Explainer
Do-More native Ethernet I/O vs ERM EBC mode
Short answer
Keep the installed ERM and EBCs when you move to a Do-more: they run in ERM mode, not native. Only EBC100 modules support the native Ethernet expansion I/O that the CPU sees as local I/O with no interlock ladder logic, and Modbus/TCP stays for endpoints that require it.
On this page
Keep the ERM and EBCs when you replace a 250 or 260 with a Do-more: the Do-more uses them, in ERM mode, and they never become native. Native Ethernet expansion I/O is a separate function, not a mode setting on those modules, and only EBC100 modules support it — the H2-EBC100, the T1H-EBC100 and the BRX Ethernet Base Controller — with the EBC100 in the CPU slot of each remote base. Non-100 EBCs cannot join it and stay on the ERM until they are replaced. Modbus/TCP stays reserved for the cases where the endpoint or the application requires it, such as Terminator I/O served to a Modbus TCP master.
Native expansion I/o needs an EBC100 in every remote base #
Do-more CPUs with an on-board Ethernet port can be configured to use that port to expand the system's I/O, and that is the configuration to build toward wherever you control the choice. The remote base carries an EBC100 slave module in its CPU slot: the H2-EBC100 in a DL205 base, the T1H-EBC100 on Terminator I/O, the BRX Ethernet Base Controller on BRX.
The CPU sees that I/O as local. Interlocking needs no ladder logic, and the native master also addresses remote CTRIO modules and drives. The distance rule comes with the architecture: vendor documentation for DL205 puts each remote base up to 100 meters from the local base, or between Ethernet switches, which is the IEEE 802.3 twisted-pair segment limit restated — 100 m of copper between two devices, with a switch starting a fresh segment.
ERM mode is where the installed hardware lives #
A Do-more runs the ERM world instead of abandoning it. If the site already has an ERM and its EBCs, the Do-more uses them as ERM mode remote I/O: the project carries the legacy I/O mapping and the DLV memory allocation, and the interlock logic remains yours to write and maintain.
The EBC100s are the hinge of the whole question because they work on both sides. The H2-EBC100 is the documented link between an H2 PLC with an H2-ERM module and remote I/O, and the BRX Ethernet Base Controller also expands systems running H2-ERM100 or H4-ERM100 masters, yet those same modules answer a Do-more CPU natively. The non-100 EBCs do not: the native expansion function was not practical to retrofit to them, so their future is the ERM or the parts bin. Read the marking on the module itself; a drawing that says EBC does not say which one is in the rack.
The ERM and EBC modules belong to the same Ethernet protocol family as the ECOM cards, and how the ECOM, EBC and ERM modules differ sorts out which module speaks which. For what that traffic looks like on the wire and how polling loads the network, the ERM and EBC network traffic and polling analysis covers the details.
Where Modbus/TCP still earns its place #
Both the Do-more's Ethernet port and the EBC hardware also speak Modbus/TCP, and there are installations where that is the right interface rather than a fallback. The documented case sits on the Terminator side: the T1H-EBC100 provides the Ethernet link between Terminator I/O and a Modbus TCP master, so a rack that must be polled by a SCADA package or a third-party controller uses Modbus/TCP because the endpoint requires it. The roles are easy to blur here; why Modbus polling is not the same as remote I/O draws the line. Treat Modbus/TCP as an interface decision, not as the price of not having native mode.
The 100 meter limit is per run, not per path #
One example shows how much that matters. A Do-more CPU and an Ethernet switch sit in the main panel. Remote base 1, an EBC100 rack, measures 85 m of cable from that switch: 85 ≤ 100, pass as installed. Remote base 2 measures 112 m on one pull: 112 > 100, fail as a single run. Put a switch in the junction box 60 m along that route and the run splits into 60 m plus 112 − 60 = 52 m, both under 100 m, and the end-to-end path is still 112 m. What the rule counts is copper between two devices, so the switch, not a shorter building, is the fix.
The decision for each installed base #
| What is installed | Decision |
|---|---|
| 250 or 260 with an ERM and non-100 EBCs | Keep the ERM and the EBCs, run ERM mode, and port the interlock logic. Swap to EBC100s only when native behavior is worth the hardware change. |
| ERM with EBC100 bases | Configure the Do-more's on-board Ethernet port for native expansion; the ERM leaves the I/O path. Staying in ERM mode is equally valid when the logic is proven and retesting it buys nothing. |
| New remote base or full retrofit | EBC100 in the CPU slot of every base, native expansion from the CPU's Ethernet port. |
| Terminator I/O polled by a Modbus TCP master | T1H-EBC100 with Modbus/TCP, because the endpoint requires it. |
However the architecture lands, verify it with the machine in a safe state: a forced output on a remote base starts real equipment, so prove inputs at the source and outputs through an approved test condition. The remote I/O commissioning checklist for a modular station walks those steps in order.
Questions asked
Will a Do-more talk to the non-100 EBCs already on my 250 or 260 system?
Yes, through the ERM, in ERM mode. The modules keep working exactly as they did under the 260, and your existing interlock logic ports across instead of being rewritten. What they cannot do is join the native Ethernet expansion I/O, because that function was never added to them.
Do I still need the ERM module once the bases have EBC100s?
Not for native expansion: a Do-more CPU with an on-board Ethernet port addresses the EBC100 bases directly, so the ERM leaves the I/O path. Keep the ERM only if you deliberately stay in ERM mode, which is the right call when the interlock logic is proven and retesting it buys you nothing.
What does the 100 meter figure apply to?
Each copper run between two devices, local base to remote base or device to switch, which is how the DL205 documentation states it and how IEEE 802.3 limits a twisted-pair segment. The end-to-end path can run longer once a switch splits it. Measure the cable that was actually pulled, not the length on the drawing.
Can a Do-more CPU without an on-board Ethernet port do native expansion?
No. The native configuration is the CPU's on-board Ethernet port expanding the system, so a CPU without that port is an ERM-mode machine: it reaches remote I/O through the ERM module, with the mapping and interlock logic that mode requires.