Connecting Wonderware to DH+ PLCs over Ethernet

SCADA and data logging Published 7 min read

Short answer

Put a 1756-DHRIO in an Ethernet-connected ControlLogix chassis and point the Wonderware ABCIP DA server at it: one device definition per DH+ controller, each carrying the full CIP path of chassis IP, module slot, DH+ channel and node address. Commission one known tag end to end before activating the rest. For one or two nodes with serial-speed access acceptable, per-PLC Ethernet-to-serial adapters work, but the PLC serial-port speed caps throughput.

On this page
  1. The path you are building
  2. Choosing the bridge by node count
  3. Installing the 1756-DHRIO
  4. Configuring the ABCIP DA server
  5. Working example: first CIP path to node 17 through slot 4
  6. Where a wrong path shows up
  7. Verifying the whole tag set
  8. Questions asked

The new PC has no bus slot for the old DH+ interface card, so the local DH+ port the HMI used is gone with it. The replacement is a bridge, not a driver swap: install one 1756-DHRIO module in the ControlLogix chassis your Wonderware PC already reaches over Ethernet, run the ABCIP DA server on the new PC with no RSLinx layer between them, and build one device definition per DH+ controller carrying the full CIP path of chassis IP, module slot, DH+ channel and node address. Commission one known tag end to end before activating anything else. The PC-driver side of reaching DH+ without a local card is its own problem, covered in reaching a PLC-5/30 DH+ network from a PC HMI driver. If the new PC doubles as the machine-side SCADA client, the hardware class to specify is an industrial panel PC.

The path you are building #

Every value on the screen crosses six links: the screen object, the Wonderware tag and its access name, the ABCIP DA server device definition, the chassis Ethernet module, the 1756-DHRIO on the backplane, and the DH+ trunk out to the node. Commission them in that order, because each fault hides behind the next one: a wrong binding looks like a dead network, and a dead network looks like a bad tag. What the screen shows tells you where to start.

What you see Check first Likely break
All DH+ values stale or bad quality Server status, then chassis reachability from the PC Server stopped or chassis unreachable
One controller down, the rest reading That device definition's CIP path Wrong channel or node in its route
One value wrong, its neighbors fine The tag's binding and item name Right tag, bound to the wrong provider or item
Values read but never change Server diagnostics against the controller value Inactive subscription, or a source that is genuinely constant

Choosing the bridge by node count #

Node count decides the architecture. More than a few DH+ controllers means one central bridge; one or two can live with an adapter at each PLC. The cheapest central bridge is the chassis you already own: if a ControlLogix chassis is powered and already reachable from the Wonderware PC over Ethernet, you buy the 1756-DHRIO card and nothing else. Building a new standalone gateway means buying its chassis, power supply and Ethernet module alongside the DHRIO.

Configuration Best fit What you accept
1756-DHRIO in an existing Ethernet-reachable chassis Several DH+ nodes and a chassis already on the plant network One added card; one central route for all HMI traffic
New ControlLogix gateway (chassis, power supply, Ethernet module, DHRIO) Several nodes, no suitable chassis exists The full hardware set for the same central route
Standalone DH+ to EtherNet/IP gateway, AN-X(2)-AB-DHRIO class No chassis wanted at all The driver sees an emulated small ControlLogix chassis, and one more configuration tool
Ethernet-to-serial adapter at each PLC (NET-ENI, Digi One IAP) One or two nodes, serial-speed access acceptable Throughput capped by the PLC serial port; a separate configuration point per node
Migrating the processors to Ethernet The long-term removal of DH+ A migration project now, and no bridge in the HMI path afterwards

The bridge does not belong to the HMI alone. OPC clients can read the same legacy controllers through the same arrangement, as in reaching PLC-5 and SLC 500 data through a ControlLogix DH+ bridge, and controller-to-controller traffic rides the same module: routing a ControlLogix MSG to a PLC-5 over DH+ uses the DHRIO in the opposite direction. Size the bridge for the combined load, not for the screen count alone.

Installing the 1756-DHRIO #

  1. Record the node map before touching software: every DH+ controller's node address, and which trunk it sits on. Every CIP path is built from this map.
  2. Install the module in an open slot of the existing chassis and move the plant DH+ trunk onto one of the module's two channels, keeping the existing cabling, shield and termination practice.
  3. Bring the chassis up and clear the bridge first: duplicate node addresses, channel faults and physical-layer errors belong to the module's diagnostics, not to something you compensate for in the HMI.
  4. From the new PC, confirm the chassis answers on Ethernet using the plant's normal check.

Moving the trunk in step 2 takes every controller on it off the HMI and off any inter-controller messages that ride it, so schedule that cutover and confirm nothing on the trunk depends on those messages while it is down.

Configuring the ABCIP DA server #

  1. Create the ABCIP DA server as the communications provider on the new PC. It speaks CIP over Ethernet itself, which is why no RSLinx layer is needed, and sites that kept one in the path have reported tag-count limits and lost communications that cleared when the Wonderware server ran alone.
  2. Point the server connection at the chassis Ethernet module's IP address.
  3. Create one device definition per DH+ controller. Six controllers means six definitions, each with its own route.
  4. In each definition enter the full CIP path: across the backplane to the 1756-DHRIO's slot, out the DH+ channel the trunk is wired to, and down to the node address. Publication 1756-UM514 is the module's user manual; use it for the exact path entry format.
  5. Bind each access name to the intended server and device definition. A screen object reads from the provider named in its binding, so installing another driver never redirects existing tags.
  6. Add one test tag on a value you can watch change, activate that definition alone, and read the server diagnostics before any bulk import.

Working example: first CIP path to node 17 through slot 4 #

The inputs, each from where it comes (these are the example site's values; yours come from the node map and the chassis configuration):

  • Chassis Ethernet module: 192.168.10.20, read from the chassis configuration.
  • 1756-DHRIO: slot 4, the open slot it was installed in.
  • DH+ channel: the channel carrying the plant trunk, because only the wired channel routes anywhere.
  • Destination: an SLC 5/04 at node 17, taken from the recorded node map.
  • Test item: one timer accumulator known to be counting.

The rule in words: a CIP path is a route, not an address. The IP brings the request to the chassis, the next segment crosses the backplane to the slot, the next leaves through the wired channel, and the last picks the node. Four elements, one hop each.

The arithmetic: with six controllers on the trunk, you build six definitions of four elements each, 6 x 4 = 24 route entries. The IP and the slot repeat in every definition, which is 12 identical entries, leaving 2 x 6 = 12 entries that differ per controller: the channel and the node. Those 12 are exactly where a copied definition goes wrong.

Result: with the first definition entered and activated on its own, the test tag reads a live, changing value in the server diagnostics.

Decision: one live, changing test item is the pass condition. Copy that definition for the other five controllers and change only the channel and node entries. If the test item sits at bad quality, stop at this definition and do not import the full tag database onto an unproven route.

Where a wrong path shows up #

Path mistake What you see Correction
Wrong chassis IP Every device on the server fails together Fix the connection destination and retest the server
Wrong slot The route stops on the backplane; devices never answer Read the physical slot and update the route
Wrong DH+ channel Controllers on the wired channel answer, the rest do not Match the route to the channel carrying the trunk
Wrong node address One device fails, or reads a different controller cleanly Compare the route with the recorded node map
Wrong tag binding The server test reads while the screen stays stale Correct the access name's provider and item

The wrong-node row is the one that hides: a healthy read from the wrong controller looks exactly like success, which is why every controller gets one distinctive, changing test value before its tags go live.

Verifying the whole tag set #

  1. Prove every device definition the way the first one was proven: one distinctive, changing value per controller, compared against what the controller actually holds, either by going online with the programming software through the same bridge or by picking a value you can predict.
  2. Import or activate the full tag set only after every definition has passed.
  3. Watch the server diagnostics under full polling. If quality degrades with everything active, stagger the polling per device before you start deleting tags.
  4. File the node map with the server configuration. The next PC replacement rebuilds from it in an afternoon instead of a week.

Questions asked

Does the Wonderware PC still need RSLinx in this setup?

No. The ABCIP DA server speaks CIP over Ethernet directly to the chassis, so RSLinx is a layer the path does not need. Sites that kept RSLinx in the middle have reported tag-count limits and lost communications that cleared when the Wonderware server ran alone. If other software on the PC requires RSLinx, keep its tags on separate access names instead of splitting one tag set across two providers.

Can you program controllers through the same bridge?

HMI traffic and controller-to-controller messaging are the parts that work well through the gateway, but multi-hop pass-through is its own test case. Downloads that cross the bridge and then pass through an SLC to a PanelView on its CH0 DH485 connection are the known weak spot, so prove that path separately before you depend on it and keep the programming route as simple as the HMI route.

How many DH+ controllers can one 1756-DHRIO carry?

The module terminates two DH+ trunks on its two channels, and every controller on a trunk is reached through its own route, so the working limit is how many nodes the trunks already carry and the polling load the server generates. Publication 1756-UM514 is the module user manual to check for the per-network node limit. One module in one chassis is the normal plant answer; add a second module before pushing one past comfortable polling rates.

One controller reads fine and another shows bad quality. Where do you look?

At the last two elements of the failed device's CIP path. A wrong chassis IP or wrong slot takes every device on the server down together, so a single failed controller points at its channel or node entry. Compare the route against the recorded node map. A wrong node that still answers is the dangerous case, because you get another controller's data with good quality.

Is a per-PLC Ethernet-to-serial adapter good enough instead of a bridge?

For one or two nodes where serial-speed access is acceptable, yes. An adapter such as a NET-ENI or Digi One IAP gives each PLC its own Ethernet entry point, and each one becomes a separate configuration and diagnostic item. Throughput is capped by the PLC serial port, so polled SCADA across several adapters scales poorly next to one ControlLogix bridge carrying the whole trunk.

Keep reading

  • Troubleshooting

    Reaching PLC-5 and SLC 500 data through a ControlLogix DH+ bridge

    Yes. An OPC UA server reaches PLC-5 and SLC 500 processors through a ControlLogix Ethernet-to-DH+ bridge when its Allen-Bradley driver documents routed legacy access. Confirm the driver, inventory the bridge modules, build each connection path to the DH+ node, and prove one read — the 1756-DHRIO carries 32 connections per DH+ channel.

    Industrial networks

  • Troubleshooting

    SCADA gateway cycles Connecting and Disconnected: subnet fix

    When one SCADA gateway cycles between Connecting and Disconnected while another reaches the same PLC, the endpoints disagree about addressing. In the case behind this article a /16 site network met a PLC still set to /24: the test gateway reached the PLC, but the PLC sent its replies to a router that was not there. Compare both masks with the AND arithmetic shown, then test the PLC's TCP service port from the gateway host instead of ping.

    Industrial networks

  • Selection guide

    Choosing PLC to SCADA communication over long distances

    For PLC-to-SCADA communication over long distance, choose the transport by reach and connection behavior: fiber Ethernet for a continuous long link (one span rated 2 km), RS-485 where serial fits, extenders or radio on existing pairs, dial-up or leased-line modems on phone service. Direct copper Ethernet fails at 100 m per segment; the SCADA driver or OPC service, not the PLC's ASCII modem commands, carries the protocol.

    Industrial networks