead of one. The legitimate use of the analog output is the mirror case: when the second display is meant to show a drive quantity such as output frequency, wire it there and scale it to that quantity.
When a signal conditioner is the better path #
Two situations move you off the plain series string. First, a meter whose input is voltage-only — a 0-10 V display, for example — cannot sit in the current loop, and the drive's analog output is not the bridge, for the reasons above. Use a signal conditioner with one current input and two outputs: one output feeds the drive's current input, the other feeds the meter's voltage input, and both still represent the transmitter's true signal. Second, isolation: when the meter lives on a different ground and you do not want the two grounds tied through the loop, an isolating conditioner goes between the loop and the meter.
A conditioner also solves a burden problem. Its input draws little from the transmitter and its outputs re-drive the signal from their own supply, so one transmitter can feed receivers whose combined resistance would otherwise exceed its limit. The ground-fault mess that isolation prevents — one fault dragging a shared analog signal around the panel — is walked through in fixing an analog output ground fault with a signal isolator.
Quarter span on one loop: 8 mA at the drive and the meter #
Inputs, with their source:
- Transmitter: a two-wire unit with a 4-20 mA output span — the transducer this article connects. The example process point sits at 25% of the transmitter's span.
- Drive: the current analog input from the manual's example (AI2), with an illustrative mapping of minimum frequency 0 Hz at live-zero and maximum frequency 60 Hz at full scale — example settings you would enter, not documented defaults.
- Meter: a panel meter with a current input, scaled to show percent of the transmitter's span.
- Loop supply: sized per the transmitter's datasheet; it does not enter this arithmetic.
Rule: a series loop has one current. Kirchhoff's current law leaves the transmitter's current no branch, so every receiver converts the same current with its own scaling.
Arithmetic:
- Loop current: 4 mA + (0.25 × 16 mA) = 4 mA + 4 mA = 8 mA.
- Drive output frequency: the loop sits one quarter of the way up the span, and the illustrative mapping runs 0 Hz to 60 Hz, so 0.25 × 60 Hz = 15 Hz.
- Meter display: 25% of its configured span.
Result: one transmitter current of 8 mA puts both receivers at the same 25% of span and, under the example mapping, runs the drive at 15 Hz.
Decision: wire the string in series whenever both receivers take current directly and the combined receiver resistance stays inside the transmitter's documented maximum loop resistance. Take the drive's analog output only when the second display is meant to show a drive quantity. Add a conditioner when the meter cannot take current or must be isolated.
Questions asked
Does it matter which receiver the loop reaches first?
No. In a series loop the current is identical at every point, so order the devices for the shortest, cleanest wiring and keep polarity strict: current enters each receiver's positive terminal and leaves its negative toward the supply. Route the loop away from the drive's output cables so the current signal does not pick up switching noise.
Can the drive's control terminals power the transmitter?
Only if the drive's manual documents a transmitter supply you can use. The GS3 quick reference lists a low-voltage +15 V terminal on the control wiring, while most two-wire process transmitters specify a 24 V loop supply. Power the transmitter from the supply its datasheet calls for, and treat a drive terminal as a supply only when the manual says it fits the job.
Why do the meter and the drive frequency disagree?
They are two independent scalings of one current. The drive turns the current into a frequency between its minimum and maximum frequency settings; the meter turns it into engineering units over the span you configured. Scale both over the transmitter's live-zero and full scale, then verify at a known point, for example mid-span, where the loop carries 12 mA.
Can the meter stay live while the drive is powered down?
Not reliably on one series string, because an unpowered receiver in the loop path can stop the current or change the burden the transmitter sees. If the display must read while the drive is off, feed the meter from a separately powered signal conditioner instead, so the loop to the drive and the display's input stay independent.